background image

 

Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  76327 Pfinztal  -  Germany        

p. 3/5 (07.2014-04-1)

 

Phone +49(721)46596-0  -   Fax +49(721)46596-77  -   

www.camtec-gmbh.com

 - 

[email protected]

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death

 

 

 

Technical Concept 

The Camtec HSR03201 series is a high precision switch mode power supply for an upscale demand. The unit 
is  voltage  adjustable.  It  is  engineered  and  manufactured  by  CAMTEC  in  Germany.  The  designed  meets 
challenging  applications  like  railway,  complex  drives,  battery  charging  for  DC-UPS,  test-stands,  machine-
building and infrastructure projects. The power supply provides a low ripple-noise, a precise load-regulation and 
high  efficiency  up  to  91%.  High-end  long-life  capacitors  guarantee  an  extended  hold-up-time  and  an 
extraordinary lifetime of the power supply. The circuit design starts complex loads easily. The internal control 
circuit manages illegal operating conditions to prevent  your system from damages. The HSR series features 
active high input transients with suppressor diodes, X2-capacitors and varistors. All inputs, outputs and feature 
connections are galvanic isolated. The design rules set value on extended interference immunity and safety. 
The unit is designed in accordance to the EN60950-1 and the EMC-compatibility to EN55022. Our engineering 
design is made in accordance to the CSA/UL60950-1 and the IEEE CB scheme rules. 

 
 

Overtemperature, Over Voltage Protection & Derating 

OT Over Temperature

 The maximum ambient temperature is +70°C. There is 

temperature protection inside the power supply. When the temperature exceeds 
a certain level the HSR03201 will be shut down. The unit provides an automatic 
restart 

when 

the 

temperature 

returns 

to 

applicable 

conditions. 

 

OVP  Over  Voltage  Protection 

Exceeding  the  OVP  results  into  ticker  mode. 

Resuming the failure causes automatic restart into normal operation. 

 

 

DC-OK (Power Good Relay) 

The DC ok relay indicates if the output voltage is low. The contact is galvanic insulated to 
the AC input and the DC output connections. The isolation covers the overall adjustment 
range of the HSR03201 series up to 60Vdc. If the DC voltage is ok the relay is closed. If the 
power supply unit is in false operation the relay is open.  
 

 

C/V Current Voltage Behaviour 

The HSR03201 series provides a good current voltage chart. It has no fold back or other abnormalities. The 
output voltage can drop down to zero volts when the power supply is overloaded. The unit delivers a stable and 
constant current to the outputs. When the output voltage is set to the maximum demanded value and the 
current limit reaches its margin, the output voltage drops down and the unit delivers constant current.  

 

Connections 

AC Main Input                

L - wire 
N - wire                                   
PE - wire                                                                                         

DC Mains 

 

DC + voltage                           
DC + voltage 
DC - voltage 
DC – voltage 

Outputs 

DC-ok power good relay  
DC-ok power good relay 
 

 

 

 

 

 

 

Parallel Operation & Decoupling 

T

o

 increase the overall power of the power supply, two or more devices of the same model with the same 

output voltage may be operated in parallel. To avoid any issues, make sure the cable lengths and cable cross-
sections of all power supplies to the star point are identical. 

Содержание HSE03201 Series

Страница 1: ...housing Up to 91 efficiency 20 C 60 C full output power C V curve down to 0V no fold back Free air convection Galvanic insulated Continuous short circuit protected Overload low voltage protected Open Circuit Proof Soft start auto recovery Hold up time 30ms Switching frequency typ 100KHz EMI EMS EN61000 6 2 3 EN55022 class B PFC EN61000 3 2 class A IEC EN 60950 1 Series parallel operation DIN Rail ...

Страница 2: ... Vout 1 Load regulation 0 5 10 100 100 10 Response to Load Change 1ms 10 100 100 10 Short Circuit Protection Continuous Open Circuit Proof Continuous Efficiency 91 typical at 90 load Load Protection 1 2x Irated with auto recovery Voltage Protection 140 of Uout with auto recovery Hold Up Time 30ms 230Vac Inrush Current 10 6Aeff 15Apeak active inrush current limiter inside MCB Circuit Breaker 4A typ...

Страница 3: ...Voltage Protection Derating OT Over Temperature The maximum ambient temperature is 70 C There is temperature protection inside the power supply When the temperature exceeds a certain level the HSR03201 will be shut down The unit provides an automatic restart when the temperature returns to applicable conditions OVP Over Voltage Protection Exceeding the OVP results into ticker mode Resuming the fai...

Страница 4: ...which apply the voltage with a slow ramp b Connect L1 and N together as well as all output poles c Use only AC test voltages with 50 60Hz The output voltage is floating and has no ohmic reference to ground d If testing output voltages are 60Vdc remain to security directives Use only isolated screw drivers to adjust output voltages Mechanics Installation Instruction of the HSR03201 Stable metal alu...

Страница 5: ...evention 2 Installation and service only by trained persons The AC power must be switched off The work is to be labeled accidental reconnection of the system must be prevented 3 Opening the device its modification loosening bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for an...