6-10KVA Rack-mount UPS User Manual                                      Installation 

14 

 

Fig 9. Input and Output Terminal Block Wiring Diagram of distribution box for standard model

 

NOTE

You must make sure that the input and output wires and the input and output terminals 

are connected tightly. 

5)    The protective earth ground wire refers to the wire connection between the equipment 

which consumes electric equipment and the ground wire. The wire diameter of protective earth 

ground wire should be at least as above mentioned for each model and green wire or green 

wire with yellow ribbon wire is used. 

6

  After having completed the installation, make sure the wiring connection is correct. 

7)    Please install the output breaker between the output terminal and the load, and the 

breaker should with leakage current protective function if necessary. 

8)    To connect the load with the UPS, please turn off all the loads first, then perform the 

connection and finally turn on the loads one by one. 

9)    No matter the UPS is connected to the utility power or not, the output of the UPS may 

have electricity. The parts inside the unit may still have hazardous voltage after turning off the 

UPS. To make the UPS have no output, power off the UPS, and then disconnect the utility 

Содержание 6KS

Страница 1: ...d 220 230 240VAC 50 or 60Hz supply The factory default setting is 220VAC 50Hz Installation instructions and warning notices are in this manual The ups 06 10KVA 220 230 240VAC is designed for use with...

Страница 2: ...urn off and unplug the ups before cleaning it z Clean the UPS with a dry cloth Do not use liquid or aerosol cleaners z Never block or insert any objects into the ventilation holes or other openings of...

Страница 3: ...6 Battery 7 3 7 Dynamic Bypass 7 4 PRODUCT SPECIFICATION And PERFORMANCE 8 4 1 Model Description 8 4 2 Product Specification and Performance 8 5 INSTALLATION 10 5 1 Unpacking and Inspection 10 5 2 Ra...

Страница 4: ...EMENT PROCEDURES 26 9 1 Battery Disposal 26 9 2 External Battery Replacement Procedures 26 9 3 Internal Battery Pack Replacement Procedures 27 10 TROUBIE SHOOTING 28 10 1 Checking UPS status 28 10 2 A...

Страница 5: ...corrosive substance This UPS contains no user serviceable parts except the internal battery pack The UPS on off push buttons do not electrically isolate internal parts Under no circumstance attempt t...

Страница 6: ...en damage equipment The series protects equipment from these disturbances The series is a compact rack mount on line UPS An on line UPS continuously conditions and regulates its output voltage whether...

Страница 7: ...6 10KVA Rack mount UPS User Manual Introduction 3 Fig 2 Front View of standard Model Fig 3 Rear View of 6KVA Long Backup Model Fig 4 Rear View of 10KVA Long Backup Model...

Страница 8: ...port SNMP card for network monitoring Intelligent card or non pluggable dry contact card for user extending Input circuit breaker Maintenance Bypass breaker External battery connector Parallel kit op...

Страница 9: ...KVA Rack mount UPS User Manual Introduction 5 Fig 6 The Removable Power Distribution Box factory attached of long backup model Fig 7 The Removable Power Distribution Box factory attached of standard m...

Страница 10: ...nsuring that the waveform of the input current used by the UPS is near ideal Extracting this sine wave input current achieves two objects z The utility power is used as efficiency as possible by the U...

Страница 11: ...ude value regulated non spoilable lead acid batteries outside To maintain battery design life operate the UPS in an ambient temperature of 15 25 C 3 7 Dynamic Bypass The ups provide an alternate path...

Страница 12: ...0 60 Input Voltage 176 275 VAC Current 34A max 57A max Battery Voltage 192VDC Current 37A max 60A max Output Voltage 220V 230V 240V Current 27 26 25A 45 43 42A Dimension W H D mm 438 130 680 438 218 6...

Страница 13: ...de is above than 1000m the output power must be derated in use please refer to the following Altitude M 1000 1500 2000 2500 3000 3500 4000 4500 5000 Derating Power 100 95 91 86 82 78 74 70 67 1 0 9 la...

Страница 14: ...the long backup model 2 Inspect the appearance of the UPS to see if there is any damage during transportation Do not turn on the unit and notify the carrier and dealer immediately if there is any dama...

Страница 15: ...into the rack rails NOTE Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the lowest possible rack position 5 2 Connect Input Output Power Cables 1 Notes for inst...

Страница 16: ...tached please refer to the appearance diagram 2 For 6KVA UPS it is recommended to select the UL1015 10AWG 6mm 2 wire or other insulated wire which complies with AWG Standard for the UPS input and outp...

Страница 17: ...6 10KVA Rack mount UPS User Manual Installation 13 Fig 8 Input and Output Terminal Block Wiring Diagram of distribution box for standard model...

Страница 18: ...reen wire or green wire with yellow ribbon wire is used 6 After having completed the installation make sure the wiring connection is correct 7 Please install the output breaker between the output term...

Страница 19: ...on 1 The nominal DC voltage of external battery pack is 192VDC Each battery pack consists of 16 pieces of 12V maintenance free batteries in series To achieve longer backup time it is possible to conne...

Страница 20: ...tput power sharing and power redundancy 2 Parallel installation 1 Users need to opt two standard 15 pin communication cables which length is appropriate to be less than 3m 2 Strictly follow the stand...

Страница 21: ...eaker Fig 11 Wiring Diagram of 6KVA and 10KVA in parallel 3 Operation 1 To perform the general operation follow the stand alone operating requirement 2 Startup The units transfer to INV mode simultane...

Страница 22: ...mode It is easy to operate the equipment with no previous training You just need to read through this manual and operate according to the instructions in it Rectifier PFC Inverter Bypass Charger UPS...

Страница 23: ...NOTE Not available when UPS is set in automatically start mode 2 Press on off directly when there is no main input press again to start UPS 3 Press on off to shutdown inverter when UPS is in normal mo...

Страница 24: ...k inverter is not working BYP Bypass indicator green bypass is normal dark UPS is in normal mode and bypass is normal red bypass fault red flicker bypass alarm BAT Battery indicator green battery char...

Страница 25: ...and function Set language contrast communication set SNT Modbus Modbus set Function function 1 transfer to bypass escape fault clear mute on off function 2 battery test maintenance test stop test Hist...

Страница 26: ...er of the battery pack is in the ON position this step only for long backup time model 2 Press the ON OFF button once to power on the LCD then press ON OFF button again choose YES to enter 3 A few sec...

Страница 27: ...off its output immediately 2 Turn the input breaker off the external mains input breaker the output breaker and the battery breaker 3 Press the others UPSs s ON OFF button All of them transfer to the...

Страница 28: ...n the UPS after remove the power distribution box and battery connection cable please wait about 10 minutes in order that the BUS capacitor voltage in the internal automatically discharges 2 Place the...

Страница 29: ...ged once every 4 to 6 months if it has not been used for a long time zIn the regions of hot climates the battery should be charged and discharged every 2 months The standard charging time should be at...

Страница 30: ...cuit There may be hazardous voltage between the battery terminals and the ground 8 Even though the input breaker is disconnected the components inside the UPS are still connected with the batteries an...

Страница 31: ...ery access door from the UPS for reassembly 4 Gently disconnect the battery plugs and battery receptacles 5 Pull the internal battery packs out of the UPS 6 Line up and slide in the new replacement in...

Страница 32: ...p and contact your local representative or Channel Support z Check whether the battery is discharging When the utility input is normal the battery should not discharge If the UPS is operating in Batte...

Страница 33: ...broken IGBT drivers are lost 17 A1 1 Reserved 18 2 Reserved 19 3 Reserved 20 4 Reserved 21 5 Reserved 22 6 Reserved 23 7 Reserved 24 8 Reserved 25 9 Input voltage Fault OK Fault Input voltage out of r...

Страница 34: ...38 6 Negative bus under voltage OK Fault UPS requires service 39 7 Battery reversed OK Fault Check if the battery wires connection is OK 40 8 Reserved 41 9 Reserved 42 10 Reserved 43 11 Reserved 44 1...

Страница 35: ...hutdown normal shutdo wn 66 2 INV protect OK Fault 67 3 Transfer times limit in one hour OK Fault Transfer times between inverter and bypass is over 5 times in one hour 68 4 Reserved 69 5 Reserved 70...

Страница 36: ...6 Reserved 81 A5 1 Reserved 82 2 Output shorted OK Fault Shutdown UPS and open output breaker check if load is effective or short internally check if output connector is shorted 83 3 Battery test None...

Страница 37: ...UPS fail Low voltage if something is failure in UPS If not high voltage 2 General alarm Low voltage if something is abnormal If not high voltage 3 GND 4 Remote shutdown UPS shutdowns rectifier and in...

Страница 38: ...dition This function can be activated through a remote contact provided by the user It requires opening NO and 24V at normal operation EPO is activated when shorting NO and 24V Description of Input Po...

Отзывы: