Without using slowdown space (slowdown space = 0)
A
Opening or closing speed
C
Approach speed (fi xed)
D
Obstruction travel sensitivity
1
Opening or closing limit-switch
3
Opening or closing approach point
Virtual encoder
For gearmotors without an encoder or with the encoder deactivated, travel is managed using a VIRTUAL ENCODER.
ALWAYS calibrate the travel, as with motors with an encoder.
If, during calibration (no encoder), the panel does not automatically detect the strike plate signalling a change of
status on the display (in the order CL1, CL2, OP2, OP1), repeat the operation as follows:
1
Close M1 and “CL1” appears on the display. When it hits the strike plate, press the ENTER button.
2
Close M2 and “CL2” appears on the display. When it hits the strike plate, press the ENTER button.
3
Open M2 and “OP2” appears on the display. When it hits the strike plate, press the ENTER button.
4
Open M1 and “OP1” appears on the display. When it hits the strike plate, press the ENTER button.
5
The message Calibration Complete shows on the display, followed by the symbol, to signal that the encoder is deactivated.
In this case, the travel end points, approaches, slowdowns and obstruction detection will be less precise.
Managing the travel and related parameters is done in the same way as described for motors with an encoder.
Functions menu
Number of motors
Set the number of motors that control the gate.
Confi guration>
Motor settings
Number of motors
M1+M2 (Default)
M2