![Camille Bauer CENTRAX CU3000 Скачать руководство пользователя страница 52](http://html.mh-extra.com/html/camille-bauer/centrax-cu3000/centrax-cu3000_device-handbook_487894052.webp)
PM 1001606 000 07
Device handbook CENTRAX CU3000-CU5000
52/106
7.7.3 Disturbance recorder
Configuration of the events to record
The device monitors the events voltage dip, swell and interruption. The user can define the threshold
levels for these events in the menu
Settings | Disturbance Logger
.
Display of disturbance recordings (locally)
Recorded disturbances are available in the form of a logbook. Each detected disturbance is entered into
the disturbance recorder list with the time of its occurrence. By selecting a list entry the graphical display
of the measured values during this event is entered. The following presentations are available:
•
Half cycle RMS curves of all voltages, all currents, all voltages and currents
•
Curve shapes of all voltages, all currents, all voltages and currents
Display matrix on the local display