11.11 Modbus® protocol on the UEY boards
The Modbus® protocol can be selected using parameter C7 (see “Serial
connection parameters”).
Chapter 7 shows a list of variables and the corresponding addresses.
For multiple read/writes, the maximum number of “Register” or “Coil”
variables is 20.
The following functions are available::
•
MB_READ_COIL_STATUS 1:
used to request the status (ON or OFF) of a
certain number of “Coil” variables (binary, 1 bit), starting from the specified
address. Broadcast mode is not allowed.
•
MB_READ_INPUT_STATUS 2:
operationally identical to the above.
•
MB_READ_HOLDING_REG 3:
used to request the value of a consecutive
block of “Register” variables (numeric, 16 bit). Broadcast mode is not
allowed
.
•
MB_READ_INPUT_REG 4:
operationally identical to the above.
•
MB_FORCE_SINGLE_COIL 5:
used to set the status of an individual “Coil”
variable (binary, 1 bit) to ON or OFF (specifying the address of the bit in
question). Broadcast mode is allowed.
•
MB_PRESET_SINGLE_REG 6:
used to set the value of an individual
“Register” variable (numeric, 16 bit). Broadcast mode is allowed.
•
MB_FORCE_MULTIPLE_COIL 15:
used to set the status of a consecutive
block of “Coil” variables (binary, 1 bit) (specifying the number of bits and
number of bytes). Broadcast mode is allowed
•
MB_PRESET_MULTIPLE_REG 16:
used to set the value of a consecutive
block of “Register” variables (numeric, 16 bit). Broadcast mode is allowed.
11.12 Exceptions managed
01 illegal function
02 illegal data address
03 illegal data value
Содержание humiSteam UE005
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 27: ...27 UE BASIC 08C0042EZ rel 1 0 16 10 2017 CN 10 䐥ഴ 10 1 㧞㼁UE005 UE015ㅴ㼀㵝 Fig 10 a 䐹䄋 䇻TAM㞅䐤 㑍ㅴ 㤌 㾂ㅻ11 1 ...
Страница 28: ...28 UE BASIC 08C0042EZ rel 1 0 16 10 2017 CN 10 2 㧞㼁UE025 UE065ㅴ㼀㵝 Fig 10 b 䐹䄋 䇻TAM㞅䐤 㑍ㅴ 㤌 㾂ㅻ11 1 ...
Страница 42: ......
Страница 44: ......
Страница 79: ......