background image

SDM-CD16D 16 Channel Digital Control Port Expansion Module

4

Table 1  Datalogger to SDM-CD16D Connections

Connection Order

SDM-CD16D

Datalogger

Function

First

12V

12V on datalogger or

external supply

Power

Second

C1

C2

C3

or G

C1 (Control Port 1)
C2 (Control Port 2)

C3 (Control Port 3)

Common Ground

Data

Clock

Enable

Multiple SDM-CD16Ds may be wired in parallel by connecting the datalogger
side of one SDM-CD16D to the next.

The transient protection of the SDM-CD16D relies on a low resistance path
to earth. Ensure that the ground return wire has as low a resistance as
possible. Where long cable runs are likely, or where lightning damage is a
possibility, the SDM-CD16D can be fitted with gas discharge tubes. Please
contact Campbell Scientific for details.

For CR10/10X, CR23X and 21X dataloggers, the total cable length
connecting SDM-CD16Ds to SDM-CD16Ds and the datalogger
should not exceed 6m. Total cable lengths in excess of 6m will
adversely affect communication performance.

 

 

For CR7 dataloggers,

the total cable length can be up to 180m.

4.1  Controlled Device Connections

The SDM-CD16D uses spring-loaded terminal blocks, which provide quick,
vibration resistant, connections. The output terminals are labelled 1 to 16. A
common ground connector is provided between each pair of terminals

Use a screwdriver in either the top or front slot, as appropriate, to open the
terminal spring. Strip any insulation from the wire to give 7 to 9mm bare wire.
Push the wire into the opening, and, while holding it in position, withdraw the
screwdriver to release the spring. The wire will now be firmly held in place. See
Figure 4, below.

You cannot reliably insert more than one solid-core wire into one
terminal connector unless the wires are soldered or clamped
together. When inserting more than one stranded wire, twist the bare
ends together before insertion.

NOTE

NOTE

Содержание SDM-CD16D

Страница 1: ...SDM CD16D 16 Channel Digital Control Port Expansion Module User Guide Issued 15 6 99 Copyright 1999 Campbell Scientific Ltd...

Страница 2: ......

Страница 3: ...in lieu of all other guarantees expressed or implied including those of suitability and fitness for a particular purpose Campbell Scientific is not liable for consequential damage Please inform us bef...

Страница 4: ......

Страница 5: ...ddress Selection Switches 5 6 Datalogger Instructions 104 CR10 10X CR23X 21X newer CR7s and 29 older CR7s 6 7 Theory of Operation 7 8 Program Example 7 Figures 1 SDM CD16D 1 2 Equivalent Output Driver...

Страница 6: ......

Страница 7: ...nchronously addressed datalogger peripheral Datalogger control ports 1 2 and 3 are used to address the SDM CD16D then clock out the desired state of each of the 16 control ports Up to sixteen SDM CD16...

Страница 8: ...d EN50082 1 1998 If more detailed output characteristics are required experienced users should consult the equivalent circuit diagrams shown in Figure 2 below Figure 2 Equivalent Output Driver Circuit...

Страница 9: ...ls This limitation reduces the number of available analogue input channels and may make an external supply for the SDM CD16D essential 4 Installation For correct operation the SDM CD16D must be instal...

Страница 10: ...ng SDM CD16Ds to SDM CD16Ds and the datalogger should not exceed 6m Total cable lengths in excess of 6m will adversely affect communication performance For CR7 dataloggers the total cable length can b...

Страница 11: ...nding address Figures 1 and 5 shows the position of the switch Note that you will have to remove the mounting bracket to gain access to this switch Table 2 Switch Position and Addresses Switch Setting...

Страница 12: ...tarting Address base 4 00 33 4 2 Card Excitation card No 5 4 Starting Input Location Execution Time 150ms to 190ms per Rep The number of SDM CD16Ds to be addressed is defined by the Reps repetitions p...

Страница 13: ...controls output 1 When the 16 control bits are clocked in C2 is held high while C3 is pulsed low then high to latch the control bits The datalogger then lowers both C3 and C2 to complete the cycle 8 P...

Страница 14: ...hreshold 2 4 3 23 5 F 4 30 Then Do then 3 Z F P30 put a 1 into heater control 1 1 F location 2 0 Exponent of 10 3 10 Z Loc Heat_1 4 End P95 end then do 5 If X F P89 if the heater is on heater 1 10 X L...

Страница 15: ...hen Do 17 Z F P30 if cooler should be turned off 1 0 F put a 0 into cooler control 2 0 Exponent of 1 location 3 15 Z Loc Cool_1 18 End P95 end then do 19 Else P94 else if cooler is off 20 Z F P30 put...

Страница 16: ...flag 2 is set 1 12 Do if Flag 2 is High 2 30 Then Do then 33 Beginning of Loop P87 start fan loop 1 0 Delay 2 5 Loop Count 34 Z F P30 put a 1 into fan control 1 1 F location 2 0 Exponent of 10 3 20 Z...

Страница 17: ...3 3 11 Heat_2 11 1 0 12 Heat_3 11 1 0 13 Heat_4 11 1 0 14 Heat_5 19 1 0 15 Cool_1 7 3 3 16 Cool_2 11 1 0 17 Cool_3 11 1 0 18 Cool_4 11 1 0 19 Cool_5 19 1 0 20 Fan_1 7 1 3 21 Fan_2 11 1 0 22 Fan_3 11 1...

Отзывы: