23
ENG
Direct version for room applic. +0300062EE - rel. 1.4 - 24.09.2020
10. HUMIDIFIER CONTROL VIA NETWORK
The variables shown in the list are a set of all the internal variables.
DO NOT CONFIGU
R
E ANY VA
R
IABLES THAT A
R
E NOT SHOWN IN THE TABLE, OTHE
R
WISE
HUMIDIFIE
R
OPE
R
ATION MAY BE AFFECTED.
The serial connection (M11) is configured by default with the following parameters:
- Address 1
- Baud rate 19200 bps
- Frame 8,N,2 (not modifiable)
NO
TICE:
it is recommended to set on the supervisor (Main) the maximum waiting time for a response from humiSonic - after being queried by the supervisor - of
at least 500 ms.
10.1 Supervisor variable list
“A”
analogue variables* (Modbus®:
R
EGISTE
R
S)
R
/W
CA
R
EL
Modbus®
1
0
Param. d0: TH probe temperature reading
R
2
1
Param. d1: TH probe humidity reading
R
3
2
Param. d2: Probe reading
R
4
3
Param. d5: Instant production
R
9
8
Param. d8: Dew point
R
“I”
integer variables (Modbus®:
R
EGISTE
R
S)
R
/W
CA
R
EL
Modbus®
1
128
Level access password
R/W
7
134
Humidifier status
0:
disabled/standby
3:
fill
6:
alarm reset
1:
autotest
4:
production
7:
wash
2:
initialisation
5:
drain
8:
cleaning procedure
R
2
129
Firmware release
R
15
142
Alarms, see chap. ALARMS:
bit0:
Alarm E0
bit4:
Alarm EP
bit8:
Alarm EE
bit12:
Alarm ES3
bit1:
Alarm Et
bit5:
Alarm PU
bit9:
Alarm CL
bit13:
Alarm OFL
bit2:
Alarm EF
bit6:
Alarm H ¯
bit10:
Alarm ES1
bit14:
Alarm EL
bit3:
Alarm Ed
bit7:
Alarm H_
bit11:
Alarm ES2
bit15:
Alarm EtL
R/W
20
147
Parameter A0: Operating mode
R/W
21
148
Parameter A2: Type of external probe
R/W
22
149
Parameter A3: Probe minimum
R/W
23
150
Parameter A4: Probe maximum
R/W
24
151
Parameter A5: Probe offset
R/W
25
152
Parameter A6: Fan off delay time
R/W
26
153
Parameter A7: Fan speed
R/W
27
154
Parameter A8: Maximum evaporation time for no production alarm
R/W
28
155
Parameter A9: Minimum evaporation time for no production alarm
R/W
29
156
Parameter b0: Operating options
R/W
30
157
Parameter b1: Time between two washing cycles
R/W
31
158
Parameter b2: Inactivity time for washing on next start
R/W
32
159
Parameter b3: Washing time (fill + drain)
R/W
33
160
Parameter b4: Start delay time
R/W
34
161
Parameter b5: Operating hours for CL alarm
R/W
35
162
Parameter b6: Operating hours for CL alarm
R/W
36
163
Parameter b7: Piezoelectric transducer On/Off control range
R/W
37
164
Parameter b8: Probe disconnected delay
R/W
38
165
Parameter b9 TAM OFF delay
R/W
39
166
Parameter bA: Maximum fill time
R/W
40
167
Parameter bb: Refill time in evaporation
R/W
41
168
Parameter bC: Maximum drain time
R/W
42
169
Parameter bd: Drain opening time to completely empty tank
R/W
43
170
Parameter bE: Delay time after measuring low level for refilling
R/W
44
171
Parameter C0: Default display (terminal)
R/W
45
172
Parameter C1: Parameter A0: Baud rate
R/W
46
173
Parameter C2: tLAN address (if 0 Main controller)
R/W
47
174
Parameter C3: Serial address
R/W
48
175
Parameter P0: Maximum flow-rate
R/W
49
176
Parameter P1: Proportional control hysteresis
R/W
50
177
Parameter P2: Low humidity alarm threshold
R/W
51
178
Parameter P3: High humidity alarm threshold
R/W
52
179
Parameter SP: Humidity / dew point set point
R/W
53
180
Parameter d3: Operating hour counter
R
54
181
Parameter d4: Unit hour counter (not resettable)
R/W
60
187
Request via serial (if digital 37 set)
R/W
62
189
Identification of variable on Secondary unit to read/write from supervisor (see paragraph “Supervisor control”)
R/W
63
190
Value of variable on Secondary unit identified by integer 62 (see paragraph “Supervisor control”)
R/W
65
192
Parameter C4: Timeout for Main serial offline
R/W
69
196
AA: Waiting time for retry
R/W
70
197
Ab: Percentage of A8 for carrying out level test
R/W
71
198
Pn: Minimum production
R/W
72
199
bF: Drain activation delay in standby
R/W
73
200
AC: Maximum time to measure level when refilling
R/W
74
201
Ad: Maximum time to measure high level
R/W
82
209
AE: Restart fan time in standby for built-in probe reading
R
87
214
Secondary 1 firmware release
R