Direct version for room applic. +0300062EE - rel. 1.4 - 24.09.2020
“I”
integer variables (Modbus®:
R
EGISTE
R
S)
R
/W
CA
R
EL
Modbus®
89
216
Secondary humidifier 1 status
R
92
219
Secondary 1 parameter d3: Operating hour counter
R/W
93
220
Secondary 2 firmware release
R
95
222
Secondary humidifier 2 status
R
98
225
Secondary 2 parameter d3: Operating hour counter
R/W
99
226
Secondary 3 firmware release
R
101
228
Secondary humidifier 3 status
R
104
231
Secondary 3 parameter d3: Operating hour counter
R/W
105
232
Piezoelectric transducer operating hour counter
R
106
233
Parameter d6: Time remaining to end of piezoelectric transducer life
R/W
107
234
Parameter AF: Piezoelectric transducer working life
R/W
112
239
Parameter bH: Enable TH probe as humidity / dew point limit
R/W
113
240
Parameter SL: Humidity / dew point limit set point
R/W
114
241
Parameter bP: proportional band for control with probe TH or external probe
R/W
115
242
Parameter bL: limit proportional band
R/W
117
244
Parameter d7: Secondary unit production management
R/W
Tab. 10.f
“D”
digital variables (Modbus®: COILS)
R
/W
“D”
digital variables (Modbus®: COILS)
R
/W
CA
R
EL
Modbus®
CA
R
EL
Modbus®
2
1
Just-started flag
R
26
25
Manual drain
R/W
3
2
Humidifier ready to produce
R
27
26
Disable via serial
R/W
4
3
Set point reached
R
28
27
Reset counter
R/W
5
4
Green LED
R
29
28
Resetting the alarms
R/W
6
5
Red LED
R
30
29
Washing due to inactivity activated
R
7
6
Yellow LED
R
30
31
Status of dipswitch 8: modulation in parallel/series
R
8
7
Remote OnOff
R
31
30
Functional test completed
R
9
8
Low level
R
33
31
Unit of measure
R/W
10
9
High level
R
34
33
Secondary 1 online
R
11
10
Aux level
R
35
34
Secondary 2 online
R
12
11
Autotest completed
R
36
35
Secondary 3 online
R
14
12
BMS serial in Tlan mode
R
37
36
Enable control via serial
R/W
15
14
TAM enabled
R
38
37
Washing activated via serial
R/W
16
15
TAM reading
R
39
38
Skip autotest or washing while running
17
16
Terminal connected
R
43
42
Reset piezoelectric transducer hour counter
R/W
18
17
Production in progress
R
44
43
Backup unit ready to produce
R
19
18
Fill
R
46
45
Production limitation in progress (limit probe function)
R
20
19
Drain
R
47
46
On/off control via Main/Secondary network
R/W
21
20
Trasduttore1
R
49
48
On/off control from Main unit keypad
R/W
22
21
Trasduttore2
R
50
49
On/off control from Secondary unit 1 keypad
R/W
23
22
Fan
R
51
50
On/off control from Secondary unit 2 keypad
R/W
24
23
Alarm relay
R
52
51
On/off control from Secondary unit 3 keypad
R/W
25
24
Auxiliary relay
R
54
53
Parameter bn: disable alarm buzzer
R/W
Tab. 10.g
10.2 Production control via network
To control production via a network connection, configure the humidifier
using following parameters:
digital
27
, digital
37
and integer
6
0
(
Modbus
188)
When D37 is set to 1, the humidifier ignores the external control signals
(external controller or probes) and uses the value of integer 60 (Modbus
188) as the control signal. Humidity production can be managed in two
modes:
To manage production as a percentage:
• Set D 37 = 1;
• Set parameter A0 = 1 (Carel 20, Modbus 148, proportional mode);
• Set Carel integer variable 60 (Modbus 188) to the desired level (0-1000
= 0-100.0%).
To manage production with a humidity probe managed by the Main unit:
• Set D 37 = 1;
• Set parameter A0 = 2 (Carel 20, Modbus 148, humidity probe mode);
• Set Carel integer variable 60 (Modbus 188) to the desired level (0-1000
= 0-100.0 rH%);
• Set Carel integer variable 52 (Modbus 180) to the desired humidity set
point.
When D37 is set to 1, if communication is lost for the number of seconds
set by parameter C4, the “Main Offline” alarm is activated (see Alarm table)
and production stops.
Production can be activated/deactivated via digital parameter D27 (see
the Parameter table).
If D27 = 1 the humidifier is disabled and production stops
if D27 = 0 the humidifier is enabled and production is activated.
D27 is independent from the status of D37.
10.3 Washing cycle activation via network
A washing cycle can be performed at any time by managing digital
variable 38.
Setting the variable to 1 will immediately activate a washing cycle, even
if the unit is in standby, and even if both automatic washing and washing
due to inactivity are disabled by their corresponding parameters.
The variable will keep the value 1 throughout the duration of the washing
cycle, and will automatically be reset at the end of the cycle.