Page 11 of 16

CX-EMF-2 MULTI-FUNCTION TIMER

INSTALLATION INSTRUCTIONS

Emergency Panic Switch (optional) 

Should an emergency occur, and assistance from the outside 
is required, the occupant can push a button or ribbon switch to 
signal the EMF-2 (input #3). When activated, the EMF-2 
will unlock the door (and optionally open the door). A 
maintaining type input is required to keep the door held open. 

Based on the settings of Dipswitch #6 & 8 either the doors will 
unlock only, or the last door used will open or, both doors will 
unlock and open simultaneously. 

Relay #4 is now activated, which can be used to signal for 
assistance, sound an alarm – whatever you choose. The 
installer can choose a continuous or pulsing output, depending 
on the settings of potentiometers #4 & 5. 

Emergency Time-out Feature 

An added safety feature in the EMF-2 is the ability to 
automatically reset to standby mode after a fixed lock time of 
15 minutes. The door unlocks, so that personnel may enter 
the restroom. This feature is engaged by turning dipswitch #7 
to ON position. If not desired, simply leave dipswitch 7 OFF.

SECTION 3E - SET-UP INSTRUCTIONS

2/3 Door Airlock (Mode 5)

This is designed to control up to 3 sets of sliding, or swinging 
doors. The relay allows only 1 door to be open at a time. 

It accomplishes this by a Door Sense input, such as a 
magnetic contact switch, located at each door. If the Door 
Sense determines that a door is open, it will not allow a 
second door to open, but remembers the request to open 
and allows it once the first door has closed. 

For 2-door airlocks, the installer can set up “Auto-crossing” 
whereby after triggering one door, the second door activates 
after the first door closes (also known as bi-directional 
door sequencing). 

Should a door become stuck open, a Trouble signal is output 
after 5 minutes. The EMF-2 also includes a “Lock-down” input 
that resets the system and/or disables all “Open” requests.

Step 1

Select MODE 5 via the first 3 positions 
of the dip switch as shown:

See Diagram 1

 for location of dipswitch, 

connectors, & potentiometers.

Step 2  -  Dip Switch Options

Use of Relay 5 is optional, and set according to dipswitches 
#4 & 5. Push switch #6 ON for “Auto Mode” (door sequencing). 
In this Mode when input A is activated, first door A opens, 
then when closed again, door B opens in sequence.

Conversely, when input B is activated, first door B opens, then 
when it is closed again, door A opens sequentially.  A third 
door cannot be used in “Auto-Mode”. Selecting this mode 
disables door C input and contact input. 
Set dipswitch #7 ON for airlocks containing 2 doors only, or set 
to OFF for 3 doors. Dipswitch #8 has no effect in this mode. 

IMPORTANT: Any changes to Mode selector or Out2 settings 
must be made with power off!

Step 3  -  Connections

Refer to Diagram 6 for the following connections. 
Wire all input connections to the (removable) Input terminal 
strip (numbered 1-14). Firmly re-insert connector if removed.  

NOTE: Magnetic contact switches:

 This system wants to 

see a Normally Closed connection when the door is closed. 
The contact will open when the door opens. Any other 
configuration will cause the relay to malfunction. We suggest 
standard door contacts (ie.Camden Model #CX-MDC). 
Make your connections to the relay output strip (numbered 
1–15). The 7-pin Digital I/O strip provides a trouble output on 
pins 6 & 7 after 5 minutes of door ajar. 
Connect 12 or 24V AC/DC supply to terminals 1 & 2 of the 
2-pin Power Connector (Terminals are not polarity sensitive).

Step 4  -  Adjustments 

In this application, you will use pots 1–3 & 5. 
Pot 4 is not used in this mode. 

Timer 1:

 Door A Delay-on-Release

Timer 2:

 Door B Delay-on-Release

Timer 3:

 Door C Delay-on-Release

Timer 4:

 Not used

Timer 5:

 Timer for clearing "walk-aways"

Apply power to door operators (EMF-2), and all connected 
equipment (strikes, lights, etc). Observe the red Power LED on 
the unit, which should light. If not, re-confirm proper voltage 
and/or terminal strip connection. 

Activate an input device to one of the doors. Observe the 
respective output LED, which should light immediately. The 
door should unlock and/or open. 

If a request to open comes in from another door while the 
first is still open, it will retain the call in memory until the 
Door Sense switch indicates the first has closed. If there is 
a succeeding request on the first door (or the door that is 
already opened), it will keep that door opened.

If automatic sequential operation between doors A and B is 
desired, put dipswitch #6 into ON position. Otherwise, for 
normal operation, leave this dipswitch off. 

Potentiometer #5 is useful if the application utilizes locks only, 
and not automatic door operators.

OFF / ON

1
2
3

Содержание CX-EMF-2

Страница 1: ...x 95mm In addition to the above Model EMF 2 ABM includes a lockable metal cabinet to house the relay The cabinet is equipped with two lighted push switches on to turn the relay power on or off and the...

Страница 2: ...op View P2 P3 P1 P4 Inputs Mode Rel 5 Opt Relay 1 Timer Settings Relay ON Indicators 7 6 5 4 3 2 1 NC C NO NC C NO NC C NO NC C NO NC C NO Relay 2 Relay 3 Relay 4 Relay 5 12 24V Power Trouble Output I...

Страница 3: ...1 2 of the Digital I O strip Re insert connector firmly if removed Connect 12 or 24V AC DC supply to terminals 1 2 of the 2 pin Power Connector Terminals are not polarity sensitive Step 4 Adjustments...

Страница 4: ...quired if Panic switch is utilised Fail Safe Electric Strike Shown if Fail Secure lock is used wire to Terminals 1 2 MOV Wire MOV supplied directly to strike or magnet Power for Strike N C Simple Micr...

Страница 5: ...ollowing connections Wire all input connections to the removable Input terminal strip numbered 1 14 Firmly re insert connector if removed Next make your connections to the Relay Output strip numbered...

Страница 6: ...inals 1 2 Wire MOV supplied directly to strike or magnet Power for Strike Door Operator Inside Wall Switch Outside Wall Switch Occupied LED optional Panic switch optional Inside Push to Lock Switch 12...

Страница 7: ...and all connected equipment strike lights etc Observe the red Power LED on the unit which should light If not re confirm proper voltage and or terminal strip connection Enter keypad key switch or othe...

Страница 8: ...ke or magnet Power for Strike Occupied LED optional Inside Wall Switch Outside Wall Switch optional Panic switch optional Inside Push to Lock Switch 12 24 V AC DC Power Magnetic Contact Switch MOV PUS...

Страница 9: ...es 4 5 See diagram 1 for location A common use in this mode would be that Relay 5 follows the lock relay and lights an occupied sign It could also be utilized for the second door lock rather than conn...

Страница 10: ...Occupied LED optional Inside Wall Switch Door 1 Outside Wall Switch Door 1 Panic switch optional 12 24 V AC DC Power Magnetic Contact Switch on both doors Wire in series PUSH TO LOCK Door 1 Lock Opti...

Страница 11: ...t A is activated first door A opens then when closed again door B opens in sequence Conversely when input B is activated first door B opens then when it is closed again door A opens sequentially A thi...

Страница 12: ...EN PUSH TO OPEN PUSH N C N C 1 Timer Settings Relay On Indicators EMF 2 1 5 2 3 4 6 7 8 9 10 11 12 13 14 15 1 5 2 3 4 6 7 1 5 2 3 4 6 7 8 9 10 11 12 13 14 Off On 1 2 5 7 4 6 3 8 Mode Rel 5 Opt 2 3 4 5...

Страница 13: ...provides a trouble output on pins 6 7 after 5 minutes of door ajar Connect 12 or 24V AC DC supply to terminals 1 2 of the 2 pin Power Connector Terminals are not polarity sensitive Step 4 Adjustments...

Страница 14: ...5 Contact Power for Strike Power for Strike Power for Strike Power for Strike Power for Strike Trouble output after 5 minutes of door ajar Select 5V or 12V output with jumper 12 24 V AC DC Power Troub...

Страница 15: ...nd or terminal strip connection Activate an input device to one of the doors Observe the respective output LED which should light immediately The door should unlock and or open If a request to open co...

Страница 16: ...Door 2 Lock TO OPEN PUSH Inside Wall Switch Door 2 LOCK DOWN N C N C Trouble Trouble output after 5 minutes of door ajar Select 5V or 12V output with jumper STEP HERE ONLY Trouble Output 1 Timer Setti...

Отзывы: