7 Electrical Connection 

 

  9 / 19 

 

7.5 Wiring AC Output 

 

Warning 

To ensure the inverter can be safely disconnected with load, must install a separate single-phase 
circuit-breaker or other load disconnection unit for each inverter. 
Note: The inverter is equipped with integrated RCM (Residual current operated monitor) and RCD 
(Residual current protective device). The rated residual current of the circuit breaker must be over 
300mA when the AC circuit breaker with RCM function selected.   

 

Notice 

The total capacity of PV-inverter is more than 3KW and less than or equal 6KW, the inverter's 
displacement power factor is adjustable between 0.95 leading to 0.95 lagging, and do not need 
external SPI. 
The total capacity of PV-inverter is more than 6KW, the inverter's displacement power factor is 
adjustable between 0.9 leading to 0.9 lagging, meanwhile need external SPI. 

Install an independent two-pole circuit breaker at the output side of the inverter for protection, the recommended AC 
circuit-breaker specifications are as follows:   

Inverter type 

AC circuit-breaker specifications 

CSI-3K-S22002-E 

25 A 

CSI-3.68K-S22002-E 

25 A 

CSI-5K-S22002-E 

32 A 

Recommend maximum AC cable length:   

Inverter type 

Conductor cross section 4.0mm

2

 

Conductor cross section 6.0mm

2

 

CSI-3K-S22002-E 

53 (m) 

79 (m) 

CSI-3.68K-S22002-E 

45 (m) 

67 (m) 

CSI-5K-S22002-E 

29 (m) 

43 (m) 

 
AC Three-core cable: 
The grid connection is established by using three-core wire (L, N, and PE, as per FIG. 7-3). 
Components of AC connector: 
The AC connector is made of four components: pressure nut, sealing ring, threaded sleeve, plug. 

 

Pressure Nut                      Sealing Ring                        Threaded Sleeve                    Plug (Metal pins and shell) 

FIG. 7-2 Components of Connector 

 
AC connectors have two types, EXCEEDCONN type or DEVALAN type, follow-up procedure:   
1) Strip the cable’s jacket, and then adjust the relative length of L, N and PE cables, to make the length of PE cable is at 
least 5mm longer than L and N ones, as per FIG. 7-3. 
 

30.0

25.0

PE

N

L

50.0

45.0

PE

N

L

 

EXCEEDCONN type                                                                            DEVALAN type 

FIG. 7-3 Adjust the Cable Length 

 

2

When using flexible cables, the conductor must be connected with suitable core end ferrules according to DIN 

46228-4, as per FIG. 7-4. 

Содержание CSI-3.68K-S22002-E

Страница 1: ...CSI 3K S22002 E CSI 3 68K S22002 E CSI 5K S22002 E PV Inverter User Manual Part No 2809002601 Release Date October 2021...

Страница 2: ...ew 3 3 1 Product Introduction 3 3 2 Appearance 3 3 3 Product Nameplate 4 4 Storage 4 5 Unpackaging and Inspection 5 6 Installation 5 6 1 Basic Installation Requirements 5 6 2 Mounting Wall mounting Br...

Страница 3: ...s 14 9 5 Switch off 14 10 Daily Maintenance 15 11 Trouble Shooting 15 11 1 Warning 15 11 2 Errors 15 12 Handling the Inverter 17 12 1 Removing Inverter 17 12 2 Packing Inverter 17 12 3 Disposing Inver...

Страница 4: ...roduct lists and documents published on our website at http www csisolar com as these lists are updated on a regular basis 1 3 Limitation of Liability CSI Solar Co Ltd shall not be held responsible fo...

Страница 5: ...liar with the safety specification about the electrical system 3 Be familiar with the local requirements rules and regulations 4 Understand the composition and working principles of the grid tied PV s...

Страница 6: ...itch Inverter AC Switch Electricity Meter Utility Grid FIG 3 1 PV Power System Diagram 3 2 Appearance Front view and bottom view A B C DE F GH A C B F E D GH C B I F E D G H CSI 3K S22002 E CSI 3 68 5...

