Camus Hydronics proudly introduces MicoFlame 
Grande commercial water heaters / hydronic 
boilers. The MicoFlame Grande boiler is a fan 
assisted boiler based on a push through design 
which offers several venting options. These gas-
burning appliances are thoughtfully designed for 
easy operation and maintenance. We are 
confident that you will come to appreciate the 
benefits of our product. 

 GENERAL INSTRUCTIONS 

The installation of this heater must conform to 
the requirements of the authority having 
jurisdiction or, in the absence of such 
requirements, to the current National Fuel Gas 
Code, ANSI Z223.1 or current CAN/CGA B149 
Installation Codes. All electrical wiring must be 
done in accordance with the requirements of the 
authority having jurisdiction or, in the absence of 
such requirements, with the National Electrical 
Code, ANSI/NFPA 70 or the Canadian Electrical 
Code Part I, CSA C22.1 Electrical Code. 

Vent installations must be in accordance with 
Part 7, Venting of Equipment, of the current 
National Fuel Gas Code, ANSI Z223.1, or 
Section 7, Venting Systems and Air Supply for 
Appliances, of the current CAN/CGA B149, 
Installation Codes and applicable provisions of 
the local building codes. 

When required by the authority having 
jurisdiction, the installation must conform to the 
Standard for Controls and Safety Devices for 
Automatically Fired Boilers, ANSI/ASME CSD-1. 

The qualified installer shall instruct the end user 
in the safe and correct operation of this 
appliance and shall ensure that the heater is in 
safe working order prior to leaving the job site. 
 

WARRANTY: 

Factory warranty shall apply only when the 
boiler is installed in accordance with local 
plumbing and building codes, ordinances and 
regulations, the printed instructions provided 
with it and good industry practices. 

Excessive water hardness causing a lime build-
up in the copper coils or tubes is not a fault of 
the boiler and is not covered by warranty. 
Consult the factory for recommendations for use 
in hard water areas. 

Excessive pitting and erosion on the inside of 
the copper tube may be caused by high water 
velocity or the use of an undersized boiler for a 

DHW application and is not covered by 
warranty. 

Using  or  storing  corrosive  chemicals  in  the 
vicinity  of  this  boiler  can  rapidly  attack  the 
copper tubes and voids warranty. 

The primary heat exchanger of this boiler is 
intended to operate under non-condensing 
conditions. Inlet temperatures must be 
maintained at 115

°

F or higher. Warranty is void 

if the primary heat exchanger is allowed to 
operate in condensing mode. 

Damage caused by freezing or dry firing voids 
warranty. 

This boiler is not to be used for temporary 
heating of buildings under construction. 

2. 

 LOCATION 

Install this appliance in a clean, dry location with 
adequate air supply and close to a good vent 
connection. 

Do not locate this appliance in an area where it 
will be subject to freezing unless precautions are 
taken. 

The appliance is approved for installation 
directly on combustible flooring and should be 
located close to a floor drain in an area where 
leakage from the appliance or connections will 
not result in damage to the adjacent area or to 
lower floors in the structure. 

If necessary a suitable drain pan must be 
installed under the appliance. 

If the appliance is installed above the level of the 
building’s radiation system, a low water cutoff 
device must be installed in the appliance outlet 
at the time of installation. Some local codes 
require the installation of a low water cutoff on 
all systems. 

Locate the appliance so as to provide adequate 
clearance for inspection and service all around 
the unit. It is recommended that 24” be provided 
for the top and sides and 48” for the front. 

This appliance is suitable for alcove installation 
with minimum clearances to combustibles as 
follows: 

Table 1 – Clearance to Combustibles 

TOP: 

12” 

SIDES: 

12” 

REAR: 

12” 

VENT: 

6” 

FLOOR 

0” 

Содержание MicoFlame Grande MFH2000

Страница 1: ...e WHAT TO DO IF YOU SMELL GAS o Do not try to light any appliance o Do not touch any electrical switch do not use any phone in your building o Immediately call your gas supplier from a neighbour s pho...

Страница 2: ...TEMPERATURE SYSTEMS 11 7 6 INSTANTANEOUS WATER HEATER 11 7 7 HOT WATER SYSTEM PIPING 11 8 INSTRUMENTATION AND CONTROLS 15 8 1 SAFETY CONTROLS 15 8 2 CONTROL PANEL 15 8 3 CONTROL DEVICES 18 9 OPERATIO...

Страница 3: ...in the copper coils or tubes is not a fault of the boiler and is not covered by warranty Consult the factory for recommendations for use in hard water areas Excessive pitting and erosion on the inside...

Страница 4: ...and Applicable provisions of the local building codes The operation of exhaust fans compressors air handling units etc can rob air from the room creating a negative pressure condition leading to reve...

Страница 5: ...PLY This appliance is intended to operate at inlet gas pressures not exceeding PSI 14 W C The appliance and its individual gas shut off valve must be disconnected from the supply piping when pressure...

Страница 6: ...xhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed do not operate a summer exhaust fan Close fireplace dampers d Place in operation the appliance being inspect...

Страница 7: ...in operation using lighting instructions provided 8 While the appliance is operating check for flue gas leaks and proper vent operation Seal any flue gas leaks using appropriate gasket or sealing mate...

Страница 8: ...vent manufacturer Aluminium tape must meet the provisions of SMACNA AFTS 100 73 Standard When venting through unheated spaces with single wall vent insulation must be properly wrapped around the vent...

Страница 9: ...tic hot water and hydronic space heating Recommended piping arrangement is shown in Figure 3 Maximum capacity through the CHRM is summarized in Table 5 flows in excess of 60 GPM must be bypassed Figur...

Страница 10: ...st be protected from down drafts rain and debris by using a listed chimney cap Approval of the installation will be at the discretion of authorities having jurisdiction Sidewall and Vertical Venting T...

Страница 11: ...isolation of the heat exchanger for servicing If the appliance is installed above radiation level it must be provided with a low water cutoff device at the time of appliance installation This applianc...

Страница 12: ...e GPM flow by 15 and the head loss by 20 The following example demonstrates the procedure to follow for calculating the revised head for the heat exchanger when using a water glycol mixture Given that...

Страница 13: ...tlet valve until the inlet temperature climbs to 115 F d If the inlet temperature is greater than 115 F but not greater than 140 F no further adjustment is required e Check the inlet temperature after...

Страница 14: ...12 Figure 7 Typical Heating System Figure 8 Typical Low Water Temperature System...

Страница 15: ...13 Figure 9 Typical Instantaneous Water System Figure 10 Typical Water Heating System...

Страница 16: ...14 Figure 11 Typical Water Heating System...

Страница 17: ...ell as T temperature rise 2 Six pre set modes of operation mode 1 2 4 and 5 for heating mode 3 for DHW and mode 6 for operation by a remote controller 3 Operation as an auto reset limit 4 Operation as...

Страница 18: ...pliance pump based on the purge feature The control turns on the appliance pump and stages the appliance to the set point target temperature at the system temperature whenever an external heat demand...

Страница 19: ...this case it is imperative that the system pump operates continuously in order to provide constant circulation past the system sensor The appliance pump then turns back on with the first stage of the...

Страница 20: ...The ignition module is mounted on a rail just behind the outer jacket front access door The ignition module provide ignition sequence flame monitoring and safety shutoff for the pilot Fan Manager Ther...

Страница 21: ...t one of the meter s terminals to the burner ground terminal on the S8600 and the other terminal to the burner ground wire Pilot running without main burner will generate 1 5 A average for best operat...

Страница 22: ...iation for at least 1 hour Check water level in expansion tank If level exceeds of tank volume air is still trapped in system Shut down appliance and continue to run pumps Within 3 days of start up re...

Страница 23: ...Fire Low Fire Three Stages Stage 3 High Fire High Fire High Fire Stage 1 Low Fire Low Fire Low Fire Stage 2 High Fire Low Fire Low Fire Stage 3 High Fire High Fire Low Fire Four Stages Stage 4 High F...

Страница 24: ...ion circuit is completed between the sensor and the burner ground The flame sensing circuit in the ignition module detects the flame current shuts off the spark generator and energizes the combination...

Страница 25: ...1 9 4000 1 9 2 2 1 9 2 2 1 9 2 2 1 9 2 2 FLUE SWITCH RECYCLE POINT W C MODEL Burner 1 Burner 2 Burner 3 Burner 4 2000 1 5 1 9 1 5 1 9 2500 1 1 1 5 1 1 1 5 1 1 1 5 3000 1 5 1 9 1 5 1 9 1 5 1 9 3500 1 2...

Страница 26: ...he electrode does not appear overheated or fouled with carbon It may be necessary to clean the ignition electrode using steel wool Once the pilot appears to be properly set reinstall it into the appli...

Страница 27: ...of sufficient water flow Under these conditions the appliance must be shut down immediately and the heat exchanger checked for damage If the exchanger is damaged from improper installation or operati...

Страница 28: ...re that igniter and ground electrodes are positioned properly Clean with steel wool if necessary Verify that back of burner box is fully engaged into the retaining slot in the combustion chamber base...

Страница 29: ...CTRICAL DIAGRAMS Each MicoFlame Grande appliance will be provided with its own wiring diagram to guarantee that any options ordered with the unit are properly detailed The following diagrams 99 5082 1...

Страница 30: ...28...

Страница 31: ...29...

Страница 32: ...30 16 EXPLODED VIEW MicoFlame Grande...

Страница 33: ...31 17 EXPLODED VIEW MicoFlame Grande Outdoor and or Condensing...

Страница 34: ...4232 14 4232 14 4232 14 4232 14 4232 23 Fan Mounting Support Right 14 4233 14 4233 14 4233 14 4233 14 4233 24 Burner Door Stop 14 4234 14 4234 14 4234 14 4234 14 4234 25 Heat Exchanger Header Stop Bar...

Страница 35: ...standard warranty 2 Years six through ten replacement purchase price pro rated at the following schedule Year six 60 Year seven 65 Year eight 70 Year nine 75 Year ten 80 of the current list price of t...

Страница 36: ...uilt water heaters and heating boilers as well as a into every single unit For more information supplier of specialty HVAC products Our service line is open 24 hours 7 days a week on our innovative pr...

Отзывы: