4. Click the Send OS tab.
5. Click Start.
6. Select the file. It will have an .a43 extension.
7. Click OK.
9.2 Troubleshooting
Symptom:
On a CRBasic data logger, data values report NAN, or on a non-Campbell Scientific data logger,
data values do not change when the tipping mechanism is activated and new measurement
commands are issued.
Solution:
1. Verify that the RainVUE-series is wired correctly (
NOTE:
Connect the power wire to the data logger 12V terminal and not the SW12 terminal.
2. Verify that power to the RainVUE-series is in the appropriate range (6 to 18 VDC).
3. Verify that the correct SDI-12 address is being used when communicating with the
RainVUE-series. Use the transparent mode to verify that the data logger can communicate
with the sensor. For additional information, refer to
RainVUE-Series SDI-12 Precipitation Sensors