RF401-series and RF430-series Spread Spectrum Radio/Modems
4
•
Short Haul modem to radio: PC to short haul modems to radios to
datalogger (see Appendix
(p. G-1)
•
Ethernet network to radio: PC to Internet to NL100 to radio to datalogger
(use LoggerNet IPPort, remote IP address, port number)
1.4 Retired Spread Spectrum Radios
1.4.1 RF400-series Radios
On May 2, 2005, the RF401, RF411, and RF416 replaced the RF400, RF410,
and RF415, respectively. The newer radios have a choice of three
communication protocol settings. The three protocol settings are Transparent,
PakBus Aware, and PakBus Node. Transparent is the protocol used by the
RF400. RF401 and RF430 radios in networks that also have RF400 radios
must use the Transparent protocol setting. Transparent is the default setting for
RF401 radios with operating systems of OS3 or lower.
Do not mix the “Transparent” protocol with any of the
PakBus protocols. This will produce RF traffic without any
RF communications.
The PakBus Aware and PakBus Node settings make the radios easier to use in
a PakBus network. Radios set to PakBus Aware and radios set to PakBus
Node can be in the same network. PakBus Aware is the default setting for
RF430 radios and RF401 radios with an operating system of OS4 or higher.
The PakBus Aware setting is the simplest to use and does not require a PakBus
address. The PakBus Node setting is intended for radios used as stand-alone
routers.
RF400 radios can be upgraded to RF401 radios by sending the RF400 to
Campbell Scientific; an RMA is required.
1.4.2 CR205, CR210, CR215 Dataloggers
On September 15, 2005, the CR206, CR211, and CR216 dataloggers replaced
the CR205, CR210, and CR215 dataloggers, respectively. The newer
dataloggers’ internal radios have two RF Protocol settings, which are PakBus
and Transparent. The PakBus setting is used with RF430 radios and RF401
radios set to PakBus Aware or PakBus Node. The Transparent RF protocol
setting is required when the network contains older equipment (e.g., RF400s,
CR205s).
2. Specifications
Power
Voltage:
9 to 16 VDC
Current:
75 mA typical during transmit (RF401 series)
78 mA typical during transmit (RF430 series)
24 mA typical receiving a signal (RF401, RF411)
36 mA typical receiving a signal (RF416)
26 mA typical receiving a signal (RF430, RF431)
40 mA typical receiving a signal (RF432)
CAUTION
Содержание RF401
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 8: ......
Страница 10: ......
Страница 16: ...Table of Contents vi...
Страница 56: ...Appendix A Part 15 FCC Compliance Warning A 2...
Страница 76: ...Appendix D Setting Up RF401 to CR206 X Communications D 10...
Страница 84: ...Appendix F Non PakBus Example Configurations F 6 FIGURE F 2 PC208W Datalogger Generic Dial String...
Страница 94: ...Appendix H Distance vs Antenna Gain Terrain and Other Factors H 8...
Страница 98: ...Appendix I Phone to RF401 Series I 4 FIGURE I 2 Phone base configuration...
Страница 99: ...Appendix I Phone to RF401 Series I 5 FIGURE I 3 Enter the base site s phone number...
Страница 114: ...Appendix K RF401 RF411 Pass Fail Tests K 8...
Страница 124: ...Appendix L RF401 RF411 Average Current Drain Calculations L 10...
Страница 129: ......