5.2 Mounting the Inverter
The inverter can be mounted to the wall or metal strut of module. The mounting holes
should be consistent with the size of the bracket or the dimensions shows below.
1. According to the figure 5.2, select the mounting height of the bracket and mark the
mounting holes. For brick walls, the position of the holes should be suitable for the
expansion bolts.
2.MAKE SURE
the
bracket is
horizonta
l and
the mounting holes
A, B,
and
C (in
Figure 5.3) are
in the correct points.
D
rilling the holes on the wall according
the marks.
WARNING:
The inverter must be mounted vertically on a vertical wall.
Use suitable expansion screws of bolts to attach the bracket
To the wall of rack as shown in figure 5.4.
The inverter should be mounted in a vertical position. The steps of mounting are as follows:
Figure 5.3 The dimensions of the mounting bracket (
in mm
)
3. Using the expansion bolts to fix the bracket to the wall.
Install on a vertical surface or structure capable of bearing the weight
.
Must install vertically /- 5. If the inverter is tilted from the vertical plane heat
dissipation can be inhibited. This may reduce system performance or reduce service
life of the inverter.
Visibility of the LED status indicator lights and LCD display screen should be considered.
NOTE:
The inverter must be installed out of reach of children.
A minimum of 500mm clearance is required top, bottom, left and right of the inverter
(isolator enclosures excepted) for air flow and cooling.
500mm
5
0
0
m
m
5
0
0
m
m
500mm
500mm
5
0
0
m
m
5
0
0
m
m
Figure 5.2 Inverter mounting clearance
A
B
C
5.
Installation
A sun shade is recommended to minimise direct sun exposure where ambient
temperature may exceed 40
℃
.
5.
Installation
.12.
.13.