NL115 Ethernet and CompactFlash
®
Module
The
CardOut()
instruction has the following parameters:
StopRing
: A constant is entered for the
StopRing
parameter to specify whether
the
DataTable
created should be a Ring Mode table (0) or a Fill and Stop table
(1).
Size
: The
Size
parameter is the minimum number of records that will be
included in the
DataTable
. If –1000 is entered, the size of the file on the card
will be the same as the size of the internal table on the datalogger. If any other
negative number is entered, the memory that remains after creating any fixed-
size tables on the card will be allocated to this table. If multiple DataTables
are set to a negative number, the remaining memory will be divided among
them. The datalogger attempts to size the tables so that all of them will be full
at the same time.
In the following example, the minimum batt_voltage and a sample of PTemp
are written to the card each time the data table is called. The
StopRing
parameter is 0 for Ring mode. This means that once the data table is full, new
data will begin overwriting old data. The
size
parameter is –1, so all available
space on the card will be allocated to the table.
DataTable(Table1,1,-1)
CardOut(0 ,-1)
Minimum(1,batt_volt,FP2,0,False)
Sample(1,PTemp,IEEE4)
EndTable
To prevent losing data, collect data from the CF card
before sending the datalogger a new or modified program.
When a program is sent to the datalogger using the Send
button in the Connect screen of LoggerNet or PC400, an
attribute is sent along with the program that commands the
datalogger to erase all data on the CF card from the
currently running program.
CAUTION
4.4 CF Card Data Retrieval
Data stored on cards can be retrieved through a communication link to the
datalogger or by removing the card and carrying it to a computer with a CF
adapter. With large files, transferring the CF card to a computer may be faster
than collecting the data over a communication link. CF card data retrieval is
discussed in detail in Section 7.4,
Data Retrieval
.
Removing a card while it is active can cause garbled data
and can actually damage the card.
Always
press the
control button and wait for a green light before removing
card.
CAUTION
LoggerNet’s File Control should not be used to retrieve
data from a CompactFlash card. Using File Control to
retrieve the data can result in a corrupted data file.
CAUTION