26
ENG
“MCmultizone” +030221981 - rel. 2.3 - 09.12.2014
cabinet
distribution
maint
enanc
e
Important:
the operations described in this menu must only be
carried out by qualifi ed personnel.
From the main screen press:
•
PRG to access the main menu;
•
DOWN to move to the maintenance menu;
•
ENTER to move to the password;
•
UP/DOWN to enter the password “77“
•
ENTER to access the selected menu;
•
UP or DOWN to move between the submenus;
•
ENTER to select parameter and move between the parameters;
•
UP/DOWN to modify the parameter;
•
ENTER to confi rm the selected parameter and go to the next
parameter;
•
ESC to return to the previous menu.
Maintenance menu screens:
1. Reset conf.
2. System info
3. Manual procedure
4. Hour counter
5. Alarm log
8.1 Reset confi gurations
Confi guration
Functions:
•
save the set confi gurations,
•
recall the saved confi guration
parameter
range
default
save confi gurations
YES/NO
NO
load confi guration
YES/NO
NO
Default parameters
Functions:
•
restore default parameters
•
code
parameter
range
default
restore default parameters
YES/NO
NO
code
display only
8.2 System information (read only)
information
display
Boot
read only
Bios
read only
Code
read only
Version
read only
Date
read only
8.3 Manual procedure
Important:
these operations must only be performed by qualifi ed
personnel, incorrect use may cause serious damage.
These procedures are used to manually test the main functions and
operations of the humidifi er.
Manual procedure (1/2)
parameter
range
default
manual procedure (*)
YES/NO
NO
air valve
ON/OFF
OFF
water valve
ON/OFF
OFF
drain valve
ON/OFF
OFF
valve at end of line
ON/OFF
OFF
production status
ON/OFF OFF
Manual procedure (2/2)
parameter
range
default
alarm relay
YES/NO
NO
proportional output
ON/OFF
OFF
proportional valve
ON/OFF
OFF
(*) To activate the individual manual procedures, fi rst enable the manual
procedure parameter.
8.4 Hour counter
parameter
range/display
hours production
display
reset hours
YES/NO
8.5 Alarm log
Recorded trace of the alarms (events) that have been activated. The
humidifi er memory can record up to 200 events (complete with
description and date, press DOWN to scroll the list).
parameter
display
Alarm
event description
Log deleted
Time
hh:mm
Date
dd/mm/yy
8. MAINTENANCE MENU