WARNING:

 separate as much as possible the probe and digital input signal cables from the 

cables carrying inductive loads and power cables to avoid possible electromagnetic disturbance. 
Never run power cables (including the electrical panel wiring) and signal cables in the same 
conduits.

NO POWER 

& SIGNAL 

CABLES 

TOGETHER

READ CAREFULLY IN THE TEXT!

Table of parameters

Parameter

Min. Max. Def.

UOM

PS

PASSWORD

0

99

22

-

/

PROBE PARAMETERS

/5

Select °C / °F ( 0 = °C; 1 = °F)

0

1

0

-

/6

Disable decimal point (1 = disabled)

0

1

0

-

/C1

Probe calibration (OFFSET)

-50.0 50.0

0.0

°C/°F

r

CONTROL PARAMETERS

St

Setpoint (control temperature)

-50.0 90.0

3.0

°C/°F

rd

Control differential (hysteresis)

0.0

19.0

2.0

°C/°F

c

COMPRESSOR PARAMETERS

c0

Comp. and fan start delay after start-up

0

100

0

min

c1

Min. time between successive comp. starts

0

100

1

min

c4

Compressor safety (duty setting)

0

100

15

min

d

DEFROST PARAMETERS

d0

Type of defrost (0 and 1= defrost by temperature; 2, 3 and 
4= defrost by time)

0

4

2

-

dI

Interval between defrosts

0

199

6

h/min

dP

Max. or effective defrost duration

1

199

20

min/s

d4

Defrost when the instrument is switched on (1= activated)

0

1

0

-

d6

Disable temperature display during defrost (1= display disabled)

0

1

1

-

A

ALARM PARAMETERS

A0

Alarm differential

-20.0 20.0

-2.0

°C/°F

AL

Low temperature alarm threshold/deviation

-50.0 250.0 -5.0

°C/°F

AH

High temperature alarm threshold/deviation

-50.0 250.0 15.0

°C/°F

Ad

Low and high temperature alarm delay

0

199

0

min

H

OTHER SETTINGS

H2

Enable keypad
0= keypad disabled
1= keypad enabled
2= keypad enabled except for ON/OFF function

0

2

1

-

EY

Restore the Default settings

0

1

0

-

Tab. 5

Table of alarms

Alarm code

Description

Parameters involved

E0

probe 1 error= control

-

LO

low temperature alarm

[AL] [Ad]

HI

high temperature alarm

[AH] [Ad]

EE

unit parameter error

-

EF

operating parameter error

-

dF

defrost running

[d6=0]

Pd

defrost awaiting execution

-

Tab. 6

How to restore the Default settings (refer to table of parameters in this 
sheet)

1)  Access parameter EY (entering password 22 and scroll parameter list).
2)  Select the desired confi guration:

• EY = 0         

 No changes;

• EY = 1         

 Restore of default settings (refer to Table of parameters in this sheet);

3)  Exit the setting procedure (holding SET button for more than 3 s).
4)  Power off the device and then power it on again while holding SET button.
5)  The display shows “CE” to indicate that the confi guration has been restored.

Switching the device ON/OFF

Press UP for more than 3 s. The control and defrost algorithms are now disabled and the 
instrument displays the message “OFF” alternating with the temperature read by the set probe.

Manual defrost

Press DOWN for more than 3 s (the defrost starts only if the temperature conditions are valid).

Continuous cycle

Press UP and DOWN together for more than 3 s.

Technical specifi cations

power supply 

115 Vac +10 / -15% 50/60 Hz
230 Vac -10% +15% 50/60 Hz

rated power

3 W

input

NTC probe

relay output

16 A relay     UL: 12 A resistive 5 FLA, 30 LRA 240 Vac  30,000 cycles
 

      EN60730-1: 12(2)A or 10(4)A (N.O. only) 250 Vac 100000 cycles;

type of probe 

Std CAREL NTC 10 K



at 25 °C

power supply/ 
relay output 
connector

- screw terminals pitch 5mm for cables with cross-sect. from 0.5 mm

2

 to 1.5 mm

2

12 A max;

probe connector

screw terminals:
- 2-pin pitch 5mm for models with 1 probe (cable cross-section from 0.5 mm

2

 to 1.5 

mm

2

); 12 A max;

assembly

using screws from the front or with brackets at the rear

display

LED display, 2 digits plus sign, decimal point and compressor icon 

keypad

3 buttons with membrane

operating conditions

-10T50 °C - humidity <90% rH non-condensing

storage conditions

-20T70 °C - humidity <90% rH non-condensing

range of measurement

-50T90 °C (-58T194 °F) - resolution 0.1 °C/°F

front panel index of protection

panel installation with IP65 type 1

case

plastic terminal, 81x36x38 mm

classifi cation according to protection 
against electric shock

Class II

environmental pollution

II

PTI of the insulating material

250 V

period of stress across the insulating parts

long

category of resistance to heat and fi re

category D (UL94 - V0)

immunity against voltage surges

category 1

type of action and disconnection

micro-disconnection 1C

no. of relay automatic operating cycles 

EN60730-1:   100,000 cycles
UL: 

       30,000 cycles (250 Vac)

software class and structure

Class A

cleaning the instrument

Only use neutral detergents and water

cable max. lenght

serial: 1 km
probes: 30 m
relay: 10 m

Tab. 7

Note: 

do not run the power cable less than 3 cm from the bottom part of the device or from the probes; 

for 

the connections only use copper wires

Safety standards

compliant with the relevant European standards. Installation precautions:
•  the connection cables must guarantee insulation up to 90 °C;
•  ensure a space of at least 10 mm between the case and the nearby conductive parts;
•  digital and analogue input connections less than 30 m away; adopt suitable measures for separating the 

cables so as to ensure compliance with the immunity standards;

Secure the connection cables of the outputs so as to avoid contact with very low voltage parts.

IMPORTANT WARNINGS

The CAREL product is a state-of-the-art device, whose operation is specifi ed in the technical documentation 
supplied with the product or can be downloaded, even prior to purchase, from the website www.carel.com.
The customer (manufacturer, developer or installer of the fi nal equipment) accepts all liability and risk relating 
to the confi guration of the product in order to reach the expected results in relation to the specifi c fi nal instal-
lation and/or equipment. The failure to complete such phase, which is required/indicated in the user manual, 
may cause the fi nal product to malfunction; CAREL accepts no liability in such cases. The customer must use 
the product only in the manner described in the documentation relating to the product. The liability of CAREL 
in relation to its products is specifi ed in the CAREL general contract conditions, available on the website www.
carel.com and/or by specifi c agreements with customers.