manualshive.com logo in svg
background image

- 4 -

TESTING  

(Continued)

Figure 10

Red Start
Button

Glass-Break

Detector

IMPORTANT: Some environmental factors may reduce the sensor
activation range.  If you do not see the green LED flashing after pressing
the red start button, move closer to the unit and try again.

If an FG-701 is not available, or if for any reason remote activa-
tion cannot be used, use a screwdriver to short the test pads at
location S3 on the PCB (see Figure 1). This will activate Test
Mode.  Make sure to replace the front cover of the FG-1025Z
before beginning test.

To test the FG-1025Z:

1. Place the unit in Test Mode as described above.
2. Set the FG-701 switches to the TEST and FLEX positions.
3. Press the red start button.  The simulator will "click" on and

start an eight second armed period.

4. Position the FG-701 near the farthest point of the protected

glass and point it directly at the FG-1025Z.

5. Generate a flex signal by carefully striking the glass with a

cushioned tool.  The FG-701 will respond by producing a
burst of glass-break audio.  (Refer to Figure 10.)

If both the flex and audio are received properly, the red alarm
LED on the FG-1025Z will light.

IMPORTANT:  If window coverings are present, close them fully and hold
the FG-701 behind the window coverings for testing.

NOTE:   You can also use the simulator in the MANual mode to test
audio alone.  The blinking green LED on the unit will flicker when
the simulator audio is received correctly.  (See the FG-701
Operating Instructions for additional information.)

After testing, exit the Test Mode using the same procedure for
activating the Test Mode.  The FG-1025Z also will automatically
exit Test Mode after ten minutes.  If the red alarm LED is lit, it will
automatically extinguish upon exiting Test Mode.

LED Indicators (Continued):

Condition

Green LED

Red LED

Normal, no event

OFF

OFF

Normal, event detected

Flicker

OFF

Normal, break detected

OFF

ON

Power-up self-test

ON, one second

ON, one second

Trouble  detected

Flash ON/OFF

Flash OFF/ON

Test mode, no alarm

Flash once per second OFF

Test mode, event detected

Flicker

OFF

Test mode, alarm

Flash once per second ON

LED Indicators:

The two LED's on the front cover are used to indicate the
sensor's operational status.  The following table summarizes the
LED operation when the LED's are enabled.

APPLICATIONS INFORMATION

The FG-1025Z is designed to detect framed glass broken by an
impact sufficient to make a hole.

To minimize the chance of false alarms:

Do not use outside.

Avoid installing in rooms with high-level noise sources, such
as air compressors, bells, power tools, etc., if those sources
can be active when the detector can signal an alarm.

Test false alarm immunity by activating any known noise
sources in the room.

To maximize detection:

Mount the unit on a wall or ceiling directly opposite the glass
if possible.  The least desirable mounting location is on the
same wall as the glass.

Minimize range to the glass.  Do not install beyond the
maximum specified range even if testing indicates greater
range.

Verify all installations back to the panel to be sure that the
protection loop is intact.

Self-Test Chart

Power-Up Self-Tests

• RAM Test

Write & read all RAM locations
with one's & zero's

• Arithmetic Test

Verify correct results for CPU
arithmetic

• Logic Test

Verify correct results for data
comparisons

• Clock Rate Test

Check clock frequency by
measuring external time
constants

• Active Analog Circuit Test

Inject signals into analog
channels to check gains,
filters, A/D, and interrupts

Continuous Self-Tests

• Watchdog

Supervises microcontroller

• ROM Checksum

Firmware ROM checksum
verified

• RAM Test

Write & read RAM locations
with one's & zero's

• Logic Test

Verify correct results for data
comparisons

• Passive Analog Circuit Test

Verify analog inputs are within
normal bounds

SELF-TESTS

The FG-1025Z automatically performs a series of self-tests
during power-up, and continuously (when the sensor is not
detecting a trouble or alarm condition.)  Refer to the chart below
for descriptions of the self-tests performed:

Содержание FG-1025Z

Страница 1: ...o the Technical Information section on page 5 MOUNTING LOCATION For the greatest flexibility in aiming the FG 1025Z mount the unit on the ceiling Figure 3 illustrates the protected excluded and keepout zones for a ceiling mounted FG 1025Z The arrows printed on the intermediate cover see Figure 1 indicate the direction of the protected zone Refer to the Mounting Guidelines to select an appropriate ...

Страница 2: ...h of the room as possible should be in the excluded zone There is no minimum range but the unit must have a clear line of sight and a clear view of the protected glass The preferred location is on the ceiling directly opposite the glass Do not mount in corners and keep the unit at least 1 0 3 m from any adjacent walls When wall mounting mount the unit at a height of at least 6 feet 1 8 m to avoid ...

Страница 3: ... S2 ON LATCH LED CMD IN 1 2 3 REMOTE LED Shaded boxes are factory default settings a Latched alarm LED does not affect timing of alarm relay b Reset the alarm LED by removing and restoring power or by toggling the S2 LATCH switch off and on c Sets function of CMD IN Remote LED terminal SWITCH OFF ON LATCH Red alarm LED Red alarm LED lights for 5 seconds latches ON when when unit alarms unit alarms...

Страница 4: ...ON one second ON one second Trouble detected Flash ON OFF Flash OFF ON Test mode no alarm Flash once per second OFF Test mode event detected Flicker OFF Test mode alarm Flash once per second ON LED Indicators The two LED s on the front cover are used to indicate the sensor s operational status The following table summarizes the LED operation when the LED s are enabled APPLICATIONS INFORMATION The ...

Страница 5: ...e is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures 1 Reorient or relocate the receiving antenna 2 Increase the separation between...

Страница 6: ... anyone for any consequential or incidental damages for breach of this or any other warranty express or implied or upon any other basis of liability whatsoever even if the loss or damage is caused by Seller s own negligence or fault Seller does not represent that its product may not be compromised or circumvented that the product will prevent any personal injury or property loss by burglary robber...

Отзывы: