User Manual
7
d.
Input the
PakBus Address
of the datalogger.
Figure 4-6. Setup screen (EZ View) Datalogger Settings
e.
Press
Next
until you reach the
Communication Setup Summary
screen.
Press
Finish
to complete the setup.
4.2.3
Step 3
– Connect
You are now ready to connect to your datalogger using the
LoggerNet Connect
screen.
Datalogger program transfer, table-data display, and data collection are now
possible.
5.
Specifications
Datalogger Compatibility:
CR1000, CR3000 (both require OS version 28 or
later)
Power Requirements:
12 V supplied through datalogger’s peripheral port
Typical Current Drain:
64 mA w/Ethernet Active @ 10 Mb
58 mA w/Ethernet Active @ 100 Mb
3 mA w/Ethernet Not Active
Note: Ethernet can be put into a low-power state
(not connected to the network, essentially off)
using the
IPNetPower()
or
EthernetPower()
instruction.
Operating Temp. Range:
–40 to 70 °C Standard
–55 to 85 °C Extended