Camtec Systemelektronik GmbH – Gewerbestraße 30 – DE76327 Pfinztal – Germany 

         

p.4/4

 

10.09A

 

Phone 0049(721)46596-0  -  Fax 0049(721)46596-77 – 

www.camtec-gmbh.com

 - 

[email protected]

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

 

Terminal Connects:    
                

 

1 = L                                     

SK1  

  

2 = N                                   

 

3 = GND+/ PE                                                                                         

 

1 = Battery Extension Input +                              

 

2 = Battery Extension Input -     

 

3 = DC + (connected to GND/Housing)         

SK2

 

4 = DC - 

 

5 = AC-Line Fail Relay 

 

6 = AC-Line Fail Relay 

 

A = Charger o.k. Relay 

SK3

 

A = Charger o.k. Relay 

 

B = AC Main Line Power o.k. Relay 

 

B = AC Main Line Power o.k. Relay 

 

 

GND-Screw (external) 

Is the PE-connection to 
the housing. Note that 
the +pole is internal 
connected to GND, too 

Battery Management Switch: 

We advise the battery management to be switched into the off-position for shipping, storing or for service operations (battery change!). If 
the switch is not in the off-position, the batteries can be damaged while beeing total discharged! The piezo warning sound of AC-main 
failure and the DC-battery backup connection is disbaled while the switch is put into the off-position. To enable the battery backup and all 
warnings, make sure that the battery management is put into the on-position (normal operation mode). 

Order Codes: 

DCUPS2U4AH.56  for 48Vdc(56,0Vdc/4Ah/1A) , ad .DF for the DC-Fail-Monitoring-option to the order code, sample: DCUPS2U4AH.56.DF 

 
Available Component Parts: 

AC-line cable L=2m H05VV1,5 with isolated ground receptacle CEE7/7 IEC60083 and connector C13 IEC60320-1 Schurter 4782, Order Code: 3061060001CA 
DC-line connector AWG10…24/0,2…44mm² with housing, 45° wiring outlet, and M3 screw fittings, Order Code: 3061051001CA 
Monitor line cable with two metal Sub-D 9pole 1:1 with kurled screws, 35° wiring outlet, L=3m Lappkabel LiYY0.5 DIN47100, Order Code: 3061052001CA 

Attention: always use C13 connector Schurter 4782 to enable securing clips to fit to the AC-line cabeling, other C13-connectors may not fit

 

Mechanics & Installation: 

Stable aluminium housing IP20 to allow adequate convection, a free air space of 1U (top/bottom) and 5mm (sidewalls) is required for the 
DCUPS2U; for active devices 15mm space from its sidewalls. For free air convection it is necessary to install the DCUPS2U horizontal 

Battery type for service replacement: 

To guarantee safe function it is advised to use the same battery type as the installed one, to DC-UPS. The battery type is the Panasonic 
LC-R124R5P 12V 4,5Ah . We recommend the batteries to change after 2 years cycle operation to prevent malfunctions. 

 

 

 
 
 

 
 

 

 
 
 
 

Safety Instructions: 

Please read all warnings and advices carefully before installing or operating the DCUPS2U. Retain this operation manual 

always ready to hand.The DCUPS2U must be installed by specialist staff only.

 

 

Installation: 

1.)  The DCUPS2U is designed for systems fulfilling the safety norms of 

dangerous voltages/energy and fire prevention 

2.)  Installation is restricted to specialists only, make sure that the AC 

wire system is free of voltage 

3.)  Opening the DCUPS2U, making any modifications to it, dismounting 

any screws from it, operating the DCUPS2U out of specification 
and/or using it in appropriate area will unevitably result in loosing 
manufactureres guarantee; we decline taking any responsibility for 
risk of demages caused to someones health or to any installed 
system. 

4.) 

Attention: The DCUPS2U has input fuses for the L and the N line. 

Replace the fuses only with the same type; we recommend to use 
the same manufacturer. The fuses must be UL-certified switch type. 
It is also necessary to wire an automatic circuit braker to the line. 
We suggest to use a 16A-type with B-characteristic. It is verboten to 
operate the DCUPS2U without protective earth wired.

 

5.) 

It is recommended to replace the internal batteries by the same 

valve regulated lead-acid battery type with Faston 197 connectors: 
Panasonic LC-R124R5P. For replacing the battery please consult 
your service provider or send the DCUPS2U to the manufacturer.

 

6.) 

After lifetime batteries has to be given to a cetified recycle company.

 

 

Warnings

Disregard these warnings can cause fire, electic shock, serious 
accident and death. 
 

1. 

Never operate the DCUPS2U without Protective Earth 

Conductor 

2. 

Before connecting the DCUPS2U to the AC wire 

system make all wires free of voltage and assure 
accidently switch on 

3. 

Allow neat and professionel cabeling 

4. 

Never open nor try to repair the DCUPS2U by yourself. 

Inside are dangerous voltages that can cause electric 
shock hazard. 

5. 

Avoid metal pieces or other conductive material to fall 

into the DCUPS2U 

6. 

Do not operate the DCUPS2U under damp or wet 

conditions 

7. 

It is verboten to operate the DCUPS2U under Ex 

conditions or in Ex-Area 

 

 

H= 2U = 88,1mm 
B= 84WU(TE) = 426,4mm 
T= 280mm 

We use a very robust full aluminium housing with stable 
aluminium handholds, drawn side frames and a 2,5mm 
aluminium anodized front plate. 

Содержание DCUPS2U4AH

Страница 1: ...Specification Metal housing 90 efficiency 10 C 40 C ambient Free air convection Galvanic insulated Continuous short circuit idle proof Overload low voltage protected Soft start auto recovery Hold up time 30ms Minimum load 0A EMI EMS EN61000 6 2 3 EN55022 class B pole connected to GND housing According to IEC EN 60950 1 Extended monitoring Thermal load protection AC Fail message Built in high relia...

Страница 2: ...ions Pollution Degree 2 EN50178 Climatic Class 3K3 EN60721 Dimensions HxWxD T 2U 84WU D 280mm Weight 9800g Connector AC C14 Schaffner IEC60320 1 L N lines fused Dismounting protected by a securing clip Schurter 4700 0001 Connectors DC Phoenix 1840599 DFK PC4 6 GF 7 62 Female Dismounting protection with M3 threads for the mating plug Connector DC Fail Message SUB D 9pole female DIN41652 T1 Specific...

Страница 3: ...th 50 60Hz The output voltages is floating and has no ohmic reference to ground d If testing output voltages are 60Vdc remain to security directives Use only isolated screw drivers to adjust output voltages Function Table and Messages optional available Indicators AC Line o k green LED AC Fail Relay Contact Battery o k LED green Battery Low LED red Battery Charge LED yellow Piezo Sound Interval 30...

Страница 4: ...vised to use the same battery type as the installed one to DC UPS The battery type is the Panasonic LC R124R5P 12V 4 5Ah We recommend the batteries to change after 2 years cycle operation to prevent malfunctions Safety Instructions Please read all warnings and advices carefully before installing or operating the DCUPS2U Retain this operation manual always ready to hand The DCUPS2U must be installe...

Отзывы: