10
ELECTRICAL INSTALLATION
10.1 Power Requirements:
Notes/Remarques:
1.
Fan should only be installed by qualified personnel in accordance with the NEC.
2.
Proper grounding of fan per the NEC is required for safety and proper operation.
3.
Length of cable from controller to fan motor to be 100 feet or less.
4.
Each fan must be connected to individual circuit breaker.
Supply Connections:
Conductor of a fan identified as grounded conductor to be connected
to an ungrounded conductor of power supply, conductor of fan identified for equipment
grounding to be connected to an equipment grounding conductor.
Canarm is not liable for any voltage disturbances with explicit reference to electronic magnetic
interference (EMI). Voltage disturbance refers to transient overvoltage, voltage unbalance, voltage swells,
rapid voltage change, flicker, superimposed signals, harmonic voltages, supply voltage variations, voltage
dips and frequency/time deviation.
Canarm n’est pas responsable des perturbations de tension en référence explicite aux interférences
magnétiques électroniques (EMI). Les perturbations de tension se réfèrent aux surtensions
transitoires, aux déséquilibres de tension, aux hausses de tension, aux variations rapides de tension,
au scintillement, aux signaux superposés, aux tensions harmoniques, aux variations de la tension
d’alimentation, aux creux de tension et aux écarts fréquence / temps.
CAUTION/ATTENTION
!
WARNING/AVERTISSEMENT
!
!
Motor cables and incoming power must never be run in the same conduit. Failure to
install per Canarm fan instructions, including wiring, may be hazardous, cause premature
failure, and void the manufacturers warranty.
Les câbles moteur et de la puissance entrant ne doivent jamais être placés sur le même
conduit. Ne pas installer par Canarm ventilateur instructions, y compris le câblage, peut
être dangereuse, entraîner une défaillance prématurée, et annulera la garantie du
fabricant.
INPUT VOLTAGE
INPUT (HZ)
INPUT/OUTPUT PHASE
220-240 VAC
50 / 60 Hz
1 Phase
220-240 VAC
50 / 60 Hz
3 Phase
400-480 VAC
50 / 60 Hz
3 Phase