CX-12 Switching Network & Bi-Directional Door Sequencer Installation Instructions 

 
 

 
 
 
 
 
 
 
 
 
 

www.camdencontrols.com  
Toll Free: 1.877.226.3369 

File:  CX-12_NF_Rev1.doc 
Revised: 13 January 2010 
Part No.: 40-82B103 

5502 Timberlea Blvd.,  
Mississauga, ON Canada L4W 2T7 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 3 of 10 

Section 4 _________________ 
System Inspection Instructions 

After  the  Installation  and  operational  check  of  the 

system: 

1.  Place warning label on the door (as per ANSI 

A156.10  or  A156.19  guidelines).    This  will 

advise  the  person  entering  the  swing  side 

zone that the door will move. 

2.  Instruct the owner on door system operation 

and  how  to  test  it.    This  should  be  checked 

on a daily basis. 

3.  Instruct the owner on what to do if the door or 

any of its components become damaged. 

4.  Strongly  recommend  to  the  owner  that  the 

complete entry be inspected twice a year as 

part of the service agreement. 

 

Section 5_________________ 
Technical Data 

Model   

 

CX-12 

Size 

 

 

3 ¼” x 2 ¼” x ¾” 

Mounting 

 

Velcro or double-sided tape 

Enclosure 

 

Protective paper sleeve. 

Operating voltage  

12 / 24 Volts, AC / DC 

Current Draw 

18 mA standby, 

40 mA max. 

Response time   

0.3 seconds 

Inputs   

 

2 x “dry” contacts,  

                                       2 x “wet” contacts: 

                                         (3-30 V AC/DC, Optically 

                                         isolated, non-polarity 

                                         sensitive). 
Relay Output   

2 x Form C (SPDT) 

Relay contact rating 

3 amps @ 20 VDC 

Time Delays 

DOR  #1   1 to 30 seconds 

DOO # 2   1 to 30 seconds 

DOR  #2   1 to 30 seconds 

Electrical Life 

100,000 operations 

@ rated capacity 

500,000 operations 

@ ½ rated capacity 

 

Section 6_________________ 
Warranty 

Camden Door Controls guarantees the CX-12 to be free from manufacturing defects for 3 years from date of sale.  If 

during the first 3 years the CX-12 fails to perform correctly, it may be returned to our factory where it will be repaired 

or replaced (at our discretion) without charge.  Except as stated herein, Camden extends no warranties expressed or 

implied regarding function, performance or service. 
 

Questions? 

Call us toll-free at 1-877-226-3369 

 

Содержание CX-12

Страница 1: ...lock will remain energized while the DRY 2 input allows a wall switch to open the door An input on DRY 1 will always unlock and open the door SEE DIAGRAM 02b Select Relay 2 Maintained if you are conne...

Страница 2: ...Typically the access panel or time clock will be wet powered therefore connect to WET 1 Terminals 9 10 The exterior activating switch is wired to DRY 2 Terminals 15 16 This input signals the door oper...

Страница 3: ...t Section 5_________________ Technical Data Model CX 12 Size 3 x 2 x Mounting Velcro or double sided tape Enclosure Protective paper sleeve Operating voltage 12 24 Volts AC DC Current Draw 18 mA stand...

Страница 4: ......

Страница 5: ...nufacturing 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 12 24 V AC DC Power Dry Input ie Push Switch Wet Input ie Radio Receiver Electric Strike Door Operator MOV Wire MOV supplied directly to str...

Страница 6: ...rlea Blvd Mississauga Ontario L4W 2T7 12 24 V AC DC Power Electric Strike Door Operator MOV Wire MOV supplied directly to strike or magnet Power for Strike Fire Alarm Panel Shown with maintained power...

Страница 7: ...Electric Strike Door Operator MOV Wire MOV supplied directly to strike or magnet Power for Strike Exterior Switch in circuit only while Lock Relay is active If Mag lock used wire to Terminals 4 5 1 5...

Страница 8: ...12 24 V AC DC Power Optional Vestibule mounted Convenience Switch Only active when Lock relay energized Switch opens door Electric Strike Door Operator MOV Wire MOV supplied directly to strike or mag...

Страница 9: ...ence Switch Only active when Lock relay energized Switch opens door Electric Strike Door Operator MOV Wire MOV supplied directly to strike or magnet Power for Strike Apartment Interphone Panel DRY con...

Страница 10: ...SED DATE 11 16 09 Camden Door Controls 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 12 24 V AC DC Power Door 2 Push Switch Door 2 Operator Door 1 Operator Wet output ie RF receiver optional Wet out...

Отзывы: