10 Daily Maintenance 

 

  15 / 19 

 

10 Daily Maintenance 

 

DANGER 

Risk of inverter damage or personal injury due to incorrect service! 
Always keep in mind that the inverter is powered by dual sources: PV array and utility grid.   
Before any service work, observe the following procedure.   
1) Disconnect the inverter from the utility grid side first and then PV array;   
2) Wait at least 5 minutes after shut down the inverter, for inner capacitors to discharge completely;   
3) Verify that no voltage and current existing with appropriate testing devices. 

 

NOTICE 

Risk of inverter damage if it is improperly serviced.   
Use accessories and spare parts approved by the inverter manufacturer only. Never modify the inverter or other 
components of the inverter. The loss of any or all warranty rights may follow if otherwise. 

 

NOTICE 

Any malfunction that may impair the inverter safety operation must be repaired immediately before the inverter 
is restarted.   
Inverter contains no customer serviceable parts inside. Please contact local authorized personnel if any service 
work is required.   

 
 
 

Information 

Servicing of the device in accordance with the manual should never be undertaken in the absence of proper 
tools, test equipment or the more recent revision of the manual with has been clearly and thoroughly 
understood.   

 

Items 

Methods 

Period 

System 

clean 

Check the temperature and dust of the inverter. Clean the inverter enclosure.   
Check the humidity and dust of the environment.   
Meanwhile check whether the filter function of the air inlet is ok. 

Six months to a year (it 
depends on the dust 
contents in air.) 

11 Troubleshooting 

When the inverter does not operate normally, we recommend the following actions for quick troubleshooting. Please 
review the error list table carefully.   

11.1 Warning 

The different LED colors and flashing status identify the current operation statuses of the inverter. If the red color is 
always on, it indicates the inverter fault. Usually the warnings can be cleared through an orderly shutdown / reset or a 
self-corrective action performed by the inverter. 

11.2 Errors 

Error codes identify a possible equipment fault, or incorrect setting/ configuration. Any and all attempts to correct or 
clear a fault must be performed by qualified personnel. Typically, the Errors code can be cleared once the cause or 
fault is removed.   
However, some of the (E) codes may cannot be cleared, in this case please contact the dealer or CSI Solar Co., Ltd. to 
replace a new one.   
Errors as indicated in the table below:   
 
 
 
 
 
 
 
 

 

Содержание CSI-3.68K-S22002-E

Страница 1: ...CSI 3K S22002 E CSI 3 68K S22002 E CSI 5K S22002 E PV Inverter User Manual Part No 2809002601 Release Date October 2021...

Страница 2: ...ew 3 3 1 Product Introduction 3 3 2 Appearance 3 3 3 Product Nameplate 4 4 Storage 4 5 Unpackaging and Inspection 5 6 Installation 5 6 1 Basic Installation Requirements 5 6 2 Mounting Wall mounting Br...

Страница 3: ...s 14 9 5 Switch off 14 10 Daily Maintenance 15 11 Trouble Shooting 15 11 1 Warning 15 11 2 Errors 15 12 Handling the Inverter 17 12 1 Removing Inverter 17 12 2 Packing Inverter 17 12 3 Disposing Inver...

Страница 4: ...roduct lists and documents published on our website at http www csisolar com as these lists are updated on a regular basis 1 3 Limitation of Liability CSI Solar Co Ltd shall not be held responsible fo...

Страница 5: ...liar with the safety specification about the electrical system 3 Be familiar with the local requirements rules and regulations 4 Understand the composition and working principles of the grid tied PV s...

Страница 6: ...itch Inverter AC Switch Electricity Meter Utility Grid FIG 3 1 PV Power System Diagram 3 2 Appearance Front view and bottom view A B C DE F GH A C B F E D GH C B I F E D G H CSI 3K S22002 E CSI 3 68 5...

Страница 7: ...00 LED Indicators Normal Waiting Steady Green Blinking Green No DC Input Off Error Steady Red More details please refer to the user manual Scan the QR code 624300XXXX FIG 3 3 Inverter Nameplate for re...

Страница 8: ...rter s weight for a long period time Please check the inverter s weight in the product specification of ANNEX B 3 The inverter is protected to IP65 can be installed indoors and outdoors 4 The humidity...

Страница 9: ...litate heat dissipation and to ensure that no moisture can penetrate the product 15 FIG 6 5 Installation Angle Requirements 13 Do not install the inverter outdoors in salt sulfur or other corrosive ar...

Страница 10: ...lling Positions 2 Drill expansion anchors into the corresponding four holes and then secure the bracket by using screws as per FIG 6 7 FIG 6 8 FIG 6 7 Install Expansion Anchors FIG 6 8 Fix Wall mounti...

Страница 11: ...pplied 7 3 Meter CT Connection Optional The inverter has integrated export limitation functionality To use this function a power meter or a CT must be installed For installation and operation methods...

Страница 12: ...d AC circuit breaker specifications are as follows Inverter type AC circuit breaker specifications CSI 3K S22002 E 25 A CSI 3 68K S22002 E 25 A CSI 5K S22002 E 32 A Recommend maximum AC cable length I...

Страница 13: ...0 8N m PE L N L N PE A A A A DEVALAN type Torque 1 4N m L N PE B B B B N PE L FIG 7 5 AC Terminal Positions 3 Push the threaded sleeve into the plug screw the press nut tightly EXCEEDCONN type DEVALAN...

Страница 14: ...value of the inverter Note Consider temperature coefficient of the PV modules Check the inverter specification in section ANNEX B 7 6 2 Wiring Negative Coupler Contactor Pin Positive Coupler Contacto...

Страница 15: ...bottom terminal of the inverter until one sound click audibly The locked DC connectors can only be disconnected with special tool FIG 7 14 Illustration of DC Ports 7 6 3 Connecting PV array DC input D...

Страница 16: ...narios to operate as per FIG 8 2 1 Standard Mode Connect to internet and operate the inverter through CSI cloud web or App 2 Local Mode Connect and operate the inverter locally without internet Soluti...

Страница 17: ...cally when the DC input voltage meets the performance requirement of the utility grid Normally there will be three statuses during the operation refer to the LED indications 1 Waiting Conditions The i...

Страница 18: ...ndertaken in the absence of proper tools test equipment or the more recent revision of the manual with has been clearly and thoroughly understood Items Methods Period System clean Check the temperatur...

Страница 19: ...ect the AC connector turn on DC Switch inverter will restore the grid connection automatically 4 If error message still exists contact Customer service F 107 DC component over range 1 Restart inverter...

Страница 20: ...h sides of the inverter 4 Remove the inverter from the bracket Note Before performing any work ensure that you are familiar with this document 12 2 Packing Inverter If possible use the original packag...

Страница 21: ...DC direct current LED light emitting diode MPPT maximum power point tracking PC personal computer PE protecting earthing PV photovoltaic RCD residual current protective device RCM residual current ope...

Страница 22: ...8 97 5 98 0 European Efficiency 97 1 96 8 97 5 MPPT Efficiency 99 9 99 5 99 9 Safety Protection DC Switch Integrated Anti Islanding Protection Integrated DC Reverse Protection Integrated Insulation Mo...

Страница 23: ...ngsu China 215129 Sales Inquiries Email sales emea csisolar com Customer Support Email service emea csisolar com This manual is subject to change without prior notification Copyright is reserved Dupli...

Страница 24: ...ANNEX C CE RoHS Declaration...

Страница 25: ......

Страница 26: ...ANNEX D REACH Declaration...

Страница 27: ......

Страница 28: ......

Отзывы: