HMP50 Temperature and Relative Humidity Probe
The temperature and relative humidity signals from the HMP50 are measured
using two single-ended analog measurements (Instruction 1).
The probe output scale is 0 to 1000 millivolts for the temperature range of
-40
°
C to +60
°
C and for the relative humidity range of 0 to 100%. Tables 3
and 4 provide calibration information for temperature and relative humidity.
TABLE 3. Calibration for Temperature
Units
Multiplier
(degrees mV
-1
)
Offset
(degrees)
Celsius 0.1
-40
Fahrenheit 0.18
-40
TABLE 4. Calibration for Relative Humidity
Units
Multiplier
(% mV
-1
)
Offset
(%)
Percent 0.1
0
Fraction 0.001
0
TABLE 5. Wiring for CR1000 and CR10X Examples
Description
Color
CR1000
CR10(X)
Temperature
Black
SE 1
SE 3 (2H)
Relative Humidity
White
SE 2
SE 4 (2L)
Signal & Power Reference
Blue
G
G
Power
Brown
12 V
12 V
Shield Clear
G
5.1 Example for CR1000
'CR1000
'Created by SCWIN (2.1)
Public AirTC
Public RH
DataTable(Table1,True,-1)
DataInterval(0,60,Min,0)
Average(1,AirTC,FP2,0)
Sample(1,RH,FP2)
EndTable
7