background image

TITLE

11 

commissioning 

via panel

Important!

Ensure the wiring is complete (refer to the wiring diagram) & any required physical stops are set before  

commencing with programming

 

Tick

1.  Power on the control panel   
2.   Press and hold the 

 button for 2 seconds to access programming 

3.   Set the language  

LANGUAGE

  – Choose Language 

4.   Disable total stop 

FUNCTION

  –  

Total Stop 

Disabled

 

5.   Disable Safety Inputs 

FUNCTION

 – 

CX Input 

Disabled

 

CY Input 

Disabled

 

CZ Input 

Disabled

  

6.   Enable the Encoder 

FUNCTION

  – 

Config 

Encoder

 

7.   Set the number of motors  

No. Motors 

M2

 

8.   Set the motor type  

Motor type 

FROG - FROG-PM6

 

9.   Press the 

 button to exit 

FUNCTION

  

 

CAUTION, Ensure the gate movement area is clear of all obstructions

10.   Check the motor direction  

TEST MOT

  

 

For motor 1, Press and hold

 

 

=M2 

 

The gate should open, if not reverse the motor cables for motor 2 (Connections X, Y) 

 

Leave the gate leaf in the halfway position.

11.   Setup the Encoder 

ENCODER

 – 

Set Encoder

 – 

Set Encoder 

Confirm (yes)

  

 

 

The Gates will now perform a close and open cycle. 

12.  Exit the programming using the 

 button 

13.  Check the gate operation by pulsing across connections 2 & 7, the gate will close 

Please refer to the main manual for:

Changing automatic closing time, adjusting encoder settings if required

1

2

3

The installation must be carried out 

by skilled and qualified personnel

 button - used to perform the following operations:

• Exit the menu
• Delete the changes
• Go back to the previous screen

 

 buttons - used to perform the following operations:

• Navigate the menu
• Increase or decrease values

 button - used to perform the following operations

• Access menus
• Confirm a choice

1

2

3

Should the gates not operate as suggested above, 

call CAME helpline 

0115 921 0430

 for technical support.

Safety inputs should now be configured and the gate force tested as required. 
Please refer to the full manual to complete the commissioning.

Содержание FROGPLUS-S7

Страница 1: ...it for a single swing gate weighing up to 550kg max width 7m TO BE READ IN CONJUNCTION WITH THE FULL INSTRUCTION MANUAL QUICK SETUP GUIDE Typical gate setup geometry Gate motor manual release Kit wiri...

Страница 2: ...lease Device with Lever Key RGSM001S Gateway Module RSE Connection Card SIM May be preinstalled in RGSM001S 1 Kit Contents 2 Safety Instructions 3 Typical Gate Setup 4 Geometry 5 Manual Release Instru...

Страница 3: ...ssing through the gate Keep feet away from the bottom of the gate during operation Do not operate the gate by remote control unless they are in view Do not attempt to block or interfere with the gate...

Страница 4: ...rs one transmitter and one receiver They should be installed between 500 600mm from the ground facing each other Power for the photocells is taken from the control panel 24v AC The maximum range of th...

Страница 5: ...screw until it makes contact with the body tighten the nut to lock the position of the screw During closing close the leaves completely loosen the screw until it makes contact with the transmission ar...

Страница 6: ...5 Please note it may be necessay to operate the motor once power is restored to fully engage the system Please take care when operating the system in this manner The FROG PLUS underground system is su...

Страница 7: ...ble length RX 4 Core 0 5mm Flex TX 4 Core 0 5mm Flex 1m 30m 10 2 TX C NC TX 2 RX TX RGSM001S Gateway Module Cable length Max 3m power 10 2 A B GND Mains Supply 230 V AC Cable length 1m 20m 3 Core 1 5m...

Страница 8: ...ength or availability and therefore will not be held liable for lack of service came automation internet came cloud setup app for the installer GET IT ON AppStore GET IT ON automation app for the end...

Страница 9: ...ll read 6V V 7V 0 230V 26V 0V 17V 0 230V 1 E2 M2 11 N2 E E 10 TS E ES 1 2 3 3P 5 7 B GND GND S1 A B1 B2 CX 2 CY CZ 4 FA1 FC1 FC2 FA2 WWW CAME COM ZM3E to check motor direction using control panel CAUT...

Страница 10: ...rrive please check your junk folder download the connect setup app adding the rgsm gateway to your technician account technician connect setup app 1 3 2 If you have an existing account please move to...

Страница 11: ...Bm 24V CONNECT 123 4 GND A N T 10 2 COM IN2 COM IN1 B A 1A 30V RGSM001S If you intend to retain control of the SIM for top up If as the installer you intend to retain control of the SIM for top up pur...

Страница 12: ...tomation Select Manual Add Select FROG 230V ZM3E from the drop down list Enter a name and description then press Add adding automation 1 FROG 230V ZM3E Automation for swing gates Encoder Frog Plus M2...

Страница 13: ...ition or Add with QR Code If you pressed Local Acquisition the screen will change to the one shown here Select the button on the fob and it will add the button straight onto the control panel Set the...

Страница 14: ...cess for all fobs Select the back button to return to the main menu If you select ADD via QR Code the app will open the devices camera enabling scanning of the QR code on the fobs packaging Once the Q...

Страница 15: ...n App On first login you will be prompted to accept the gateway You will then be presented with control options for your automation To transfer to a customer select the 3 dots Select Transfer site Ent...

Страница 16: ...Connections X Y Leave the gate leaf in the halfway position 11 Setup the Encoder ENCODER Set Encoder Set Encoder Confirm yes The Gates will now perform a close and open cycle 12 Exit the programming...

Страница 17: ...d on the screen A maximum of 250 individual buttons can be saved Remove transmitter button 1 Press and hold the button for 2 seconds to access programming Language appears on the display 2 Users Remov...

Страница 18: ...n require activation from a command device to restart C1 REOPENING DURING CLOSING When the automation is in its closing cycle and the safety circuit is triggered the automation will stop and reverse i...

Страница 19: ...and fit the replacement SIM card into the slot Replace the casing and power up the control panel Send an SMS to the telephone number of the SIM reporting the APN details Access Point Name ask the serv...

Страница 20: ...colour 806SL 0240 SELB1SDG2 Surface mounted with blue backlighting for 50 users RAL7024 Grey colour 806SL 0250 SELB1SDG3 Surface mounted with blue backlighting for 250 users RAL7024 Grey colour TRANS...

Страница 21: ...to each other with no interference issues cross talk 001DIR10 Pair of 12 24 V AC DC outdoor photocells range 10m 001DIR20 Pair of 12 24 V AC DC outdoor photocells range 20m 001DIR30 Pair of 12 24 V AC...

Страница 22: ...correct use of the Software requires the possession of an automation home automation security temperature control and or video surveillance system manufactured by Came which has been enabled for remo...

Страница 23: ...ation of the automation home automation security temperature control and or video surveillance system manufactured by Came may be associated with the system itself In this way the installer can perfor...

Страница 24: ...immediate effect in the event of the violation of the terms of Articles 2 2 and or 2 5 In this case termination shall occur automatically upon receipt by the Installer of the notification sent by Came...

Страница 25: ...vidual parts of the additional network services and other related services referred to in Section 3 1 lit c of these GTC 1NCE expressly points out that the type and scope of such services of the respe...

Страница 26: ...tion 2 of these GTC for the Services Within the framework of the conclusion of the contract the Customer may choose between different payment methods offered by 1NCE Unless otherwise agreed between th...

Страница 27: ...a Protection Act Bundesdatenschutzgesetz 10 2The Parties also undertake to treat all other confidential information of the other Party that the receiving Party becomes aware of in connection with the...

Страница 28: ...O THIS DOCUMENT AT ANY TIME THE DATA AND INFORMATION SHOWN IN THIS CATALOGUE ARE SUBJECT TO CHANGE WITHOUT OBLIGATION TO GIVE PRIOR NOTICE BY CAME S P A E OE CAME BPT North Unit 1B Sills Road Willow F...

Отзывы: