Example of Port Forwarding using the Modem
A-2
CR200X portion of the application:
In this example, the CR200X is left in its default state.
1.
Modem Serial Configuration
i.
Change the COM1 data baud rate to 9600 to match the CR200X default
baud rate.
ii.
Confirm that the local listening port is 6785 (default port of the CR200X).
Submit
new settings.
FIGURE A-2. Serial RS-232
2.
Activate Firewall
Set the Firewall Carrier request to
Block
. This is required for the operation of
the firewall and port forwarding rules.
FIGURE A-3. Firewall - General