CPS-EP3000(R2) MANUAL
Camtec Power Supplies GmbH - Gewerbestrasse 30 - DE-76327 Pfinztal / Germany
P.11/19 (01/2018.01.1)
Tel. +49 (721) 46596 - 0 Fax +49 (721) 46596 - 77
www.camtec-gmbh.com
-
(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
Fan Fail Signal (FF)
The power supply fans are continuously monitored. FF occurs when one or both fans have an error (lower
speed due to bearing contamination, blockage, or failures). A failure message is sent: The status signal FF
applies high. Output Open Collector I
MAX
=10mA, V
LOW
≤
0,6V, V
MAX
=30V.
C/V Chart and Operating Point
The output voltage set Vout is set with the potentiometer at the rear oft he power
supply.
The current limit is fix.
The system integrator must make sure that the nominal output power does not
exceed below values to protect the unit from operating under overload conditions.
(also see OT thermal SD)
Model
Value UA1 (V)
Value IA1 (A)
Value UA2 (V)
Value IA2 (A)
Pmax (IA1/IA2)
CPS-EP3000.012
15Vdc
160A
12Vdc
200A
2400/2400W
CPS-EP3000.024
30Vdc
100A
24Vdc
125A
3000/3000W
CPS-EP3000.036
45Vdc
66,7A
36Vdc
83A
3002/2988W
CPS-EP3000.048
58Vdc
51,7A
48Vdc
62,5A
2999/3000W
CPS-EP3000.072
90Vdc
33,3A
72Vdc
41,6A
2997/2995W
CPS-EP3000.110
150Vdc
20,0A
110Vdc
27,2A
3000/2992W
CPS-EP3000.220
300Vdc
10,0A
220Vdc
13,6A
3000/2992W
Inrush Current Limiter (electronic)
The power supply unit has an electronic current limiter
(230Vac=14,6A
rms
/20,7A
peak
).
It is a precisely working circuit instead of a usual simple NTC
solution. The accuracy is ±10%, regardless of the operating
temperature and the duty cycles (interval
≥
10s). We recommend
the smallest circuit breaker a characteristic B with 25A.
Temperature Monitoring & Derating
The maximum ambient temperature during
operation is + 60°C. If the overtemperature
protection is activated, the power supply but
not the fan is switched off.
The measuring point is 50mm outside the
power supply at the front side (fan/blower
input). The power supply unit starts
automatically when it has cooled down.