Section 3
Model 753A Gage Pressure Transmitter
Perform the following steps to complete field wiring.
1. Connect the power supply and the receiver to the transmitter as shown in
Figures 3.1 and 3.2.
2. Determine the total loop resistance required for the installation, using
Figure 3.3, page 13
, for reference. The total loop resistance must be
less than the maximum calculated value.
Table 3.1, page 13,
provides
loop resistance values for various cable wire sizes.
3.
Install a load resistor sized for the application.
!
WARNING: Failure to properly calculate power supply DC output voltage
may result in inaccurate transmitter readings, possibly leading to safety
system performance degradation during design basis events. To avoid
equipment inaccuracy hazards, follow the examples and tables in this
section for determining the proper power supply DC output voltage.
Figure 3.1—Typical field wiring connections for Model 753A with junction box
Figure 3.2—Typical field wiring connections for Model 753A without junction box