24 V AC/DC

A1

A2

A1 / A2: 

▲ 

Supply voltage (24 V DC or 24 V AC)

1 / 2: 

 

Sensor 1

3 / 4: 

 

Sensor 2

11 / 14: 

▲  

Safety output 1   

21 / 24: 

▲  

Safety output 2   

5 / 6: 

 

Status output (see chapter 4.5) 

 

i

  No function test possible without connected outputs (Display E 007 or E 008)

 

  Wiring mandatory

Connected sensors with a terminating resistor of 8.2 kOhm are monito-
red for a change in current.  
In the idle mode
•  all safety outputs are conductive
•  the LED lights up green
•  both dots on the display flash

When one or more sensors are 

actuated

•  the total resistance of the sensor system drops towards zero ohm
•  the defined switching threshold is not reached anymore
• the corresponding Safety output opens
•  the LED lights up orange, P appears on the display

In the event of a 

fault 

in the sensor circuit (for example cable breakage)

•  the total resistance of the sensor system increases 
•  the defined switching threshold is exceeded
•  

both

 Safety outputs open

•  the LED lights up red, E appears on the display

1

2

1

4

Configuration and set-up

3

Function

4.1   Terminals

4.2   Switch on supply voltage

Wiring the device

If necessary, configure the device

Block diagram

Function and

safety check

Function and

safety check

Safety 

Output 1

Safety 

Output 2

Status

Output
(see 

chapter 4.5)

Power supply

Sensor  1

8k2

Sensor 2

8k2

4.3  Configuration mode

 (edit mode)

On initial commissioning, the device must be adapted (configured)  
to the application.

Configuration

•  Press the “Mode” button to select the requested parameter.
•  Press the “Data” button to set the value.

Exit Configuration menu:

 

Press “Mode” until “h End”, than press “Data”.

Adjustable parameters:

C  active inputs: 001 = both inputs 1 and 2, 002 = only input 1,  
  003 only input 2 
h  The holding time (extension of the output signal):   

 

  001 = none,  002 =100 ms, 003 = 200 ms, 004 = 500 ms, 005 = 1000 ms

To enter Configuration menu 

(see also chapter 4.4):

•  Enter diagnostic menu: Press “Mode” and “Data” buttons simultaneously for 2 seconds 

→ 

Status LED flashes orange. 

•  Press “Mode” repeatedly until “C” and “con” are displayed.
•  Press “Data” button, “con” starts flashing.
•  Press “Mode” and “Data” buttons simultaneously until “con” stops flashing. 
•  Release “Mode” and “Data”, “C” starts flashing, both safety outputs open.

Configu- 

ration

Holding  

time

001*

Sensor 1 + 2

001

none

End

002

Sensor 1

002

100 ms

003

Sensor 2

003*

200 ms
004

500 ms
005

1 s


2 sec

*  

 Factory setting

Exit 
Configuration 
menu

{

C

h

h