• on the burner  

the blocking signal following intervention by the burner's 

flame control box. 

 

Warning 

NEVER do more than two restarts in a row: unburned fuel 

can accumulate in the combustion chamber and suddenly 

flare up at the next restart

.

 

 

If the heater is still not working properly, please contact your 
nearest dealer or authorized Service Centre. 
 
 
 

 

 

 

 

 

 

 

 

 

 

FAULT CAUSE  REMEDY 

• The heater does not start: 

 lamp 

 is off 

• No power supply 

• Check functioning and position of switch 
• Check the mains 

• Check power connections 
• Check fuse 

• The heater does not start: 

 lamp 

 is on 

• Switch (a) in wrong position 

• Select correct position 

•  Incorrect functioning of the room thermostat 

• Check that thermostat connection plug is inserted 

• Check thermostat electrical connection 
• Check thermostat setting and correct it 
• Check functioning of thermostat 

• The burner goes on and off alternately and LED 

OUT 2 on the temperature controller remains 
ON.  

• Insufficient gas supply 

• Check and clean gas filter. 
• Clean and recalibrate the burner. 

•  Incorrect setting of burner 

• Clean and recalibrate the burner. 

• The burner goes on and off alternately and LED 

OUT 2 on the temperature controller is OFF 
when the burner goes off.  

• Burner thermostat has tripped due to 

overheating 

• Check correct position of air distribution channels 

and opening of any flaps, openings, etc. 

• Remove any foreign bodies trapped in the air ducts or 

ventilation grilles 

• The heater does not work: 

 the 

lamp   on the electrical panel is on 

 

•  Manual reset safety thermostat has tripped due 

to excessive overheating of combustion 
chamber 

• Check that the fan motor starts correctly and is not 

obstructed 

• Check that the fan motor is not burned out or that the 

motor condenser is not broke 

• Check burner calibration 
• Check the path and correct discharge of fumes 

• The heater does not work:: 

 the 

lamp 

 on the burner is steady on 

•  Burner's safety equipment has tripped 

• Refer to the burner manual for diagnosis and causes 

• Fan noise or vibrations 

• Foreign bodies on fan blades 

• Remove foreign bodies 

• Insufficienct air circulation 

• Eliminate all possible obstacles to proper air flow 

• Insufficient heating 

• Insufficient burner capacity 

• Contact Customer Service 

Содержание JUMBO 400

Страница 1: ...L L 265 00 BM 1 24 INSTRUCTIONS MANUAL MANUEL D INSTRUCTIONS SPACE HEATER GENERATEUR D AIR CHAUD JUMBO 400 JUMBO 600 JUMBO 800 FR EN...

Страница 2: ...ING MATERIALS PAPER OR CARDBOARD AT SAFE DISTANCE AWAY FROM THE HEATER AS RECOMMENDED BY THE INSTRUCTIONS NEVER USE THE HEATER IN SPACES WHICH DO OR MAY CONTAIN VOLATILE OR AIRBORNE COMBUSTIBLES OR PR...

Страница 3: ...t in gas leaks and fire or explosion from the leak The hose assembly must be protected from the traffic building materials and contact with hot surfaces both during use andwhile in storage WARNING Pro...

Страница 4: ...R REFROIDISSEMENT 4 COMBUSTION CHAMBER CHAMBRE DE COMBUSTION 5 BURNER BRULEUR 6 THERMOSTATS L2 BOX BOITIER THERMOSTATS L2 7 HOISTING BRACKETS TRIERS DE LEVAGE 8 SUPPORT HANDLE SUPPORT POIGNEE 9 WHEEL...

Страница 5: ...INTAKE FOR PRE HEAT FILTER PRISE POUR FILTRE PR CHAUFFAGE f CABLE CLAMP FOR POWER CABLE PRESSE C BLES POUR C BLE D ALIMENTATION g TEMPERATURE CONTROLLER THERMOR GULATEUR h BURNER LIGHT VOYANT BR LEUR...

Страница 6: ...f f c c d d d d d a a a e e e a GAS SELECTOR VALVE VALVE S LECTEUR GAZ b MANIFOLD PRESSURE PORT PORT PRESSION BRULEUR c MANIFOLD PRESSURE REGULATOR R GULATEUR PRESSION d MAIN GAS VALVE SOUPAPE PRINCIP...

Страница 7: ...stop of the space heater In this case the heater will restart automatically when the required condition is restored The section TROUBLESHOOTING describes all possible operating faults and their possib...

Страница 8: ...or ceiling must always be at least 1 metre 4 2 POWER CONNECTIONS Warning The 120V unit is fitted with a proper power cord The 220V equipment is fitted with a temporary power cable used for the final...

Страница 9: ...r check that the direction of rotation of the fan matches the direction shown on the fan itself The air distribution channels can be connected by using the various accessories supplied placing the con...

Страница 10: ...ter operation and not with the heater off The space heater has a gas ramp with gas filter pressure regulator safety electrovalve work electrovalve pressure stabilizer pressure valve It is good practic...

Страница 11: ...y to change the kind of gas from natural gas to L P G or viceversa follow the detailed instructions indicated in section CHANGING TYPE OF GAS Only when the heater has been prearranged according to the...

Страница 12: ...tests are completed the hole drilled for the probe must be sealed with a material that is resistant to high temperatures and that ensures the tube remains airtight 5 OPERATING INSTRUCTIONS 5 1 START...

Страница 13: ...y set to 35 C with hysteresis of 5 C Red LED OUT 1 shows the operating state of the fan thermostat LED ON the fan is on LED OFF the fan is off Control of trip temperature of burner thermostat The temp...

Страница 14: ...amaged wires or connectors if necessary 6 5 CHECKING AND TESTING THE BURNER To reach the burner Remove the burner fixing screw Remove the burner and follow the checking and cleaning instructions in th...

Страница 15: ...and recalibrate the burner Incorrect setting of burner Clean and recalibrate the burner The burner goes on and off alternately and LED OUT 2 on the temperature controller is OFF when the burner goes...

Страница 16: ...NTROL LAMP LAMPE TEMOIN SECURITE DE SURCHAUFFE L1 BURNER THERMOSTAT setting 90 C THERMOSTAT BRULEUR r gulation 90 C TA ROOM THERMOSTAT PLUG PRISE THERMOSTAT D AMBIACE RE2 DELAYED IGNITION RELAY RELAIS...

Страница 17: ...NTROL LAMP LAMPE TEMOIN SECURITE DE SURCHAUFFE L1 BURNER THERMOSTAT setting 90 C THERMOSTAT BRULEUR r gulation 90 C TA ROOM THERMOSTAT PLUG PRISE THERMOSTAT D AMBIACE RE2 DELAYED IGNITION RELAY RELAIS...

Страница 18: ...sea level U S A and Canada Heat input BTU h 393 052 Manifold pressure in w c 2 40 Burner head position N 4 Burner Air setting N 4 7 Fuel consumption CFH 158 40 Altitude 2 000 4 500 ft above sea level...

Страница 19: ...nd Canada Heat input BTU h 593 609 Manifold pressure in w c 1 60 Burner head position N 3 Burner Air setting N 3 4 Fuel consumption CFH 239 22 Altitude 2 000 4 500 ft above sea level Canada only Heat...

Страница 20: ...ut BTU h 805 499 Manifold pressure in w c 2 20 Burner head position N 5 Burner Air setting N 5 2 Fuel consumption CFH 317 16 Altitude 2 000 4 500 ft above sea level Canada only Heat input BTU h 724 95...

Страница 21: ...L L 265 00 BM 21 24 NOTICE DE MONTAGE DU PIED DE LA POIGNEE FOOT HANDLE ASSEMBLY INSTRUCTION...

Страница 22: ...L L 265 00 BM 22 24...

Страница 23: ...L L 265 00 BM 23 24...

Страница 24: ...L L 265 00 BM 24 24 BIEMMEDUE S p A Via Industria 12 12062 Cherasco CN Italy Tel 39 0172 486111 Fax 39 0172 488270 www biemmedue com bm2 biemmedue com...

Отзывы: