4.4 Drain
water
•
this contains the same substances dissolved in the supply water,
however in larger quantities;
•
it may reach a temperature of 100 °C;
•
it is not toxic and can be drained into the sewerage system, category
3, EN 1717.
4.5 Technical
specifi cations
KUE*(R, 1)*
KUES2* KUET2* KUES3* KUET3* KUET4*
Steam:
fl ow-rate kg/h (lbs/hr)
1,5...3
(3..3/6.6)
5 (11)
5...8
(11/17.6)
9 (19.8)
10...15
25...45
connection: D mm (‘‘)
23/30
(0.9/1.2)
30 (1.2)
40
outlet pressure limits
(Pa/PSI)
0...500 (0...0.072)
0...2300
Supply water:
connection
G 3/4’’ M
temperature limits (°C/°F)
1...40 (33.8...104)
pressure limits
0,1...0,8 (1...8 BAR, 14.5...116 PSI)
hardness limits ppm
CaCO3(°fH)
≤ 400 (40)
instant fl ow-rate l/min
(gal/hr)
0,6 (9,5)
1,2 (19)
4
Drain water:
connection: D mm (‘‘)
32 (1.2)
40
typical temperature (°C/°F)
≤ 100 (212)
instant fl ow-rate I/min
(gal/hr)
10 (159)
22,5
Environmental conditions:
ambient operating
temperature (°C/°F)
1...50 (33.8...122)
ambient operating
humidity (% rH)
10...90 (non condensante)
storage temperature
(°C/°F)
-10T70 (14T158)
storage humidity (% rH)
5...95
index of protection
(IEC EN 60529)
IP00
Tab. 4.c
4.2 TAM (current transformer)
confi gurations
one cable turn
one of two cables
of the same phase
two cables of the same phase
one cable
on “bouble turn” mode
three cable turns
of the same phase
CPY*
700
500
300
100
700
500
300
100
700
500
300
100
700
500
300
100
700
500
300
100
CP*
700
500
300
100
a
b
c
d
e
Fig. 4.c
4.3 Supply water
Only use mains drinking water with:
•
pressure between 0.1 and 0.8 MPa (1 and 8 bars), temperature between
1 and 40 °C and an instant fl ow-rate no lower than the rated fl ow of the
fi ll solenoid valve, the connection is G 3/4’’ M;
•
hardness no greater than 400 ppm of CaCO3 (40 °fH), conductivity
range: 75-1250 μS/cm;
•
no organic compounds.
supply water characteristics
unit of
measure
normal
water
water with low
salt content
min.
max. min.
max.
Hydrogen ions (pH)
7
8,5
7
8,5
Specifi c conductivity
at 20 °C (σR, 20 °C)
μS/cm
350
1250 75
350
Total dissolved solids (TDS)
mg/l
(1)
(1)
(1)
(1)
Dry residue at 180°C (R180)
mg/l
(1)
(1)
(1)
(1)
Total hardness (TH)
mg/l CaCO3
100 (2) 400
50 (2)
160
Temporary hardness
mg/l CaCO3
60 (3)
300
30 (3)
100
Iron + Manganese
mg/l Fe+Mn
0
0,2
0
0,2
Chlorides
ppm Cl-
0
30
0
20
Silica
mg/l SiO2
0
20
0
20
Residual chlorine
mg/l Cl2
0
0,2
0
0,2
Calcium sulphate
mg/l CaSO4
0
100
0
60
Metallic impurities
mg/l
0
0
0
0
Solvents, thinners, detergents,
lubricants
mg/l
0
0
0
0
Tab. 4.b
(1)
= values depend on the specifi c conductivity; in general:
TDS
0,93 * σ
R, 20 °C
; R
180
0,65 * σ
R, 20 °C
(2)
= not less than 200% of the chloride content in mg/l CL
-
(3)
= not less than 300% of the chloride content in mg/l CL
-
There is not reliable relationship between hardness and conductivity of
the water.
Important:
•
do not treat the water with softeners, this may cause the entrainment
of foam, aff ecting the operation of the unit;
•
do not add disinfectants or anticorrosive compounds to the water, as
these are potential irritants;
•
the use of well water, industrial water or water from cooling circuits
and, in general, any potentially chemically or bacteriologically
contaminated water is not recommended.