Camus Hydronics MicoFlame Grande MFH2000 Скачать руководство пользователя страница 26

 

24 

 

Remove burner being careful to not 
damage the igniter or ground 
electrodes. 

3.  Thoroughly clean burner using water or 

air. Check all ports and air channels for 
blockage. 

4.  Reinstall the burner being careful to fully 

engage the back of the burner box into 
the retaining slot in the combustion 
chamber base. Failure to properly locate 
the burner will result in erratic flame 
operation with the possibility of delayed 
ignition on light off. 

5.  Restore electrical power and gas supply 

to the appliance. 

 

Following the lighting instructions 
put the appliance back into 
operation 

 

Check for gas leaks and proper 
appliance and vent operation. 

10.2.  PILOT BURNER 

Turn the pilot firing valve to off position and 
allow the appliance to try for ignition. Observe 
the spark making sure that it is strong and 
continuous. 

If the spark is not acceptable the igniter will have 
to be adjusted. This can be readily 
accomplished after removing the main burner.  
 
The spark gap should be 1/8” to 3/16” between 
igniter and ground rod and 3/8” between igniter 
and surface of metal fiber. Make sure that the 
electrode does not appear overheated or fouled 
with carbon. It may be necessary to clean the 
ignition electrode using steel wool. Once the 
pilot appears to be properly set, reinstall it into 
the appliance making sure to properly tighten 
the pilot line connection. 
 
If the pilot is removed from the main burner in 
the course of servicing the appliance, it is 
important to reinstall it so that there is no gap 
between the top surface of the pilot tube and the 
underside of the metal filter support screen. 
When properly set it will not be possible to slip a 
business card between the pilot burner and the 
support screen. Figure 15 shows the burner box 
assembly with the metal filter cover removed to 
expose pilot tube. 
 
 

Figure 15 – Pilot and Burner Box 

 

 

Once the spark is satisfactory, open the pilot gas 
and allow the pilot burner to light. Once air has 
been purged from the pilot line, the pilot flame 
should appear almost instantly at the initiation of 
spark. Cycle the pilot several times to confirm 
reliability. A properly set pilot will appear blue 
and will engulf the igniter and ground electrode.  

Open the firing valve and allow the main burner 
to light. The pilot must not extinguish. After 
running for 15 minutes, cycle the appliance to 
ensure that the pilot remains stable. 

 

 

 

 

 

 

 
 
 

Содержание MicoFlame Grande MFH2000

Страница 1: ...e WHAT TO DO IF YOU SMELL GAS o Do not try to light any appliance o Do not touch any electrical switch do not use any phone in your building o Immediately call your gas supplier from a neighbour s pho...

Страница 2: ...TEMPERATURE SYSTEMS 11 7 6 INSTANTANEOUS WATER HEATER 11 7 7 HOT WATER SYSTEM PIPING 11 8 INSTRUMENTATION AND CONTROLS 15 8 1 SAFETY CONTROLS 15 8 2 CONTROL PANEL 15 8 3 CONTROL DEVICES 18 9 OPERATIO...

Страница 3: ...in the copper coils or tubes is not a fault of the boiler and is not covered by warranty Consult the factory for recommendations for use in hard water areas Excessive pitting and erosion on the inside...

Страница 4: ...and Applicable provisions of the local building codes The operation of exhaust fans compressors air handling units etc can rob air from the room creating a negative pressure condition leading to reve...

Страница 5: ...PLY This appliance is intended to operate at inlet gas pressures not exceeding PSI 14 W C The appliance and its individual gas shut off valve must be disconnected from the supply piping when pressure...

Страница 6: ...xhaust fans such as range hoods and bathroom exhausts so they will operate at maximum speed do not operate a summer exhaust fan Close fireplace dampers d Place in operation the appliance being inspect...

Страница 7: ...in operation using lighting instructions provided 8 While the appliance is operating check for flue gas leaks and proper vent operation Seal any flue gas leaks using appropriate gasket or sealing mate...

Страница 8: ...vent manufacturer Aluminium tape must meet the provisions of SMACNA AFTS 100 73 Standard When venting through unheated spaces with single wall vent insulation must be properly wrapped around the vent...

Страница 9: ...tic hot water and hydronic space heating Recommended piping arrangement is shown in Figure 3 Maximum capacity through the CHRM is summarized in Table 5 flows in excess of 60 GPM must be bypassed Figur...

Страница 10: ...st be protected from down drafts rain and debris by using a listed chimney cap Approval of the installation will be at the discretion of authorities having jurisdiction Sidewall and Vertical Venting T...

