During initial start-up
■
Once the testing interval has expired
■
After maintenance and repairs
Record the results.
►
Disconnect SC4 from the machine.
►
Connect a meter to the contacts of the safety relay that release the
machine function.
►
Actuate the SC4s one after another.
a
LEDs must be lit red.
a
The safety relay must not release N/O or N/C contacts.
Switching on must be verified at the output contacts of the safety relay
using the meter and must not exceed the safety times (0.5 s in this case).
►
Disconnect the SC4 from the power supply.
►
Actuate and continue actuating the SC4.
►
Restore the power supply.
a
LEDs must be lit red.
a
The safety relay must not release N/O or N/C contacts.
6
Maintenance
6.1
Maintenance operations
Carry out the following maintenance operations at the specified intervals.
Maintenance operation
as
needed
annually Testing interval
Clean the button surface
X
Test the safety function
X
Check cables for intactness
and firm fit
X
Check screw connections
for tightness
X