Filter Removal Rods

 

 
Camfil’s Bag-In/Bag-Out multi-wide housings are equipped with filter removal rods for prefilters and final 
filters, to pull the second and/or third filters to the front access port of the housing.  The removal rods are 
operated from inside the change-out bag using the glove sleeves.  Camfil recommends removing the first 
filter by hand (without the use of the removal rod), to lighten the load that will have to be pulled by the 
removal rod.  If the housing contains adsorbers it may be necessary on a three (3) wide housing, to 
remove the second adsorber by hand also, before using the removal rod to pull out the third adsorber. 

PREFILTER MODEL NO.:

STOP AIRFLOW THROUGH HOUSING BY 
SHUTTING DOWN THE SYSTEM OR CLOSING 
UPSTREAM AND DOWNSTREAM ISOLATION 
DAMPERS BEFORE REMOVING DOOR.  CONSULT 
YOUR SAFETY OFFICER AND READ INSTRUCTION 
MANUAL TO INSURE PROPER FILTER 
INSTALLATION AND CHANGE−OUT.

FINAL FILTER MODEL NO.:

CHANGE−OUT BAG SIZE:

CAUTION:

FILTER HOUSING

BAG−IN/BAG−OUT

Washington, North Carolina 27889    (252) 975−1141

CAMFIL FARR MODEL NO.:

CAMFIL FARR JOB NO.:

FILTER HOUSING

BAG−IN/BAG−OUT

Washington, North Carolina 27 889    (252) 975−1141

STOP AIRFL OW THROUGH HOUSING BY 
SHUTTING DOWN THE SYSTEM OR CLOSING 
UPSTREAM AND DOWNSTREAM ISOLATION 
DAMPERS BEFORE REMOVING DOOR.  CONSULT 
YOUR SAFETY OFFICER AND READ INSTRUCTION 
MANUAL TO INSURE PROPER FILTER 
INSTALLATION AND CHANGE−OUT.

PREFILTER MODEL NO.:

FINAL FILTER MODEL NO.:

CHANGE−OUT BAG SIZE:

CAUTION:

CAMFIL FARR MODEL NO.:

CAMFIL FARR JOB NO.:

Washington, North Carolina 27889    (252) 975−1141

BAG−IN/BAG−OUT
FILTER HOUSING

STOP AIRFLOW THROUGH HOUSING BY 
SHUTTING DOWN THE SYSTEM OR CLOSING 
UPSTREAM AND DOWNSTREAM ISOLATION 
DAMPERS BEFORE REMOVING DOOR.  CONSULT 
YOUR SAFETY OFFICER AND READ INSTRUCTION 
MANUAL TO INSURE PROPER FILTER 
INSTALLATION AND CHANGE−OUT.

CAMFIL FARR JOB NO.:

CAMFIL FARR MODEL NO.:

CHANGE−OUT BAG SIZE:

FINAL FILTER MODEL NO.:

PREFILTER MODEL NO.:

CAUTION:

Remove rod 
for prefilter. 

Remove rod 
for final 

In-Place Test Section Housings 

 
Camfil offers qualified In-Place Test Section housings to assist qualified testing technicians while performing In
-Place Testing of filters or adsorbers.  These test sections have proven to perform as good or better than the 
conventional method of in-place testing.  Camfil has designed and qualified four (4) types of test sections 
(upstream, combination, downstream and accurate scan) for any need.  The upstream test section housing 
design allows you to disperse a challenge agent uniformly across the filter/adsorber face so that the complete 
filter/adsorber is challenged.  It also samples the concentration entering the downstream filter/adsorber.   The 
combination test section provides the same function as the upstream test section, plus sampling the air stream 
for leaks, which have by-passed the upstream filter/adsorber.  Downstream test sections sample the air stream 
for leaks, which have by-passed the upstream filter/adsorber.  Camfil’s  “Accurate Scan” test housing is 
designed to scan the downstream face of a HEPA filter for leaks.  The “Accurate Scan” test housing 
incorporates an access port protected by a heavy duty plastic bag, so all scan testing can be performed from 
outside the contaminated air stream.  A probe is provided with guide rods to scan straight lines across the 
complete filter face and overlaps so that no part of the filter face will be missed when checking for leaks. 
 
Users of “High Efficiency” filtration systems must commit to a testing program that will insure the installed 
filtration system will perform as intended from initial start-up, throughout the life of the filtration system. In some 
applications, guidelines for filter system testing may not be established by appropriate regulatory agencies or 
engineering societies.  Whenever an organization has no established guidelines, often the standards for in-
place testing of air filtration units for nuclear facilities is specified. 

Содержание FB Series

Страница 1: ...Installation Operation and Maintenance Manual Camfil Installation Operation Maintenance Manual FB Housing 3401i 0404 Camfil clean air solutions Camfil FB Series Fluid Seal Bag in Bag out Filter Housing ...

Страница 2: ...r changing a contaminated filter Since all types of housing designs and configurations cannot be addressed by a single manual or set of safety procedures we propose a proven method of replacing contaminated filters with clean filters Once this method is understood by both maintenance personnel and safety personnel they can adapt the most suitable method to use based on the housing location type of...

Страница 3: ...lation of Filtration Housing 6 Installation of New Filter s or Adsorber s Prior to New System Startup 6 Filter Change Out Replacing Contaminated Filter s or Adsorber s 10 Filter Change Out Overview 13 Maintenance 14 Locking Mechanism Adjustment 17 Spare Parts and Accessories 18 ...

Страница 4: ...he knife edge seal inside the fluid gel creating a positive airtight seal The filter locking mechanism is operated from inside the housing and designed to prevent the access door from being installed without the locking mechanism properly secured When the initial filters are installed or the contaminated filters are changed out the system must be in place leak tested to assure the filters are seal...

Страница 5: ...OUT BAGSIZE FINAL FILTER MODELNO PREFILTER MODELNO CAUTION Remove rod for prefilter Remove rod for final In Place Test Section Housings Camfil offers qualified In Place Test Section housings to assist qualified testing technicians while performing In Place Testing of filters or adsorbers These test sections have proven to perform as good or better than the conventional method of in place testing C...

Страница 6: ...ng All sections of the filtration system including fans dampers etc should be complete and ready for operation The overall filtration system should be securely mounted to a curb base or structural support 5 Following installation of the ductwork and filtration housing the system should be cleaned to remove dust or debris before installing new filter s adsorber s into the system Installation Of New...

Страница 7: ...chanism Make sure the filter adsorber is correctly orientated when placing inside of the filtration housing The filter clips should be positioned on the top and bottom of the filter see pictures The filter shall be installed with the pleats or separators in the vertical position Install adsorbers with the carbon beds in the horizontal position Push the filter s adsorber s to the back of the filtra...

Страница 8: ...wards the locking handle latch see illustrations and pictures on this page and pictures on next page This allows the fluid seal channel on the filter adsorber to seal with the knife edge sealing surface Lock the locking mechanism handle with the handle latch Slowly close the locking mechanism handle by pushing the handle towards the handle latch ...

Страница 9: ...ecurity strap and secure any excess strap so that it does not interfere with the door seal when the door is installed After the change out bag has been secured with the security strap extend the bag out completely Fold and roll the bag towards the housing squeezing trapped air out of the folded rolled portion of the bag until the bag is tucked neatly between the bagging ring and the filter access ...

Страница 10: ...taminated filter s adsorber s the airflow through the filtration system must be stopped This can be performed by shutting down the system or bypassing the airflow through the system to another system when applicable To minimize possible contamination close upstream and downstream dampers if equipped It is recommended that protective clothing gloves and respirators be worn when changing filters wit...

Страница 11: ...in the middle of section Tape over exposed edges where bag was cut Remove the contaminated filter adsorber for disposal A banding kit can also be used as shown in picture see Spare Parts and Accessories page18 Remove the change out bag security strap and gently position the bag s shock cord between the two raised ribs of the bagging ring If the filtration system only has a single filter proceed to...

Страница 12: ...talled inside housing using a new change out bag for each new filter adsorber installed For filtration housings that contain more than one filter adsorber it may be necessary to push one filter as far inside the housing as possible then install the second filter to help push the first filter to the back of the housing 8 Once all filters adsorbers are installed in the housing secure the change out ...

Страница 13: ...GH HOUSING BY SHUTTING DOWN THE SYSTEM OR CLOSING UPSTREAM AND DOWNSTREAM ISOLATION DAMPERS BEFORE REMOVING DOOR CONSULT YOUR SAFETY OFFICER AND READ INSTRUCTION MANUAL TO INSURE PROPER FILTER INSTALLATION AND CHANGE OUT CAUTION Washington North Carolina 27889 252 975 1141 Doorknob Installation Ratchet Attachment can assist during tightening of doorknobs To order from Camfil see Spare Parts and Ac...

Страница 14: ...act The filtration system is no longer functioning properly when any of the following occurs A periodic site inspection routine maintenance checks or other planned surveillance testing reveals torn gaskets broken welds stripped threads on door bolts or any other indication that the system s ability to contain the process airstream has been compromised To assure that the filtration system is mainta...

Страница 15: ...r when performing the final installation It is important to cut gasket as straight as possible 4 Locate adhesive caulking DC 732 or equal and caulking gun Cut tip off adhesive tube so that a bead of caulking approximately 1 8 to 3 16 diameter will be produced Deposit a continuous bead of caulking 1 8 to 3 16 diameter inside the bottom of the extruded gasket channel 5 Start placing gasket on door s...

Страница 16: ...king mechanism does not fall This could damage the housing or injure the personnel working on the locking mechanism Measure the distance which the 3 8 locknuts are positioned on the locking mechanism adjustment refer to Detail No 2 on next page this dimension will be used when replacing the new locking mechanism Remove two 2 3 8 locknuts from backside of adjustment studs connected to pivot arms an...

Страница 17: ...anism do not force the handle closed The locking mechanisms are preset at the factory when installed in a filtration system from the factory with the correct tension on the locking handle The handle should move fairly easily until within approximately 1 of the locking handle latch then moderate pressure should be applied to latch and secure the handle If the handle takes more than moderate pressur...

Страница 18: ...nge Out Bag Size Camfil offers additional parts and accessories which can be used for repairing door gaskets or assisting in the Filter Change Out Door Gasket Camfil Part Number M32001001 order by the foot to determine length need measure circumferance of door which the gasket is to be replaced and add one foot extra carry to next highest foot length Doorknobs Camfil Part Number M36001000 Change O...

Страница 19: ..._________________________________________ _______________________________________________________________ _______________________________________________________________ _______________________________________________________________ _______________________________________________________________ _______________________________________________________________ ______________________________________...

Страница 20: ...pi Laval Quebec Conover North Carolina Washington North Carolina Concord Ontario World Wide Manufacturing Locations Belgium France Germany Ireland Malaysia Sweden Switzerland United Kingdom Camfil http www camfil us Represented by Camfil has a policy of continuous research development and product improvement We reserve the right to change designs and specifications without notice Camfil Inc United...

Отзывы: