9.1 Troubleshooting
Note
: if the problem identified cannot be solved using the following
guide, contact CAREL technical service.
1.
Firstly, check the humidifier and the surrounding area.
Problem
Cause
Check
Solution
No atomised water
production
Power supply
Humidifier switch in the OFF
position
Check the switch
Switch ON
No power
Measure the voltage at the humidifier
input terminals
Connect power
Power supply fault
Measure the voltage at the power supply
output terminals
Replace the power supply
Feedwater system
Valve closed upstream
Check
Open the valve
The quantity of atomised
water is too low
Power supply
Low power supply voltage
Check the voltage at the power supply
output terminals
Replace the power supply, if
damaged
Feedwater system
Water level during production
is too high and overflowing
Check visually
See table 2)
Other
The humidifier is not installed
horizontally
Check visually
Adjust
No atomised water
production
Dust and foreign matter accumulated in the tank (*)
Clean the inside of the tank
Transducer deterioration
The average life of the transducer is
around 10,000 to 15,000 operating hours
Replace
The quantity of atomised
water is too low
Dust and foreign matter accumulated in the tank (*)
Check a view the inside of the tank
Clean the inside of the tank
and replace the transducers
Scale build-up on the surface of the piezoelectric transducers (*)
Tab. 9.b
(*) These malfunctions can be avoided by carrying out preventive
maintenance.
2.
If the cause has not been identified with the previous checks, there
may be faulty components. Check the inside of the humidifier.
Problem
Cause
Check
Solution
No atomised water
production
Feedwater system
Float level sensor fault
Empty the tank, remove the electronic board
and check continuity of the level sensor
Contact service to replace the
level sensor
Float level sensor blocked
Clean the sensor. If normal
operation is not restored, replace
Fill valve fault
No water filled even when the tank has been
emptied
Replace the valve
Clean the sensor. If normal
operation is not restored, replace
Other
The fan cables are loose or
detached
Check connection after removing the
humidifier cover
Restore correct connection to the
terminals
The quantity of atomised
water is too low
Water level overflow
Float level sensor blocked
If the water level in the tank reaches the
overflow pipe, remove the connector from
the control board and check continuity of the
level sensor
If there is continuity, contact
service to replace the level sensor
Fill valve fault
Water is filled even after switching off the
appliance
Replace the fill valve
Tab. 9.c
Содержание humiSonic UU02
Страница 2: ......
Страница 4: ......
Страница 6: ...6 ITA Direct version for room applic 0300062IE rel 1 1 16 11 2017 ...
Страница 34: ...34 ITA Direct version for room applic 0300062IE rel 1 1 16 11 2017 Note ...
Страница 36: ......
Страница 38: ...6 ENG Direct version for room applic 0300062IE rel 1 1 16 11 2017 ...
Страница 66: ...34 ENG Direct version for room applic 0300062IE rel 1 1 16 11 2017 Notes ...
Страница 67: ......