18
+05C003290 - 1.5 - 09.09.2008
Relation between AWG and wire cross-section
AWG
Cross-section (mm
2
) Current
20
0.5
2
15
1.5
6
14
2.5
8
pLAN network/user terminal connection
type
RS485 half-duplex asynchronous
transmission speed
62.5 Kbps or 115.2 Kbps, selectable via software
terminal connector
6 pin telephone (J10)
pLAN network/graphic terminal/aria terminal connector 3 pin plug-in connector (J11)
The maximum distance between the pCO and user terminal is shown in the following table.
cable type
power supply distance
power supply
telephone
50 m
taken from the pCO (150 mA)
AWG24 shielded cable
200 m
taken from the pCO (150 mA)
AWG20/22 shielded cable
500 m
separate power supply via TCONN6J000
The maximum distance between two pCO
3
controllers with AWG20/22 shielded cable is 500 m.
Note:
• a maximum of one terminal (pCOT, pCOI, pGD0, pGD1) can be connected, or two terminals but without using
use the backlighting on display. One version of the pCO
3
features optically-isolated connection to the pLAN
network.
• the graphic terminal and aria terminal should be always powered with a separate power supply.
• the 21 Vdc present at +Vterm (J24) can be used to power an external terminal with a maximum input of 2
W. Only one terminal can be connected (for example PLD terminal or ARIA terminal) in addition to the one
connected to terminal J10.
Other specifications
storage conditions
-40T70 °C, 90% RH non-condensing
operating conditions
-25T70 °C, 90% RH non-condensing
index of protection
IP20, IP40 front panel only
environmental pollution
normal
class according to protection against electric shock
to be incorporated into Class I and/or II appliances
PTI of the insulating materials
250 V
period of stress across the insulating parts
long
type of action
1C
type of disconnection or microswitching
microswitching
category of resistance to heat and fire
category D (UL94 - V0)
immunity against voltage surges
category 1
ageing characteristics (operating hours)
80,000
no. of automatic operating cycles
100,000 (EN 60730-1); 30,000 (UL 873)
software class and structure
Class A
category of immunity to voltage surges (CEI EN 61000-4-5) Category III
The device is not designed to be hand-held
WARNING
• for applications subject to strong vibrations (1.5 mm pk-pk 10/55 Hz), secure the cables connected to the µ
pCO
3
using clamps placed around 3 cm from the connectors
• If the product is installed in industrial environments (application of the EN 61000-6-2 standard) the length of
the output connections must be less than 30 m.
• installation must be performed according to the standards and legislation in force in the country where the
appliance is used;
• for safety reasons the appliance must be housed inside an electrical panel, so that the only accessible part is the
display and the control keypad;
• all the very low voltage connections (analogue and digital inputs at 24 Vac/Vdc, analogue outputs, serial bus
connections, power) must have reinforced or double insulation from the mains;
• in the event of malfunctions do not attempt to repair the appliance, but rather contact the REHAU service
centre;
• in domestic environments, the connection cable between the pCO
3
and the terminal must be shielded.