Block Diagram 

 

     

Main connector: 

1) 

Battery Ext 

2) 

Battery Extension - 

3) 

Battery Out + 

4) 

Battery Out –  

5) 

Power Fail Message 

6) 

Power Fail Message 

 
         

Available Options (Sub-D): 

A) 

DC-o.k.-monitoring for the 

battery charger power supply 

B) 

DC-o.k.-monitoring for the 

main power supply 
 

 
 

 

 
 

AC Fail Message 

 

Low Voltage:  
If the AC-Input drops -20% the AC-OK-
Relay (R) opens (control message). The 
green DC-OK LED is off. 
 
 

 

Test 

Time  A 

 
Type test and factory tests are  
conducted by the manufacturer.  
Do not repeat the test in the  
field. Field test rules:

 

Type Test 

60s 

2500Vac  3000Vac  500Vdc  500Vdc 

Factory Test 

5s 

2000Vac  2000Vac  500Vdc  500Vdc 

Field Test 

2s 

2000Vac  2000Vac  500Vdc  500Vdc 

 

a)  Use approriate test equipment which apply the voltage with a slow ramp 
b)  Connect L1 and N together, as well as all output poles 
c)  Use only AC test-voltages with 50/60Hz. The output voltages is floating and has  

no ohmic reference to ground. 

d)  If testing output voltages are ≥60Vdc remain to security directives.  

Use only isolated screw drivers to adjust output voltages. 
 

Function Table and Messages 

 

 

 

 

 

 

 

                            

*) optional  available

 

Indicators 

AC-Line o.k. 
green LED 

AC-Fail 
Relay 
Contact 

Battery o.k. 
LED green 

Battery Low 
LED red 

Battery 
Charge 
LED yellow 

Piezo Sound 
Interval 30s 

Battery 
Extension  
LED green 

*)

 DC-o.k. 

Relay 1 

(Charger)

 

*)

 DC-o.k. 

Relay 2  

(Main AC-power)

 

Normal operation 

On 

Closed (C) 

On 

Off 

Off 

Off 

On  

(if connected) 

Open 

Open 

AC-Main line fail at 
184Vac 

Off 

Open (O) 

On 

Off 

Off 

On 

On  

(if connected)

 

Closed 

Closed 

Battery Low Voltage 
α  < 38Vdc 

On/ 
Off 

(AC-fail)

 

C/O 

(AC-fail)

 

Off 

On 

On/ 
Off 

(AC-fail)

 

Off/ 
On 

(AC-fail)

 

On 

(if connected)

 

Open/ 
Closed 

(AC-fail)

 

Open / 
Closed 

(AC-fail)

 

Battery  
38Vdc < α > 52Vdc 

On/ 
Off 

(AC-fail)

 

C/O 

(AC-fail)

 

Off/ 
On 

(AC-fail)

 

Off 

On/ 
Off 

(AC-fail)

 

Off/ 
On

(AC-fail)

 

On  

(if connected)

 

Open/ 
Closed 

(AC-fail)

 

Open/ 
Closed 

(AC-fail)

 

Battery o.k. > 52Vdc 

On/ 
Off 

(AC-fail)

 

C/O 

(AC-fail)

 

On 

Off 

Off 

On/Off 

(AC-

fail)

 

On  

(if connected)

 

Open/ 
Closed 

(AC-fail)

 

Open/ 
Closed

 (AC-fail)

 

Charger Power 
Supply disable 

On 

Open 

Off 

(<90%)

 

On 

(<70%)

 

Off ! 

Off 

On  

(if connected)

 

Closed 

Open 

Main Power Supply 
disable 

On 

Open 

Off 

(<90%)

 

On 

(<70%)

 

Off ! 

Off 

On  

(if connected)

 

Open 

Closed 

 
 
 

SMPS 
Charger 

PE 
 
                  
 
L       Fuse 
 
 
 
 
N      Fuse 

Battery 

Logic 


Main 
Connector 

EMI 
Filter 

Power 
Fail  

SMPS 
Main 


Sub-D 

GND 

DC-Fuse 

Содержание DCUPS2U4AH

Страница 1: ...Specification Metal housing 90 efficiency 10 C 40 C ambient Free air convection Galvanic insulated Continuous short circuit idle proof Overload low voltage protected Soft start auto recovery Hold up time 30ms Minimum load 0A EMI EMS EN61000 6 2 3 EN55022 class B pole connected to GND housing According to IEC EN 60950 1 Extended monitoring Thermal load protection AC Fail message Built in high relia...

Страница 2: ...ions Pollution Degree 2 EN50178 Climatic Class 3K3 EN60721 Dimensions HxWxD T 2U 84WU D 280mm Weight 9800g Connector AC C14 Schaffner IEC60320 1 L N lines fused Dismounting protected by a securing clip Schurter 4700 0001 Connectors DC Phoenix 1840599 DFK PC4 6 GF 7 62 Female Dismounting protection with M3 threads for the mating plug Connector DC Fail Message SUB D 9pole female DIN41652 T1 Specific...

Страница 3: ...th 50 60Hz The output voltages is floating and has no ohmic reference to ground d If testing output voltages are 60Vdc remain to security directives Use only isolated screw drivers to adjust output voltages Function Table and Messages optional available Indicators AC Line o k green LED AC Fail Relay Contact Battery o k LED green Battery Low LED red Battery Charge LED yellow Piezo Sound Interval 30...

Страница 4: ...vised to use the same battery type as the installed one to DC UPS The battery type is the Panasonic LC R124R5P 12V 4 5Ah We recommend the batteries to change after 2 years cycle operation to prevent malfunctions Safety Instructions Please read all warnings and advices carefully before installing or operating the DCUPS2U Retain this operation manual always ready to hand The DCUPS2U must be installe...

Отзывы: