CM-310EE Instructions.doc , Page 2 

APPLICATIONS 
& SET-UP INSTRUCTIONS: 

STANDARD TIMER MODE 

(Make/Break Relay) 

Set dipswitches as shown > 

Refer also to Diagram 01. 

Connect a dry contact such as a wall switch to 

DRY1

 

(Terminals  11  &  12).    A  Wet  (powered)  output 
connects to 

WET 2

 (Terminals 13 & 14). 

Upon  a  switch  activation  the  strike  relay  will  fire  for 
the  time  set  by  potentiometer  1  (

DOR  RL1

).    After  a 

delay  adjustable  by  potentiometer  2  (

DOO  RL2

)  the 

operator  relay  will  fire.    The  hold  time  for  relay  #2  is 
set with potentiometer 2 (

DOR RL2

). 

Most  modern  door  operators  have  built-in  time 
delays, and if so, it is usually desirable to use them to 
add  sufficient  hold-open  time. In this  case  adjust  the  
CX-29  to  send  just  a  momentary  pulse  (1  or  2 
seconds only). 

Observe  the  door  and  adjust  timers  until  desired 
operation is observed. 

The  above  dipswitch  setting  is  also  used  for 
applications  such  as  apartment  entries  with  an  
interphone panel.  Refer to Diagrams 03a & 03b. 

In  each  case  the  interphone  input  (

WET  1

)  will 

activate  the  strike  relay  only.    If  a  courtesy  switch  is 
located  in  the  vestibule,  it  is  connected  to 

DRY  2

 

(Terminals  15  &  16).    This  input  is  only  active  when 
the strike relay is energized. 

Another  application  using  this  mode  is  door 
sequencing  in  one  direction  only.    Connect  Door  1 
operator  to  relay  1,  and  door  2  operator  to  relay  2.  
The delay between the two doors is  adjusted  via the 

DOO 

RL2

 

potentiometer. 

 

For 

bi-directional 

sequencing  refer  to  specific  set-up  instructions  at 
right. 

 

 BESAM MODE 

– with N/O Fire Alarm Input 

 

Set dipswitches as shown > 

Refer also to Diagram 02. 

Connect  the  Activating  wall  switch(es)  to 

DRY  1

 

(Terminals 11 & 12).  This input will unlock and open 
the  door.  The  door  unlock  time  is  adjusted  by 

DOR RL1

  (note that this timer does not start until the 

door closes). 

The  delay  between  the  lock  relay  and  the  operator 
relay is adjusted by 

DOO RL2

, and the hold open time 

for the operator is adjusted by pot 

DOR RL2

Connect the door position switch to 

DRY 2

 (Terminals 

15  &  16).    The  switch  can  be  a  magnetic  contact 
switch  on  the  header,  or  the  HNO  terminals  on  the 
CU2  control.    Regardless,  the  contacts  need  to  be 
normally open when the door is closed. 

The  door  position  switch  tells  the  CX-29  when  the 
door  is  open  and  will  not  let  the  locks  engage  until 

AFTER

 the door has closed. 

The 

WET  2

  (Terminals  13  &14)  are  for  a  connection 

to the Fire Alarm Panel. In this mode we are looking 
for  a  N/O  connection.    When  this  contact  closes, 
Relay  1  turns  on  immediately,  unlocking  the  door.  
The wall switches are ignored.  When the Fire Alarm 
signal  drops  out,  Relay  1  releases  after  the  time  set 
by  Pot  #1,  and  the  door  re-locks  (but  not  before  the 
door closes). 

 
BESAM MODE 

– with N/C Fire Alarm Input 

 

Set dipswitches as shown > 

Refer to Diagram 02. 

Similar to previous mode with the following exception: 
the  CX-29  is  looking  for  a  N/C  Fire  alarm  signal.  
Connect  the  Wet  (powered)  output  of  the  Fire  panel 
to 

WET  2

  (Terminals  13  &  14).    When  the  fire  alarm 

input  opens,  Relay  1  will  turn  on  immediately, 
unlocking the door. 

Bi-Directional Sequencing MODE 

 

Set dipswitches as shown > 

Refer to Diagram 04. 

Turn on power and activate the Interior input (switch). 
Observe 

LED1

,  which  should  light  immediately.  The 

length of hold time is determined by adjusting the pot 
marked  DOR/RL1,  clockwise  for  more  time, 
counterclockwise for less time. 

The delay between the two doors is  adjusted  via the 
DOO RL2 potentiometer. 

After  the  above-mentioned  delay, 

LED2

  should  light.  

The length of hold time is adjusted by the pot marked 
DOR/RL2.   

The  ideal  time  delay  between  the  two  doors  is  best 
set by actual  walk-testing.  It should be set so that a 
person  can  walk  in  either  direction  without  having  to 
pause before the second door activates.  Test in both 
directions. 

Page 2 of 8 

Off / On 


Off / On 


Off / On 


Off / On 


Содержание CX-29

Страница 1: ...hout fear of malfunction SEE DIAGRAM 01 Additionally we provide a direct connection from an apartment interphone panel Only Relay 1 strike will operate when a voltage is applied to this input A vestib...

Страница 2: ...elay and the operator relay is adjusted by DOO RL2 and the hold open time for the operator is adjusted by pot DOR RL2 Connect the door position switch to DRY 2 Terminals 15 16 The switch can be a magn...

Страница 3: ..._______ Technical Data Model CX 29 Size 3 x 2 x Mounting Velcro or double sided tape Enclosure Protective paper sleeve Operating voltage 12 24 Volts AC DC Current Draw 18 mA standby 40 mA max Response...

Страница 4: ...uring 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 12 24 V AC DC Power Dry Input ie Push Switch Wet Input ie Radio Receiver Electric Strike Door Operator MOV Wire MOV supplied directly to strike or...

Страница 5: ...T7 12 24 V AC DC Power Electric Lock MOV Wire MOV supplied directly to strike or magnet Power for Strike Fire Alarm Panel with Wet output Select N O Mode 2 N C Mode 3 optional Wall Switch FIRE If usin...

Страница 6: ...12 24 V AC DC Power Optional Vestibule mounted Convenience Switch Only active when Lock relay energized Switch opens door Electric Strike Door Operator MOV Wire MOV supplied directly to strike or mag...

Страница 7: ...ence Switch Only active when Lock relay energized Switch opens door Electric Strike Door Operator MOV Wire MOV supplied directly to strike or magnet Power for Strike Apartment Interphone Panel DRY con...

Страница 8: ...TE 04 14 11 Camden Door Controls 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 12 24 V AC DC Power Door 2 Push Switch Door 2 Operator Door 1 Operator Wet output ie RF receiver optional Wet output ie...

Отзывы: