FIGURE 6-4. Battery family list
Set the Battery Family to match the battery family being used. The default settings are Battery
Capacity of zero (0) and Battery Family of EnerSys/Genesis NP Series. Setting the Battery Capacity
to zero (0) forces the charger to only float charge the battery. Battery Capacity must be changed
to allow cycle charging.
(p. 17) shows the default settings for each battery family. The
settings are based on the following equation:
V
charge
(T) = C
0
+ C
1
(T-25°C) + C
2
(T-25°C)
2
Where:
T = Battery temperature in ° C.
C
2
= 0 for linear charge voltage vs. temperature relation.