CPS-EP3000(R2) MANUAL

                

Camtec Power Supplies GmbH  -  Gewerbestrasse 30  -  DE-76327  Pfinztal / Germany   

P.3/19 (01/2018.01.1) 

Tel. +49 (721) 46596 - 0  Fax +49 (721) 46596 - 77    

www.camtec-gmbh.com

   -   

[email protected]

 

(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death) 

 

Features 

 

Idling behavior

 

The CPS-EP Series is permanently open-circuit proof. When an output 
voltage is preset it comes stable. If a load is switched suddenly, the unit 
stabilized within <1ms. An overshoot of the output voltage is irrelevant. 
 

Start behavior

 

The power supply has a start delay of 1s to stabilize all measuring circuits 
for the interface messages accurately. The power supply starts with a 
ramp (soft start) of 100ms. The output voltage does not overshoot - 
regardless of whether a load is connected or not. 
 

Galvanic isolation and insulation

 

The switching power supply is galvanically isolated between the input and 
the output. All major digital inputs and outputs of the interface are 
electrically isolated. 
 

Voltage set (Uadj) 

The output voltage of the CPS-EP power supply can be adjusted by a 
potentiometer located at the rear of the unit. The current limit is fix. The 
power supply operates data stable even at all output voltages. 

 

C Monitor (Imon) 

The power supply provides real-time monitoring of the output current. It is 
the exact and real value at the output terminals. The latency signal preset 
to the measured value is negligible since the control circuit is constructed 
completely analogously. 
 

Potentiometer Internal Control (Uadj)

 

The power supply will be set with an internal potentiometer. It is located at 
the rear of the unit. 
 

Sense Mode 

The power supply has a sense mode to compensate for voltage drops of 
2V per load line. 
 

Continuous Mode

 

The unit operates in continuous mode. In the continuous mode, the power 
supply provides constant current mode in a continuous flow and no ticker-
operation. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Current Share Bus (CS)

 

In parallel operation, the involved network components communicate with each 
other and share the total power evenly to each other. 
 

Remote Shutdown (SD) 

All CPS-EP devices have a remote shutdown (open collector or switching 
contacts). 
 

Inhibit Mode (Interlock) 

The inhibit circuit reliably prevents unintentional starting of the power supply. The 
control loop is internally locked. Since this blocking is done progressively it is 
active even when the control signal, is missing due to a cable break or temporarily 
suspend. A premature restart of the power supply is prevented. 
The inhibit input can be connected to a relay or switch. If the contact is interrupted, 
the power supply is switched off. If the contact is closed again, the power supply 
restarts.

 

 

DC and AC Fail 

By DC-fail the power supply reports that the power output is disabled. 
By AC-fail the power supply reports an AC undervoltage. Both signals have 
separate outputs. Each of them can be selected between NO and NC.

 

 

Over Voltage Protection (OVP) 

Until the abolition of the fault the device switches off. 
 

Over Current Protection (OCP)

 

The power supply provides continous current when it is overloaded. The voltage 
goes down to zero voltage.

 

 

Temperature Thermal Shutdown (OT)

 

The device has a thermal monitoring. When the temperature of the power supply 
is higher than the over temperature protection threshold, the unit shuts down and 
automatically restarts. An alarm signal is applied to the interface. 

 

Fan Failure Monitoring (FF)

 

If it comes to a fan failure or blocking, a signal is applied to the interface. The 
speed signal of the fan is monitored. Thus, even a creeping fault is detected at an 
early stage and there is a warning long sold separately in front of a fan failure. 
 

3D-HD (3D Heat Dissipation)

 

Our aligned and controlled heat dissipation design opens possibilities that are 
formerly being reserved to custom design power supplies: Steplessly hard mount 
of the CPS-EP2000/3000 power supply modules in a 3D-room. 
In practice that means that one can mount the modules into every angle 
imaginable. Our 3D heat dissipation (3D-HD) ensures optimal cooling in each 
mounting position you may consider. 
 

Design-to-Service:

 

Most recorded failures in the field concern the signal interface of a power supply. 
Camtec offers new concept of design-to-service that allows the customer easily to 
exchange the interface himself in the field. The analogue and digital interfaces 
apply plug & play self calibrating and can be used independent from the model 
CPS-i/EX/EP 2000 & 3000 Thus, system down cost is being reduced and only a 
small amount of spare parts need to be stocked by the customer. 

 

Содержание 3041109001CA

Страница 1: ...issipation CSB Current Share Bus Inhibit for safe interlocking Remote Shutdown Sense mode Current Monitoring 0 5V Power Good Relay DC ok Precise dynamics on load change Series parallel operation up to 100kW EMC conducted class B radiated class A Efficiency 92 94 PFC Powerfactor 0 99 Variable controlled fans from Papst Long lifetime under hard operation Solid 2U and 3U subframes available Model Vol...

Страница 2: ...ons call for the highest standards of safety and interference suppression The device was developed in accordance with the requirements of EN61010 1 EN61010 2 201 EN62368 1 and the EMC standards EN55032 conducted Class B radiated Class A The mechanical design of the CPS EP3000 device series is unique It is the first power supply line in the world market which can be flexibly adapted to any installa...

Страница 3: ...switching contacts Inhibit Mode Interlock The inhibit circuit reliably prevents unintentional starting of the power supply The control loop is internally locked Since this blocking is done progressively it is active even when the control signal is missing due to a cable break or temporarily suspend A premature restart of the power supply is prevented The inhibit input can be connected to a relay o...

Страница 4: ...1 Temperature Control yes thermal shutdown autorecovery 70 C outside measuring point distance 10mm Hold Up Time 20ms 230Vac mains buffering at full load Inrush Current 14 6Aeff 20 7Apeak 230Vac active electronic inrush protection no simple NTC Startup Delay typ 1s Softstart typ 100ms Ambient Temperature 20 C 60 C operating derating 2 5 C 50 C Storage Temperature 40 C 85 C Ambient Conditions Humidi...

Страница 5: ...onnected No Function 3 DGND Digital Ground 4 NC NC Not Connected No Function 5 NC NC Not Connected No Function 6 NC NC Not Connected No Function 7 FF Output Signal Fan Failure Open Collector 8 NC NC Not Connected No Function 9 OT Output Signal Over Temperature Open Collector 10 NC NC Not Connected No Function 11 NC NC Not Connected No Function 12 NC NC Not Connected No Function 13 NC NC Not Connec...

Страница 6: ...8 01 1 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death Schematic of the internal circuits CON1 4 NC NC ...

Страница 7: ...wercon powercon 20 a nac3fca CON1 Push In 0 14 1 5mm AWG26 16 CON2 CON3 CON4 DC M8 200A 60 C 250Vac 20A Neutrik PowerCon 3x2 5 mm Neutrik NAC3FCA Interface pluggable Push Pull Connectors from Weidmueller included Input Power Connector Neutrik NAC3FCA included Output Power Connection M8 Powerbars Lock Pins snap into the 2U 3U 19 subrack WARNING OUTPUT CONNECTION INSTRUCTION Mount the cable lugs dir...

Страница 8: ...ge drop over long load lines The compensation amounts to a maximum of 2V per load line Under certain circumstances it can be expected to apply more complicated external interference suppression If sense is not used CON4 Sense and Sense shall necessarily be connected by short bridges to the power outputs factory setup Sense operation Remove the bridges between Sense Sense and the power outputs Conn...

Страница 9: ... the participating power supplies is important To prevent one of the power supplies going early into the current limitation and display error message An uneven load and thus premature aging of the participating devices is prevented further information on page 12 Connect CON3 contact 5 CS to contact 13 of the next device Are other devices involved in the parallel operation you may grind the CS bus ...

Страница 10: ...forced Isolation of max 400Vdc and a basic isolation of max 600Vdc working voltage DC OK Relay DC Power Good The signal DC OK has potential free relay contacts changeover The contacts of CON1 Pin2 and CON1 Pin4 are closed relay coil is energized when the power operates as a connstant voltage source The contacts CON1 Pin2 and CON1 Pin4 are open when the power output is inhibited by SD INH OT FF OVP...

Страница 11: ...ad conditions also see OT thermal SD Model Value UA1 V Value IA1 A Value UA2 V Value IA2 A Pmax IA1 IA2 CPS EP3000 012 15Vdc 160A 12Vdc 200A 2400 2400W CPS EP3000 024 30Vdc 100A 24Vdc 125A 3000 3000W CPS EP3000 036 45Vdc 66 7A 36Vdc 83A 3002 2988W CPS EP3000 048 58Vdc 51 7A 48Vdc 62 5A 2999 3000W CPS EP3000 072 90Vdc 33 3A 72Vdc 41 6A 2997 2995W CPS EP3000 110 150Vdc 20 0A 110Vdc 27 2A 3000 2992W ...

Страница 12: ...plicable to EN62368 1 Due to the dielectric strength of the internal components used only the models with an output voltage of 48Vdc and later are approved for series operation Other power supplies are not approved for series operation above 60Vdc Parallel Operation N 1 Decoupling To increase the overall power of the power supply up to 5 units of the same model with the same output voltage may be ...

Страница 13: ...l Germany P 13 19 01 2018 01 1 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death ...

Страница 14: ...cal Safety Factory Test Field Test Owner 48Vdc 2800Vdc Type and factory test are the manufacturer While repating damage can happen to the power supply unit For the field test owner follow the below instruction a Use suitable test equipment raising the voltage slowly b Short circuit L1 and N and all the DC output terminals c Use only test voltages of 50 60Hz The outputs are unearthed and therefore ...

Страница 15: ...result in injury or death Mechanics Aluminium housing IP20 Cooling is achieved via front to rear fans To ensure adequate heat dissipation 50mm to the front and 150mm blockade free distance from the device back wall must be guaranteed The harnesses are to be designed and installed to that the air outlet of the unit is not being blocked In a rack mounting of multiple subracks the rear distance of th...

Страница 16: ...ww camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death 19 Subrack 2U 3U 2U Subrack for 1 3 CPS EX3000 with up to 9kW continuous power 3U Subrack for 1 5 CPS EX3000 with up to 15kW continuous power ...

Страница 17: ...to custom design power supplies Steplessly hard mount of the CPS EP2000 3000 power supply modules in a 3D room In practice that means that one can mount the modules into every angle imaginable Our 3D Heat Dissipation 3D HD ensures optimal cooling in each mounting position you may consider All you may consider is to make sure that at least a distance of 5cm 2 Inch to the front cooling slots and 15c...

Страница 18: ...ace 3041109001CA CPS EP3000 024 R2 24Vdc model incl analogue interface 3041109002CA CPS EP3000 036 R2 36Vdc model incl analogue interface 3041109003CA CPS EP3000 048 R2 48Vdc model incl analogue interface 3041109004CA CPS EP3000 072 R2 72Vdc model incl analogue interface 3041109005CA CPS EP3000 110 R2 110Vdc model incl analogue interface 3041109006CA CPS EP3000 220 R2 220Vdc model incl analogue in...

Страница 19: ...bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things 4 Note The device must not be operated without an upstream circuit breaker CB We recommend the use of B Type 25A It is prohibited to use the unit without PE It may be necessary upstrea...

Отзывы: