17

Note:

 all the receivers within range when the channel button is pressed (and 

which have at least one of the transmitter channel buttons memorised) will 

activate their signal buzzer "

B1

" (fig. 1).

2. Press one of the channel buttons on the same transmitter. The receivers 

which do not contain that channel code will sound a five-second long 

"beep" and will then deactivate. The receivers which contain the channel 

code will sound a one-second long "beep" and will enter the "

program-

ming via radio" 

mode.

3. Press the previously chosen channel buttons on the transmitter which you 

wish to memorise; the receiver will sound 2 "beeps" of half a second each 

after which the receiver will be ready to receive another code.

4. To leave the programming mode wait for 3 seconds without pressing any 

buttons. The receiver will sound a five-second long "beep" and will then 

exit the programming mode.

Note: 

When the memory is entirely occupied the buzzer will sound 10 rapid 

"beeps" and will automatically leave the "

programming via radio

" mode.

The same signal is given each time you try to enter "

programming via radio

when the memory is full.

Note:

 the memo radio procedure can only be carried out after program-

ming has terminated and you have quit the setting/programming menu.

t

Memorizing more transmitters by using a previously memorised 

transmitter (only S504 - S508)

This procedure allows you to enable a new transmitter (from a remote po-

sition) with the help of a transmitter that has already been memorised in 

the system. As the presence of the receiver is not required this procedure 

can be carried out in any remote location (for example in your chosen sales 

outlet).
Access to the "rapid memorizing" procedure is possible if the "MEMO RA-

DIO" function has been activated via the menu "OPTIONS" on the electronic 

programmer.
- Remove the upper cover from the transmitter to be memorised and from 

the transmitter that has already been memorised as shown in the drawing 

below (det. a).

- Place the transmitter 

A

, that has already been memorised in the receiver, 

beside the new transmitter 

B

 (det. b).

- Using a pointed object press and release the 

MR

 button on both transmit-

ter (in sequence or simultaneously).

- The orange LEDS on the transmitters will flash slowly.

- Press and release a channel button on transmitter  

A

  that is already pre-

sent in the receiver (det. c).

- The led of the new unit 

B

 will remain lit for 3 seconds to confirm that the 

transmiter has been  accepted (det. d).

Transmitter 

B

 will now command the receiver exactly like transmitter 

A

.

CONNECTING THE ANTENNA 

Connect an  

ANS400 / ANQ800-1

 tuned antenna using a coaxial cable 

RG58

 

(impedance 

50

Ω) with a maximum length of 

15 m

.

1) Automatic

Selected by enabling automatic reclosing (Automatic reclosing "

ON

" on 

the display). When the gate is completely closed the opening command will 
start a complete cycle which will end with automatic reclosing. 
Automatic reclosing starts after the programmed pause period has elapsed 
(minimum 2 seconds) when the opening cycle has been completed or 
straight away after the intervention of a photoelectric cell (the intervention 
of a photoelectric cell causes the pause time to be reset). 

LIMITED OPENING (PEDESTRIAN ACCESS)

FUNCTION MODES

MEMORIZZAZIONE CODICE TX-TX

TRQ504

29-10-2013

DM0910

Description :

Product Code :

Date :

Drawing number :

P.J.Heath

CARDIN ELETTRONICA S.p.A

  - 31020 San Vendemiano (TV) Italy - via Raffaello, 36 Tel: 0438/401818 Fax: 0438/401831

Draft : 

All rights reserved. Unauthorised copying or use of the information contained in this document is punishable by law 

MR

A

MR

B

1

MEMORIZZAZIONE CODICE TX-TX

TXQ504C4

29-10-2013

DM0911

Description :

Product Code :

Date :

Drawing number :

P.J.Heath

CARDIN ELETTRONICA S.p.A

  - 31020 San Vendemiano (TV) Italy - via Raffaello, 36 Tel: 0438/401818 Fax: 0438/401831

Draft : 

All rights reserved. Unauthorised copying or use of the information contained in this document is punishable by law 

A

MEMORIZZAZIONE CODICE TX-TX

TXQ504C4

29-10-2013

DM0912

Description :

Product Code :

Date :

Drawing number :

P.J.Heath

CARDIN ELETTRONICA S.p.A

  - 31020 San Vendemiano (TV) Italy - via Raffaello, 36 Tel: 0438/401818 Fax: 0438/401831

Draft : 

All rights reserved. Unauthorised copying or use of the information contained in this document is punishable by law 

B

During the pause time "

Pause

" will flash on the display along with the 

remaining pause time.
Pressing the blocking button during this period will stop automatic reclosing 
and consequently stop the display from flashing. 
The indicator light remains lit until the closing manoeuvre has terminated.

2) Semiautomatic

Selected by deactivating automatic reclosing (Automatic reclosing "

OFF

on the display). Work cycle control using separate opening and closing 

commands. 
When the door has reached the completely open position the system will 

wait until it receives a closing command either via an external control button 

or via radio control, before completing the cycle. 
The indicator light remains lit until the closing manoeuvre has terminated.

3) Manual manoeuvring with released motors

Releasing the motor the gate can be moved by hand; once the motor has 

been re-engaged the programmer will recover the position after two con-

secutive attempts to arrive at the travel limit.

4) Emergency manoeuvre

By default the emergency manoeuvre is disabled, to enable it move the 

jumper to the position 

J6

 "ENABLE" (fig. 1). 

If the electronic programmer no longer responds to commands due to 

a malfunction you may use the 

EMRG1

 or 

EMRG2

 inputs to move the 

gate leaf manually (fig. 1). 
The 

EMRG1

 or 

EMRG2

 inputs directly command the motor without pass-

ing through the logic control.
Gate movement will be at normal speed and the direction depends on the 

installed position of the motor:

Attention!

 During the emergency manoeuvre all safety devices 

are disabled and there is no gate positioning control: release the 

commands before you are at the mechanical travel buffer. Only 

use the emergency manoeuvre in cases of extreme necessity.

The electric lock (even if it is enabled) is not active. Therefore 

if an electric lock is fitted it will have to be activated manually.

After you have carried out an emergency manoeuvre the electronic program-

mer will lose the position of the gate ("out of pos" on the display) and therefore 

when normal operation is restored it will carry out a repositioning manoeuvre.

This always effects gate 1; the limited opening space can be set (see 

display menu) to 1/3, half, 2/3 or the entire opening distance for gate 1.

 If the "open-close" mode is set for the "

TD

" button (menu "OPTION") 

activating the "

TAL

" button will start the limited opening stage (only from 

the completely closed position) but while the gate is opening pressing 

the button again will have no effect. Once the opening position has 

been reached pressing the "

TAL

" button will start closing after which 

pressing "

TAL

" again will have no effect.

  If the "open-block-close" mode is set for the "

TD

" button (menu 

"OPTION") activating the "

TAL

" button will start the limited opening 

stage (only from the completely closed position) pressing the button 

again will block the gate; pressing the button a third time will start the 

closing cycle. Pressing the "

TAL

" button again will have no effect.

• If an opening command is received during limited opening; the limited 

opening command will become a full opening command. 

  If the 

FI

 photocell cuts in during the closing stage you will only have 

partial movement in the opening direction (It reopens only for the dis-

tance it has been closing the gate).

• 

Note:

 The limited opening command can also be given by remote control.

COURTESY LIGHT /CH2 RADIO OUTPUT

Binding posts “

9

 ","

10

 " are linked to a C-NO relay; this can be activated 

as follows:

• Jumper 

J5

 in position 1:

  the contact is closed by a timer and works as a “courtesy light" 

• Jumper 

J5

 

in 

position 

2: 

     

the contact works as a second radio channel.

Binding posts “

9

 ","

10

" only give a potential free contact; this means that the 

courtesy light will have to be powered by an external circuit and the contact 

used as a simple switch.

Содержание CC242ETOP

Страница 1: ...lectrique exemple d installation Page 3 Consignes importantes Page 20 Branchement lectrique Pages 20 21 Proc d de programmation Page 22 23 Menu de visualisation Page 24 Commande via radio Page 24 25 M...

Страница 2: ...pliqu e sur l emballage ou sur la notice d installation et d utilisation fournie avec le produit mettez le programmateur lectronique hors tension remplacez le module de m moire 24 LC16 S449 par le mod...

Страница 3: ...RL 24Vdc CMN LS LP CMN LC CH2 ELS 12Vdc CMN F4 10 A J3 F3 10 A BATTERY CHARGER J1 R1 J6 J2 J4 L2 ANS400 Enable Disable ANQ800 1 3 4 5 6 1 2 Bl Gr Gy Yw M1 ENCODER 1 Rd Bk M1 3 4 5 6 1 2 Bl Gr Gy Yw M2...

Страница 4: ...o scariche si verifica laperditadelcontrollodellaposizionedell antaconconseguente segnalazionediallarmeenecessit diriposizionamento Controllare quindi l efficienza delle batterie ogni sei mesi vedi pa...

Страница 5: ...gnalazione fotocellule di stop FS 3 FS S4 Segnalazione costa sensibile CP 3 CP S5 Segnalazione tasto di apertura TA TA S6 Segnalazione tasto di chiusura TC TC S7 Segnalazione comando sequenziale TD TD...

Страница 6: ...IN STOP TEST FI ON OFF TEST FS ON OFF TEST FS ON OFF SFASAM APERTURA ON OFF ELETTROSERRATURA ON OFF TEST FI ON OFF TEST FS ON OFF SFASAMENTO IN APERTURA ON OFF SFASAM APERTURA ON OFF ELETTROSERRATURA...

Страница 7: ...TAL INT COSTA TB FI FS CP TA TD TC TAL INT SENS PROG OK per confermare PREMERE sul trasmettitore il canale da memorizzare PREMERE sul trasmettitore lo stesso canale per memorizzare PROG OK per conferm...

Страница 8: ...alla voce CANCEL TOTALE Memorizzazione di ulteriori canali via radio solo S449 S486 La memorizzazione pu essere anche attivata via radio senza aprire la scatola dove alloggiata la centralina se l imp...

Страница 9: ...essere spostate a mano una volta ribloc cati il programmatore provveder al ripristino della posizione dopo due tentativi consecutivi di arrivare in battuta 4 Manovra di emergenza Lamanovradiemergenza...

Страница 10: ...della centralina che anche in caso di blackout alimentano i circuiti ad essa collegati Quando la batteria si scarica completamente in assenza di tensione di rete il programmatore perde la posizione de...

Страница 11: ...11 NOTES...

Страница 12: ...t professionally qualified installers of electricalequipment andmustrespectthelocalstandardsandregula tions in force All materials used must be approved and must suit the environment in which the inst...

Страница 13: ...Indicator for the inverting photoelectric cells FI 3 FI S3 Indicator for the stop photoelectric cells FS 3 FS S4 Indicator for the safety edge CP 3 CP S5 Indicator for the opening button TA TA S6 Ind...

Страница 14: ...ONTRAST 0 63 REAR LIGHTING ALWAYS ON 60 30 SEC EXIT PROG OK to return to display Note 1 Note 2 Note 3 Note 3 Note 6 Note 7 Note 8 Note 9 The number of manoeuvres carried out by the operator arm and th...

Страница 15: ...S CP TA TD TC TAL AUTO PROG TB FI FS CP TA TD TC TAL OPENING TB FI FS CP TA TD TC TAL STOP OPENING TB FI FS CP TA TD TC TAL CLOSING TB FI FS CP TA TD TC TAL STOP CLOSING PROG OK to confirm PRESS the t...

Страница 16: ...ng ulterior channels via radio S4XX transmitters The system can be remotely activated using radio control devices with outopeningthereceiver bysetting MEMORADIO hasbeenactivated in the OPTIONS menu 1...

Страница 17: ...le by law A MEMORIZZAZIONE CODICE TX TX TXQ504C4 29 10 2013 DM0912 Description Product Code Date Drawing number P J Heath CARDIN ELETTRONICA S p A 31020 San Vendemiano TV Italy via Raffaello 36 Tel 04...

Страница 18: ...ning on battery power is dependent on the ambient conditions and on the load connected at binding posts 16 17 power is always routed there during blackouts When the battery is completely flat during b...

Страница 19: ...19 NOTES...

Страница 20: ...en bon tat En cas de coupure de courant et batteries d charg es le programmateur perd la m morisation de la position occup e par le vantail cette situationentra neunesignalisationd alarmeetunrepositi...

Страница 21: ...v criture blanche sur fond noir Branchements du bornier 7 CMN commun pour toutes les entr es sorties 8 ELS sortie pour serrure lectrique 12 Vdc 15 W 9 10 LC CH2 sortie contact non aliment N O pour act...

Страница 22: ...63 LUMIERE FONDE TOUJOUR ON 60 30 SEC SORTIE PROG OK pour confirmer CONTRASTE 0 63 LUMIERE FONDE TOUJOUR ON 60 30 SEC SORTIE PROG OK pour changer le valeur CONTRASTE 0 63 LUMIERE FONDE TOUJOUR ON 60 3...

Страница 23: ...te ou de gauche pour modifier la langue Italiano Fran ais Appuyer sur la touche PROG OK pour confirmer la langue PROG OK pour confirmer APPUYER sur l metteur le canal m moriser APPUYER sur l metteur l...

Страница 24: ...is termin l effacement total de la m moire l afficheur revient la rubrique EFF TOTAL M morisation par radio d autres canaux seulement S4XX Cette m morisation peut galement tre activ e via radio sans d...

Страница 25: ...on d action de la t l commande et qui ont au moins un canal de l metteur de m moris enclencheront simultan ment l avertisseur sonore B1 fig 1 2 Pour s lectionner le r cepteur dans lequel il faut m mor...

Страница 26: ...tifsbranch sauxbornes16 17 fig 1 de la centrale lesquelles alimentent m me en cas de coupure de courant les circuits y aff rents Quand la batterie se d charge compl tement en cas de coupure de courant...

Страница 27: ...27 NOTES...

Страница 28: ...eistungsf higkeit der Batterien sollte daher alle sechs Monate berpr ft werden siehe Seite 34 berpr fung der Batterien NachdemdieVorrichtunginstalliertwurdeundbevordieSteuerung mitStromversorgtwird mu...

Страница 29: ...TB S2 Anzeige Bewegungsumkehrunglichtschranken FI 3 FI S3 Anzeige Lichtschranke f r Stop FS 3 FS S4 Anzeige Sicherheitsleiste CP 3 CP S5 Anzeige ffnungstaste TA TA S6 Anzeige Schlie ungstaste TC TC S...

Страница 30: ...FF PHASENVERSCHIEB ON OFF ELEKTROSCHLOSS ON OFF FUNK SPEICHERUNG ON OFF ELEKTROSCHLOSS ON OFF FUNK SPEICHERUNG ON OFF AUSGANG LC CH2 FUNK KANAL WACHLICHT PROG OK um zu best tigen PROG OK um der Wert z...

Страница 31: ...eln Italienisch Deutsch Zur Best tigung der Sprache die Taste PROG OK dr cken PROG OK um zu best tigen Die zu speichernde Kanaltaste auf dem Sender dr cken Die zu speichernde Kanaltaste auf dem Sender...

Страница 32: ...zur ck Speicherung weiterer Kan le ber Funk nur S4XX Die Speicherung kann auch ber Funk aktiviert werden ohne die Dose zu ffnen in der sich das Steuerger t befindet wenn die Einstellung FUNKSPEICHERU...

Страница 33: ...e Drawing number P J Heath CARDIN ELETTRONICA S p A 31020 San Vendemiano TV Italy via Raffaello 36 Tel 0438 401818 Fax 0438 401831 Draft All rights reserved Unauthorised copying or use of the informat...

Страница 34: ...mie des Systems ist bei einer Versorgung durch Batterie eng verbunden mit den Umweltbedingungen und dem an die Klemmen 16 17 Abb 1 der Steuereinheit die auch bei Stromausfall die an sie angeschlossene...

Страница 35: ...35 NOTES...

Страница 36: ...namiento Controlar tambi n el buen funcionamiento de las bater as cada seis meses v ase p g 42 Prueba de las bater as Tras haber instalado el dispositivo y antes de proporcionar tensi n a la centralit...

Страница 37: ...fotoc lulas de parada FS 3 FS S4 Se alizaci n banda sensibile CP 3 CP S5 Se alizaci n tecla de apertura TA TA S6 Se alizaci n tecla de cierre TC TC S7 Se alizaci n control secuencial TD TD S8 Se aliza...

Страница 38: ...LULA INV EN CIERRE ADEMAS EN STOP LUZ TESTIGO FIJA INTERMITENTE FOTOCELULA INV EN CIERRE ADEMAS EN STOP TEST FI ON OFF FOTOCELULA INV EN CIERRE ADEMAS EN STOP TEST FI ON OFF TEST FS ON OFF TEST FS ON...

Страница 39: ...de funcionamiento TB FI FS CP TA TD TC TAL PAUSA TB FI FS CP TA TD TC TAL AUTO PROG TB FI FS CP TA TD TC TAL APERTURA TB FI FS CP TA TD TC TAL STOP APERTURA TB FI FS CP TA TD TC TAL CIERRE TB FI FS C...

Страница 40: ...lo S4XX Lamemorizaci npuedeactivarsetambi nv aradio sinabrirlacajadondela centralita est alojada si la configuraci n MEMO RADIO ha sido activada en el men OPCIONES 1 Utilizando un radiomando en el cua...

Страница 41: ...runa delasteclasdecanaldelmismoemisor Losreceptoresquenocontenganel c digodedichateclasedesactivar nconlaemisi ndeun bip de5segundos deduraci n encambio elquecontengaelc digoemitir otro bip quedurar u...

Страница 42: ...onectada a los bornes 16 17 fig 1 de la centralita que tambi n en caso de interrupci n total de la energ a alimenta los circuitos conectados con la misma Cuando la bater a se descarga completamente cu...

Страница 43: ...x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x...

Страница 44: ...quency module aerial connection FM NO inputs opening button limited opening button closing button dynamic button NC 8 2 k inputs inverting photocells stop photocells blocking button safety edge Output...