Страница 7: ...00 LED Indicators Normal Waiting Steady Green Blinking Green No DC Input Off Error Steady Red More details please refer to the user manual Scan the QR code 624300XXXX FIG 3 3 Inverter Nameplate for re...

Страница 8: ...rter s weight for a long period time Please check the inverter s weight in the product specification of ANNEX B 3 The inverter is protected to IP65 can be installed indoors and outdoors 4 The humidity...

Страница 9: ...litate heat dissipation and to ensure that no moisture can penetrate the product 15 FIG 6 5 Installation Angle Requirements 13 Do not install the inverter outdoors in salt sulfur or other corrosive ar...

Страница 10: ...lling Positions 2 Drill expansion anchors into the corresponding four holes and then secure the bracket by using screws as per FIG 6 7 FIG 6 8 FIG 6 7 Install Expansion Anchors FIG 6 8 Fix Wall mounti...

Страница 11: ...pplied 7 3 Meter CT Connection Optional The inverter has integrated export limitation functionality To use this function a power meter or a CT must be installed For installation and operation methods...

Страница 12: ...d AC circuit breaker specifications are as follows Inverter type AC circuit breaker specifications CSI 3K S22002 E 25 A CSI 3 68K S22002 E 25 A CSI 5K S22002 E 32 A Recommend maximum AC cable length I...

Страница 13: ...0 8N m PE L N L N PE A A A A DEVALAN type Torque 1 4N m L N PE B B B B N PE L FIG 7 5 AC Terminal Positions 3 Push the threaded sleeve into the plug screw the press nut tightly EXCEEDCONN type DEVALAN...

Страница 14: ...value of the inverter Note Consider temperature coefficient of the PV modules Check the inverter specification in section ANNEX B 7 6 2 Wiring Negative Coupler Contactor Pin Positive Coupler Contacto...

Страница 15: ...bottom terminal of the inverter until one sound click audibly The locked DC connectors can only be disconnected with special tool FIG 7 14 Illustration of DC Ports 7 6 3 Connecting PV array DC input D...

Страница 16: ...narios to operate as per FIG 8 2 1 Standard Mode Connect to internet and operate the inverter through CSI cloud web or App 2 Local Mode Connect and operate the inverter locally without internet Soluti...

Страница 17: ...cally when the DC input voltage meets the performance requirement of the utility grid Normally there will be three statuses during the operation refer to the LED indications 1 Waiting Conditions The i...

Страница 18: ...ndertaken in the absence of proper tools test equipment or the more recent revision of the manual with has been clearly and thoroughly understood Items Methods Period System clean Check the temperatur...

Страница 19: ...ect the AC connector turn on DC Switch inverter will restore the grid connection automatically 4 If error message still exists contact Customer service F 107 DC component over range 1 Restart inverter...

Страница 20: ...h sides of the inverter 4 Remove the inverter from the bracket Note Before performing any work ensure that you are familiar with this document 12 2 Packing Inverter If possible use the original packag...

Страница 21: ...DC direct current LED light emitting diode MPPT maximum power point tracking PC personal computer PE protecting earthing PV photovoltaic RCD residual current protective device RCM residual current ope...

Страница 22: ...8 97 5 98 0 European Efficiency 97 1 96 8 97 5 MPPT Efficiency 99 9 99 5 99 9 Safety Protection DC Switch Integrated Anti Islanding Protection Integrated DC Reverse Protection Integrated Insulation Mo...

Страница 23: ...ngsu China 215129 Sales Inquiries Email sales emea csisolar com Customer Support Email service emea csisolar com This manual is subject to change without prior notification Copyright is reserved Dupli...

Страница 24: ...ANNEX C CE RoHS Declaration...

Страница 25: ......

Страница 26: ...ANNEX D REACH Declaration...

Страница 27: ......

Страница 28: ......

Отзывы: