Campbell Guardian 400A Скачать руководство пользователя страница 11

Campbell Company 

906-0003 AGPS Installation Manual Rev D.docx  

Advisor Guide Pedestrian Signal 

[Version D] 

 

Document Name: 906-0003 AGPS Installation Manual Rev D.docx 

Page 11 of 15 

© Company 2014. All rights reserved    

3.  Locate a tapped hole in close proximity to the 120 VAC three position barrier terminals 

(this may vary among manufactures) 

4.  Insert the ¼” - 20 x 1” FHP through the SPI housing and into the tap holes. Align the SPI 

horizontally such that the 120 VAC wires sag below the housing and attach to the three 

position barrier terminal; tighten firmly securing the SPI to the back of the housing. See 

Table 2. 

Note: The sag in the 120 VAC wire creates a drip loop for water to drain off the SPI housing on 

to the bottom of the Pedestrian Signal Head.  
  

Attention: Do not set the SPI on the bottom of the Pedestrian Signal Head.  Failure to attach the 
SPI vertically on the back surface wall can expose the power supply to water damage and will 
void the warranty of the SPI

Figure 2 

 

 

 

Figure 2 shows the drip loop in the120 VAC lines and its location to the barrier terminal inside the 

Pedestrian Signal Head.  

 

 

Содержание Guardian 400A

Страница 1: ...nstallation Manual 906 0003 Revision D January 20 2014 This Installation Guide provides guidance to those involved in the installation of the application This guide assumes that you have some knowledge of the operating system and the system ...

Страница 2: ...ronic mechanical photocopying recording or otherwise without prior written permission from Campbell Company All copyright confidential information patents design rights and all other intellectual property rights of whatsoever nature contained herein are and shall remain the sole and exclusive property of Campbell Company The information furnished herein is believed to be accurate and reliable Howe...

Страница 3: ...All rights reserved Page 3 of 15 Installation Guide 906 0003 Document Revision History Revision Revision Update Revised By Date A Released tbrennan 6 18 2012 B Released tbrennan 10 01 2012 C CAL TRANs Released ptate 10 17 2012 C1 Released Zsapp 12 21 2012 C2 Released tbrennan 12 02 213 D Released tbrennan 1 13 20013 AGPS Base Station 400A Base Station ...

Страница 4: ...T 5 1 2 IDENTIFICATION 5 1 3 REFERENCE INFORMATION 5 1 4 POINTS OF CONTACT 5 2 Installation Plan 6 2 1 SCOPE 6 2 2 STANDARD COMPONENTS 6 2 3 TASKS 7 2 4 INSTALL UTILITY APPLICATION 7 2 5 INSTALLATION PROCEDURE 8 3 Post Installation 13 3 1 OPERATIONAL CHECK 13 3 2 OPERATIONAL CHECK LIST 13 4 System Requirements 14 4 1 SOFTWARE REQUIREMENTS 14 4 2 HARDWARE REQUIREMENTS 14 4 3 OPERATING SYSTEMS 14 5 ...

Страница 5: ...ation Advisor Guide Pedestrian System AGPS Base Station Fully Integrated Pedestrian Station FIPS Signal Power Interface SPI Utility Version 1 3 X Firmware Version 1 3 X 1 3 Reference information See AGPS Owner s Manual for operational information See AGPS Troubleshooting Manual Reference Campbell Company Intersection Worksheet for location information 1 4 Points of Contact Customer Support Queries...

Страница 6: ...n packet Pedestrian Stations are identified with the Campbell Company Work Order number and Station Identification number 2 3 Standard Components 1ea Base Station with four conductor cable 1ea Signal Power Interface 1ea USB type B cable per installation 1ea Adapter Plate see dimension Hardware options below 1ea Sign 5x7 Adapter Plate Sign Hardware and BS Mounting Hardware o 2ea 8 32 X 1 FHP Screws...

Страница 7: ...t Base Station 6 Install SPI in Pedestrian Signal Head 7 Make Connections for the SPI 8 Test and Adjust 9 Fax checklist to Campbell Company 2 5 Install Utility Application The AGPS Utility application provided by Campbell Company is required before installation USB Configuration Utility Install the computer based configuration utility onto a portable computer An electronic copy of the utility is a...

Страница 8: ...Company Technical Support if a security bit is needed for tactile arrow modification Note THE PEDESTRIAN RELIES ON THIS INFORMATION TO CROSS SAFELY Rubber mounting bumpers screw on to the back plate of the Base Station These are adjustable allowing for a number of configurations to ensure a precision fit especially on decorative small diameter poles where the station needs to be angled to provide ...

Страница 9: ...tion See Table 1 page 10 4 Place a small bead of silicone around the flange for the back plate and tighten screws 5 Use an anti seize compound on all screws 6 Place the pedestrian station on the pole and fasten using two 20 FHP screws Ensure a snug fit 7 Place the adapter plate and or sign using provided hardware 8 Base Station Hardware kits 5x7 Adapter Plate Sign Hardware and Base Staion Mounting...

Страница 10: ...e left or right requiring two security screws and a security driver Campbell Company provides this hardware packet only when specified at the time of purchase Contact Campbell Company Technical Support if a security bit is needed for tactile arrow modification Note THE PEDESTRIAN RELIES ON THIS INFORMATION TO CROSS SAFELY Install Signal Power Interface Board SPI 1 Disconnect the power to the Pedes...

Страница 11: ... 120 VAC wires sag below the housing and attach to the three position barrier terminal tighten firmly securing the SPI to the back of the housing See Table 2 Note The sag in the 120 VAC wire creates a drip loop for water to drain off the SPI housing on to the bottom of the Pedestrian Signal Head Attention Do not set the SPI on the bottom of the Pedestrian Signal Head Failure to attach the SPI vert...

Страница 12: ...I to the three position barrier terminal for the pedestrian signal head visual display See fig 1 7 a Orange to Don t Walk b White to Neutral c Blue to Walk Warning Danger All SPI leads become hot when the Orange or Blue 120 VAC is connected Disconnect the power to the Pedestrian Signal Head prior to SPI installation Figure 3 12 VDC Outputs Terminal 1 S1 DW Terminal 2 S2 W Terminal 3 Neutral Termin...

Страница 13: ...Walk Phase message verify an audible locator tone is present at the clearance phase Flashing Don t Walk 6 Recheck all units for a full cycle to ensure all options and features operate as desired 7 Depending on intersection location factory default settings for volume AGC and vibro tactile settings may require modifications Proceed to the System Configuration section for details 3 2 Operational Che...

Страница 14: ...ll this application USB Configuration Utility A computer based USB configuration utility down load onto a portable computer A USB connection is required for base station communications 4 2 Hardware Requirements The recommended minimum specifications for the computer include the following Computer USB port USB cable type B 4 3 Operating Systems The Utility operates on the following operating system...

Страница 15: ...rom 1 3 seconds may activate special features including audible beaconing and extended pedestrian clearance interval EP Intersection Worksheet Intersection Map of street names and station locations provided with installation packet Pedestrian Stations are identified with Campbell Company Work order and Station Identification number Signal Power Interface SPI Power Source that interfaces with Pedes...

Отзывы: