B-1

Appendix B.  Modbus Register Map 

Parameter 

Description 

Register 

Start 

Register 

Stop 

Low 

Range 

High 

Range 

Units 

ModbusData(1) 

Minute 

HeartBeat 

40001 

40002 

59 

Seconds 

ModbusData(2) 

Soiling_Loss_Index_Isc 

Soiling Loss Index Isc 

40003 

40004 

–20

20 

%

 

ModbusData(3) 

Soiling_Loss_Index_Geff 

Soiling Loss Index Geff 

40005 

40006 

–20

20 

%

 

ModbusData(4) 

IscTest 

IscTest, Measured short circuit current from the dirty panel 

40007 

40008 

–10

10 

Amp 

ModbusData(5) 

IscRef 

IscRef, Measured short circuit current from the clean panel 

40009 

40010 

–10

10 

Amp 

ModbusData(6) 

TempTest 

TempTest 

40011 

40012 

–30

80 

°C 

ModbusData(7) 

TempRef 

TempRef 

40013 

40014 

–30

80 

°C 

ModbusData(8) 

GeffTest 

GeffTest, Effective Irradiance received by the dirty panel 

40015 

40016 

1200 

W/m^2 

ModbusData(9) 

GeffRef 

GeffRef, Effective Irradiance received by the clean panel 

40017 

40018 

1200 

W/m^2 

ModbusData(10) 

Offset_Isc 

Offset in Isc between the clean and test panels, when both are 

clean 

40019 

40020 

10 

No 

Units 

ModbusData(11) 

Offset_Geff 

Offset in Geff between the clean and test panels, when both 

are clean 

40021 

40022 

10 

ModbusData(12) 

Update_Offset 

Update Offset 

40023 

40024 

ModbusData(13) 

UTC_Offset_UserEntered 

UTC Offset of the site, User Entered 

40025 

40026 

–12

12 

hrs 

ModbusData(14) 

Latitude_UserEntered 

Latitude of the site, User Entered 

40027 

40028 

degrees 

ModbusData(15) 

Longitude_UserEntered 

Longitude of the site

,

 User Entered 

40029 

40030 

degrees 

ModbusData(16)  TempCoeffIscTest_UserEntered  Temperature Coefficient of Isc for the Test panel, User 

Entered 

40031 

40032 

No 

Max 

Amp 

ModbusData(17) 

TempCoeffIscRef_UserEntered  Temperature Coefficient of Isc for the clean panel, User 

Entered 

40033 

40034 

No 

Max 

Amp 

ModbusData(18) 

IscTeststc_UserEntered 

Short circuit current of test panel at STC, User Entered 

40035 

40036 

0.5 

20 

Amp 

ModbusData(19) 

IscRefstc_UserEntered 

Short circuit current of clean panel at STC, User Entered 

40037 

40038 

0.5 

20 

Amp 

ModbusData(20) 

HrSolNoonOffset_UserEntered  Offset from solar noon for daily average 

40039 

40040 

hrs 

ModbusData(21) 

GeffThreshold_UserEntered 

Threshold in effective irradiance

,

 User Entered 

40041 

40042 

100 

500 

W/m^2 

ModbusData(22) 

RTU_Voltage 

RTU Battery Voltage 

40043 

40044 

13 

Volts 

ModbusData(23) 

RTU_Internal_Temp 

RTU Internal Temp 

40045 

40046 

-40

70 

°C 

ModbusData(24) 

LocalSolarNoon 

Local Solar Noon 

40047 

40048 

12:00 

13:00 

hrs 

Содержание CR-PVS1

Страница 1: ...CR PVS1 PV Soiling Loss Index RTU Revision 04 2020 Copyright 2017 2020 Campbell Scientific CSL I D 1205 Product Manual ...

Страница 2: ......

Страница 3: ...s under guarantee or not Please state the faults as clearly as possible and if the product is out of the guarantee period it should be accompanied by a purchase order Quotations for repairs can be given on request It is the policy of Campbell Scientific to protect the health of its employees and provide a safe working environment in support of this policy a Declaration of Hazardous Material and De...

Страница 4: ......

Страница 5: ...s digital cell phones and aerials may also not be applicable according to your locality Some brackets shields and enclosure options including wiring are not sold as standard items in the European market in some cases alternatives are offered Details of the alternatives will be covered in separate manuals Part numbers prefixed with a symbol are special order parts for use with non EU variants or fo...

Страница 6: ......

Страница 7: ...e beginning work Wear a hardhat and eye protection and take other appropriate safety precautions while working on or around tripods and towers Do not climb tripods or towers at any time and prohibit climbing by other persons Take reasonable precautions to secure tripod and tower sites from trespassers Use only manufacturer recommended parts materials and tools Utility and Electrical You can be kil...

Страница 8: ......

Страница 9: ...5 6 Compliance 5 5 7 Physical 5 6 Installation 5 7 Operation 6 7 1 Measurement 6 7 2 Soiling Loss Index Details 9 8 Maintenance 10 8 1 Offset Correction 10 Appendices A Glossary of Variable Names A 1 B Modbus Register Map B 1 Figures 4 1 Example applications 3 7 1 Effective Irradiance as calculated from short circuit current of the PV modules on a clear sky day 7 7 2 Effective Irradiance and SLI o...

Страница 10: ...in SLI after a cleaning event Both modules were cleaned at a time corresponding to the record number 650 9 Tables 6 1 Solar Panel Wire Colour Function and CR PVS1 Connections 5 6 2 110PV Wire Colour Function and CR PVS1 Connections 6 ...

Страница 11: ... UNDERSTAND the Safety section at the front of this manual DANGER Fire explosion and severe burn hazard Misuse or improper installation of the internal lithium battery can cause severe injury Do not recharge disassemble heat above 100 C 212 F solder directly to the cell incinerate or expose contents to water Dispose of spent lithium batteries properly WARNING Protect from overvoltage Protect from ...

Страница 12: ...mbers on utility scale solar projects using proven methods Numerous studies and documents have been published over several decades outlining and testing various methods in order to calculate losses due to soiling along with their advantages and disadvantages These studies show that the short circuit current of a solar module is directly proportional to the light intensity and can be used as a reli...

Страница 13: ...ent Factory recalibration is recommended every three years Soiling Loss Index can detect 1 Maximum Open Circuit Voltage 100 V Maximum Current 20 A Measurement Accuracy 2 µV 5 1 Back of Panel Temperature Measurements Measurement Range 40 to 135 C Temperature Uncertainty Temperature Tolerance 40 to 70 C 0 2 C 71 to 105 C 0 5 C 106 to 135 C 1 C Steinhart Hart Linearization Equation Error 0 0024 C max...

Страница 14: ...DNP3 Custom user definable over serial USB USB micro B device only 2 0 full speed 12 Mbps for computer connection RS 232 Female RS 232 9 pin interface 5 4 System Clock Accuracy 1 min per month Clock Resolution 1 ms Program Execution Rate 30 s 5 5 Power Requirements Charger Input CHG 16 to 32 VDC current limited at 0 9 A Power converter or solar panel input External Batteries BAT 12 VDC lead acid 7...

Страница 15: ...and other installation and configuration information Device Configuration Utility software is required This can be installed from the USB sent with the CR PVS1 It is also available for download at www campbellsci eu devconfig Download the Quick Deploy Guide at www campbellsci eu cr pvs1 To prevent injury completely cover the PV panels to limit output and current and voltage during installation Do ...

Страница 16: ...ature the effective irradiance of each panel is calculated in accordance with IEC 60904 and the SLI is calculated according to equation 7 2 A daily average SLI is calculated available for SCADA supervisory control and data acquisition and stored in onboard memory For immediate feedback a real time index and quality factor are available Raw measured data are stored and available for analysis or ind...

Страница 17: ...eaned at record number 650 The soiling index after cleaning is 0 003 0 16 on clear sky and 0 000 0 16 on the variable sky conditions This is an indication of the lowest level of soling loss that can be detected FIGURE 7 1 Effective Irradiance as calculated from short circuit current of the PV modules on a clear sky day FIGURE 7 2 Effective Irradiance and SLI on a cloudy day ...

Страница 18: ...oiling Loss Index RTU 8 FIGURE 7 3 Effective Irradiance and SLI during 1 hour of solar noon and Geffref 800 W m22 FIGURE 7 4 Geff and SLI taken during a cloudy day with Geffref 800 w m2 during 1 hour of solar noon ...

Страница 19: ...he loss in transmission properties of the glass as a result of soiling The irradiance is calculated from short circuit current as 𝐺𝐺𝑒𝑒𝑒𝑒𝑒𝑒 𝐼𝐼𝑆𝑆𝑆𝑆 1 𝛼𝛼 𝑇𝑇 𝑇𝑇0 𝐼𝐼𝑆𝑆𝑆𝑆 𝑆𝑆𝑆𝑆𝑆𝑆 7 1 Where Geff effective irradiance reaching the solar cells ISC measured short circuit current of the panel ISC STC short circuit current at standard test conditions STC T back of panel temperature T0 back of panel temperature ...

Страница 20: ... This offset in power output can be determined upon installation and updated after each cleaning The procedure determines the offset and then implements a correction factor into the measurement sequence to remove any effects that may be caused by the offset Carefully clean both panels before initiating this process Cleaning should be completed before 11 a m 1 Connect to the CR PVS1 using Device Co...

Страница 21: ...test panel Amps IscRef Short circuit current of reference panel Amps TempTest Back of panel temperature of test panel C TempRef Back of panel temperature of reference panel C GeffTest Effective irradiance of test panel W m2 GeffRef Effective irradiance of reference panel W m2 Offset_Geff Measured offset between reference and test panels Stable_Data_Count Incrementally counts when conditions are ap...

Страница 22: ......

Страница 23: ...2 1 10 ModbusData 12 Update_Offset Update Offset 40023 40024 0 1 ModbusData 13 UTC_Offset_UserEntered UTC Offset of the site User Entered 40025 40026 12 12 hrs ModbusData 14 Latitude_UserEntered Latitude of the site User Entered 40027 40028 degrees ModbusData 15 Longitude_UserEntered Longitude of the site User Entered 40029 40030 degrees ModbusData 16 TempCoeffIscTest_UserEntered Temperature Coeff...

Страница 24: ......

Страница 25: ......

Страница 26: ...info campbellsci fr www campbellsci fr Germany Location Phone Email Website Bremen Germany 49 0 421 460974 0 info campbellsci de www campbellsci de India Location Phone Email Website New Delhi DL India 91 11 46500481 482 info campbellsci in www campbellsci in South Africa Location Phone Email Website Stellenbosch South Africa 27 21 8809960 sales campbellsci co za www campbellsci co za Spain Locati...

Отзывы: