5.4 Minimum thickness and type of cables
2 1
5
295
5
A
ll t
h
e d
at
a a
n
d i
n
fo
rm
at
io
n c
o
n
ta
in
ed h
er
ei
n i
s c
o
n
si
d
er
ed s
u
b
je
ct to c
h
an
g
e a
t a
n
y t
im
e a
n
d a
t o
u
r d
is
cr
et
io
n
.
ENGLISH
Connections
Type of cable
Length of
cable 1<10 M
Length of ca-
ble 10<20 M
Length of ca-
ble 20<30 M
230/400V 3F power supply line
FROR CEI 20-22
CEI EN 50267-2-1
4G 1,5mm²
4G 2,5mm²
4G 4mm²
230V 2F power supply line
3G 1,5mm²
3G 2,5mm²
3G 4mm²
230/400V 2F/3F motors
4G 1mm²
4G 1,5mm²
4G 2,5mm²
24V motors
2 x 1mm²
2 x 1,5mm²
2 x 2,5mm²
230V fl ashing lamp
2 x 0,5mm²
2 x 1mm²
2 x 1,5mm²
24V fl ashing lamp
2 x 0,5mm²
2 x 1mm²
2 x 1,5mm²
230V courtesy / cycle light
3G 0,5mm²
3G 1mm²
3G 1,5mm²
24V power supply accessory
2 x 0,5mm²
2 x 0,5mm²
2 x 1mm²
24V pilot light
2 x 0,5mm²
2 x 0,5mm²
2 x 1mm²
24V “in motion” output
2 x 0,5mm²
2 x 0,5mm²
2 x 1mm²
Safety contacts
2 x 0,5mm²
2 x 0,5mm²
2 x 0,5mm²
N.O./N.C. control button
2 x 0,5mm²
2 x 0,5mm²
2 x 0,5mm²
End stop
3 x 0,5mm²
3 x 1mm²
3 x 1,5mm²
Command 2nd combined motor
1 x 0,5mm²
1 x 0,5mm²
1 x 1mm²
Antenna connection (max 50M)
RG58
Encoder connection (max 30M)
2402C 22AWG shielded cable
N.B.: An evaluation of the size of the cables with lengths other than the data in the table must be made based on the effective
absorption of the connected devices, according to the instructions indicated by the CEI EN 60204-1 standards.
For connections that require several loads on the same line (sequential), the size given on the table must be re-evaluated based
on actual absorption and distances.
The holes measure
20/21 mm diameter