Страница 11: ...isolation of the heat exchanger for servicing If the appliance is installed above radiation level it must be provided with a low water cutoff device at the time of appliance installation This applianc...

Страница 12: ...e GPM flow by 15 and the head loss by 20 The following example demonstrates the procedure to follow for calculating the revised head for the heat exchanger when using a water glycol mixture Given that...

Страница 13: ...tlet valve until the inlet temperature climbs to 115 F d If the inlet temperature is greater than 115 F but not greater than 140 F no further adjustment is required e Check the inlet temperature after...

Страница 14: ...12 Figure 7 Typical Heating System Figure 8 Typical Low Water Temperature System...

Страница 15: ...13 Figure 9 Typical Instantaneous Water System Figure 10 Typical Water Heating System...

Страница 16: ...14 Figure 11 Typical Water Heating System...

Страница 17: ...ell as T temperature rise 2 Six pre set modes of operation mode 1 2 4 and 5 for heating mode 3 for DHW and mode 6 for operation by a remote controller 3 Operation as an auto reset limit 4 Operation as...

Страница 18: ...pliance pump based on the purge feature The control turns on the appliance pump and stages the appliance to the set point target temperature at the system temperature whenever an external heat demand...

Страница 19: ...this case it is imperative that the system pump operates continuously in order to provide constant circulation past the system sensor The appliance pump then turns back on with the first stage of the...

Страница 20: ...The ignition module is mounted on a rail just behind the outer jacket front access door The ignition module provide ignition sequence flame monitoring and safety shutoff for the pilot Fan Manager Ther...

Страница 21: ...t one of the meter s terminals to the burner ground terminal on the S8600 and the other terminal to the burner ground wire Pilot running without main burner will generate 1 5 A average for best operat...

Страница 22: ...iation for at least 1 hour Check water level in expansion tank If level exceeds of tank volume air is still trapped in system Shut down appliance and continue to run pumps Within 3 days of start up re...

Страница 23: ...Fire Low Fire Three Stages Stage 3 High Fire High Fire High Fire Stage 1 Low Fire Low Fire Low Fire Stage 2 High Fire Low Fire Low Fire Stage 3 High Fire High Fire Low Fire Four Stages Stage 4 High F...

Страница 24: ...ion circuit is completed between the sensor and the burner ground The flame sensing circuit in the ignition module detects the flame current shuts off the spark generator and energizes the combination...

Страница 25: ...1 9 4000 1 9 2 2 1 9 2 2 1 9 2 2 1 9 2 2 FLUE SWITCH RECYCLE POINT W C MODEL Burner 1 Burner 2 Burner 3 Burner 4 2000 1 5 1 9 1 5 1 9 2500 1 1 1 5 1 1 1 5 1 1 1 5 3000 1 5 1 9 1 5 1 9 1 5 1 9 3500 1 2...

Страница 26: ...he electrode does not appear overheated or fouled with carbon It may be necessary to clean the ignition electrode using steel wool Once the pilot appears to be properly set reinstall it into the appli...

Страница 27: ...of sufficient water flow Under these conditions the appliance must be shut down immediately and the heat exchanger checked for damage If the exchanger is damaged from improper installation or operati...

Страница 28: ...re that igniter and ground electrodes are positioned properly Clean with steel wool if necessary Verify that back of burner box is fully engaged into the retaining slot in the combustion chamber base...

Страница 29: ...CTRICAL DIAGRAMS Each MicoFlame Grande appliance will be provided with its own wiring diagram to guarantee that any options ordered with the unit are properly detailed The following diagrams 99 5082 1...

Страница 30: ...28...

Страница 31: ...29...

Страница 32: ...30 16 EXPLODED VIEW MicoFlame Grande...

Страница 33: ...31 17 EXPLODED VIEW MicoFlame Grande Outdoor and or Condensing...

Страница 34: ...4232 14 4232 14 4232 14 4232 14 4232 23 Fan Mounting Support Right 14 4233 14 4233 14 4233 14 4233 14 4233 24 Burner Door Stop 14 4234 14 4234 14 4234 14 4234 14 4234 25 Heat Exchanger Header Stop Bar...

Страница 35: ...standard warranty 2 Years six through ten replacement purchase price pro rated at the following schedule Year six 60 Year seven 65 Year eight 70 Year nine 75 Year ten 80 of the current list price of t...

Страница 36: ...uilt water heaters and heating boilers as well as a into every single unit For more information supplier of specialty HVAC products Our service line is open 24 hours 7 days a week on our innovative pr...

Отзывы: