![Camille Bauer SINEAX AM2000 Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/camille-bauer/sineax-am2000/sineax-am2000_device-handbook_3665442029.webp)
29/62 Device handbook SINEAX AM2000, 173 849, 04/2015
7.5 Resetting measurements
The device provides minimum and maximum values of different measured quantities, which may be reset
during operation. Reset may be performed in groups using the service menu.
Group
Values to be reset
1
Min/max values of voltages, currents and frequency
2
Min/max values of Power quantities (P,Q,Q(H0),D,S); min. load factors
3
Min/max values of power mean-values, bimetal slave pointers and free selectable mean-values
4
Maximum values of harmonic analysis: THD U/I, TDD I, individual harmonics U/I
5
All imbalance maximum values of voltage and current
7.6 Setting / resetting of meter contents
Meter contents may be individually set or reset during operation using the service menu.
7.7 Configuration
A full parameterization of the device can be performed via the menu settings. With the exception of the
“
country and clock”
menu, all modifications will not take effect before the user accepts the query “Store
configuration changes” when leaving the settings menu.
•
Country and clock: time/date, date format, display language
•
Display settings: Refresh rate, brightness, screen saver
•
Measurement input: System type, nominal values of U/I/f, sense of rotation, quadrants
•
Power mean-values: Interval time, synchronization source
•
Free selectable mean-values: Measured quantity, interval time, synchronization source
•
Standard meters: Tariff switching ON/OFF, meter resolution
•
Free selectable meters: Basic quantity, tariff switching ON/OFF, meter resolution
•
Limit values: Measured quantity, limit value for ON/OFF
•
Digital input: Minimum pulse width, polarity
•
Monitoring functions: Logic inputs 1…3, Logic function, switch-in delay, description text, classification
•
Alarm module
•
Digital outputs: Type, source, pulse width, polarity, number of pulses per unit
•
Relay outputs: Type of output, source
•
Analog outputs: Type of output, source, transfer characteristic, upper/lower range limit
•
Modbus interface settings: Baudrate, parity, number of stop bits, device address
•
User settings
•
Demo mode ON/OFF
•
Device information texts