64
Section 3
Scanner
®
2000 microEFM
When an external power supply is used as the primary power source, the lithium battery pack serves as
a backup power supply. The use of an alternate power source extends battery life and helps ensure that
timekeeping and volume accumulation will not be interrupted during a power failure.
External Power Supply
The Scanner 2000 can be connected to a remote power supply by a two-conductor cable (Figure 3.3). The
power supply and cable must be capable of supplying 6 to 30 VDC @ 50 mA.
The external power supply must be an approved SELV source, insulated from the AC main by double/
reinforced insulation per CSA C22.2 No.61010-1-04 / UL 61010-1 – 2nd Edition.
Important In all applications using an external power supply, a switch or circuit breaker must be in-
cluded in the safe area external power supply installation within easy reach of the opera-
tor. The switch or circuit breaker must be marked as the “disconnect” for the safe area
external DC power supply.
Important If the main circuit board is marked with a revision level of 02 or older (revisions 01, C, B,
or A), a zener diode (Part No. 1.5KE33CA) must be installed for CE approval. The zener
diode is not required for revision 03 and newer circuit boards.
J1
TB1
TB2
TB3
BATTERY
13
14
J2
P
O
W
E
R
R
TD
P
O
R
T 2
P
O
R
T 1
I
+
R
+
R
-
I
-
SCANNER 2000
Main Circuit Board
PN: 9A-30160010
POWER
SUPPLY
6 to 30
VDC
–
+
–
+
–
+
–
+
2
3
4
5
6
1
7
8
9
10
11
12
TF
M
1
GND
GROUND
SCREW INSIDE
ENCLOSURE
SWITCH
DIG OUT 1
Figure 3.3—External power supply wiring
Содержание Scanner 2000 microEFM
Страница 1: ...NUFLO Scanner 2000 microEFM Hardware User Manual Manual No 9A 30165023 Rev 10 ...
Страница 26: ...26 Section 1 Scanner 2000 microEFM ...
Страница 104: ...A 18 Appendix A Scanner 2000 microEFM ...
Страница 106: ...B 2 Appendix B Scanner 2000 microEFM ...
Страница 188: ...E 10 Appendix D Scanner 2000 microEFM ...
Страница 190: ...R U S S I A 603 5569 0501 ms kl c a m com ...