pAD +030220873 - rel. 1.2 18.01.2013  

28

 

5.4 

Setting the temperature set point 

To set the temperature set point in the zone controlled by the 
pAD terminal. 

 Press 

the 

 or 

 buttons; the main area of the pAD will 

display the current set point. 

 

To the right of the value, the 

 symbol comes on 

(flashing). 

 Pressing 

,

 again changes the set point. 

 

The procedure for setting the temperature set point ends 
automatically 3 seconds after the last button was pressed. 

 

 

If the setting of the temperature set point is not accessible 
to the user, the lock symbol   will be displayed. 

 

If time bands have been configured in pAD mode (see the 
paragraph on “Time bands”) and these are active, the new

 

value will only be valid until the end of the current time 
band. If, on the other hand, the time bands are managed 
directly by the pCO controller, these will be controlled 
exclusively by the pCO, based on the selected set point. 

 
 

5.5 Humidify 

 

 

 

To activate humidification in the zone controlled by the pAD 
terminal (if the model of pAD purchased features the humidity 
sensor) 

 

Make sure that the system is operating (see the paragraph 
“system ON/STANDBY”). 

 

Press MODE repeatedly until the display shows the 
HUMIDIFY symbol 

 

The possibility to activate humidification in the zone 
managed and functions of the buttons depend on the 
configuration set by the controller application program. 

 

5.6 Dehumidify 

 

 

 
To activate dehumidification in the zone controlled by the pAD 
terminal (if the model of pAD purchased features the humidity 
sensor). 

 

Make sure that the system is operating (see the paragraph 
“system ON/STANDBY”). 

 

Press MODE repeatedly until the display shows the 
DEHUMIDIFY symbol 

 

The possibility to activate dehumidification in the zone 
managed and functions of the buttons depend on the 
configuration set by the controller application program. 

 

5.7 

Setting the humidity set point 

 

 

 

To set the humidity set point in the zone controlled by the pAD 
terminal. 

 

Press the button associated with the humidity set point 
setting 

 (default KEY 3) 

 

Press the buttons 

 or 

 buttons; the main area of the pAD 

will display the current set point. 

 

To the right of the value the 

 and 

 symbols come 

on (the latter flashing). 

 Pressing 

,

 again changes the set point. 

 

The procedure for setting the humidity set point ends 
automatically 3 seconds after the last button was pressed. 

 

If the setting of the humidity set point is not accessible to 

the user, the lock symbol   will be displayed.

 

 

 

5.8 Sleep 

mode 

 

 

 

This mode is used to increase the room temperature set point in 
cooling (an decrease it in heating) at certain times. It is useful for 
improving comfort and ensuring energy saving. 
 
Procedure: 
Press the 

 button (KEY4 by default). If the mode is already active, 

it is deactivated. If not already active, it will be activated, and the 

 

symbol will be displayed. The 

 field displays “1

HR

”, flashing, 

indicating that “Sleep” mode will be active for one hour. 
Pressing the button again within 3 seconds increases the duration of 
“Sleep” mode, up to a maximum of 9 hours. 

 

The number shown in the 

 field is rounded up to the 

next hour, that is, if the remaining time is “1 hour and 1 
minute”, “2

HR

” is displayed.

 

The Sleep function also features a differential, which represents the 
temperature difference from the set point in the area managed by the 
pAD. 
To set the differential:  

 Hold 

the  button (KEY4 by default) for 3 seconds. 

 the 

 field becomes the Sleep differential setting 

(the value displayed corresponds to the current operating 
mode set during configuration, or the default value, and the 

 field displays “

diff

”). 

 

Set the desired value using the UP/DOWN buttons. The 
range of values available is from 0.0 (disabled) to 10.0 
°C/°F (Default at startup = 2.0).  

 

Press the NIGHT button again to confirm or wait 3 seconds 
for automatic confirmation. 

Содержание ADPB003000

Страница 1: ...pAD Ambient Display terminal User manual...

Страница 2: ......

Страница 3: ......

Страница 4: ...CAREL CAREL CAREL CAREL www carel com CAREL CAREL CAREL CAREL CAREL CAREL CAREL CAREL www carel com CAREL CAREL 2002 96 EC 27 2003 13 2005...

Страница 5: ...1 9 1 1 pAD 9 1 2 pAD 9 1 3 pAD 9 2 10 2 1 10 2 2 10 2 3 10 3 11 3 1 11 3 2 11 3 3 11 4 12 5 13 5 1 13 5 2 13 5 3 13 5 4 14 5 5 14 5 6 14 5 7 14 5 8 14 5 9 15 5 10 15 6 16 7 17...

Страница 6: ...6...

Страница 7: ...013 9 1 1 1 pAD pAD pCO pAD pLAN RS485 1 2 pAD pAD 3 pCO pAD pCO pAD 1 3 pAD ADPB003000 pAD NTC ADPB003010 pAD NTC ADPC003000 pAD NTC ADPC003010 pAD NTC ADPG003000 pAD NTC ADPG003010 pAD NTC ADPH00300...

Страница 8: ...30220873 rel 1 2 18 01 2013 10 2 2 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 2 2 KEY1 KEY6 1 KEY 1 POWER 2 mode KEY 2 MODE 3 KEY 3 HUM 2 4 KEY 4 NIGHT 5 KEY 5 CLOCK 1 6 KEY 6 TEMP 7 8 1 2 ADPC ADPG ADPH 2 3...

Страница 9: ...pAD 030220873 rel 1 2 18 01 2013 11 3 3 1 pAD CEI C 431 IEC 670 3 2 G G0 2 0 5 1 5 2 250 mAT G 2 4 G0 pAD G0 G0 G pAD pAD pAD 3 3 RS485 3 AWG20 22 500 90 5 pLAN RS485 pLAN 32 30 pAD Carel Modbus RS485...

Страница 10: ...PRG 2 KEY6 3 1 4 KEY6 3 60 KEY4 45 Ad01 Br01 pAD Ad01 pAD pLAN 1 32 2 Ad02 1 255 1 Br01 pLAN 0 62 5 1 115 2 0 Br02 0 4 4 En01 0 1 1 Pc01 9 9 9 9 C F 0 0 rEL Prot 1 3 1 1 Carel Modbus Carel Modbus Br0...

Страница 11: ...pAD 030220873 rel 1 2 18 01 2013 13 5 5 1 POWER ON pAD POWER pAD OFF POWER OFF OFF pAD POWER 3 pAD POWER pAD POWER 3 5 2 pAD MODE 5 3 pAD MODE...

Страница 12: ...pAD 030220873 rel 1 2 18 01 2013 14 5 4 pAD pAD 3 pAD pCO pCO 5 5 pAD pAD MODE 5 6 pAD pAD MODE 5 7 pAD KEY 3 pAD 3 5 8 KEY4 1HR 3 9 1 1 2HR pAD KEY4 3 diff...

Страница 13: ...5 0 0 10 0 C F 2 0 NIGHT 3 pCO OFF pAD pAD 5 9 pAD pAD 5 KEY5 rtc 0 23 0 59 day 0 7 1 2 pAD pCO pCO 5 10 2 2 1 HH 1 1 ACTION 2 HH 2 2 ACTION 1 HH 1 1 ACTION 2 HH 2 2 ACTION 1 3 17 18 1 5 2 0 23 3 4 OF...

Страница 14: ...pAD 030220873 rel 1 2 18 01 2013 16 6 2 Alr oLn pLAN AtE Ahu pAD...

Страница 15: ...1 2 18 01 2013 17 7 EN60730 1 24 Vac 15 50 60 70 1 5 31 Vdc 29 70 UL873 24 Vac 50 60 2 25 5 36 25 Vdc 2 1 RS485 2 0 50 C 10 85 20 70 C 0 85 2 A A IP30 100 C EN60703 1 3 1 2 pAD 1 0 5 1 5 2 2 C 10 83 5...

Страница 16: ...pAD 030220873 rel 1 2 18 01 2013 18...

Страница 17: ......

Страница 18: ...comply with the temperature and humidity limits specified in the manual Do not attempt to open the device in any way other than described in the manual Do not drop hit or shake the device as the inter...

Страница 19: ...sembly and installation instructions 25 3 2 Power supply connections 25 3 3 Serial interface 25 3 4 Installation warnings 25 4 CONFIGURATION AND STARTING 26 5 FUNCTIONS 27 5 1 Device ON STANDBY 27 5 2...

Страница 20: ......

Страница 21: ...e and humidity set point reading of temperature and or humidity sensors time band management manual and automatic heating cooling mode changeover manual and automatic fan speed setting 3 speed clock s...

Страница 22: ...program Icon Name standard Function 1 KEY 1 POWER Switch the system on or to standby 2 mod e KEY 2 MODE Set the operating mode cooling heating auto manual dehumidify manual humidify 3 KEY 3 HUM 2 Set...

Страница 23: ...ortant if a terminal of the power supply needs to be earthed use terminal G0 and NOT terminal G both on the pAD the other powered devices When pAD has a DC power supply the controllers connected via t...

Страница 24: ...in three seconds press the DOWN button 6 when PAr is displayed in the main area release the DOWN button while holding the UP button and press KEY6 within three seconds Procedure for setting the parame...

Страница 25: ...seconds until the main field on the display shows OFF all the symbols will be switched off pAD ON AND TIME BANDS ACTIVE the symbol is on to temporarily activate deactivate the operation of the system...

Страница 26: ...by the controller application program 5 7 Setting the humidity set point To set the humidity set point in the zone controlled by the pAD terminal Press the button associated with the humidity set poin...

Страница 27: ...first five days of the week Monday Friday 2 common time bands for the last two days Saturday Sunday Setting the times and the actions The time bands menu displays the following settings in sequence ti...

Страница 28: ...alarm code every 2 seconds The meaning of the codes is shown below Alarm Meaning Alr Active alarm on the controller Shown while the alarm is active oLn Offline no communication between the device and...

Страница 29: ...d structure A Index of protection IP30 Ball pressure test temperature on the plastic used for the case 100 C Classification according to protection against electric shock EN60703 1 3 to be integrated...

Страница 30: ...pAD 030220873 rel 1 2 18 01 2013...

Страница 31: ......

Страница 32: ...CAREL INDUSTRIES HQs Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com pAD 030220873 rel 1 2 18 04 2013...

Отзывы: