CX-12 Switching Network & Bi-Directional Door Sequencer Installation Instructions 

 

 

 
 
 

www.camdencontrols.com  
Toll Free: 1.877.226.3369 

File: CX-12_NF_Rev1.doc 
Revised: 13 January 2010 
Part No.: 40-82B103 

5502 Timberlea Blvd.,  
Mississauga, ON Canada L4W 2T7 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 2 of 10

 

APPLICATIONS 

& SET-UP INSTRUCTIONS: 
STANDARD TIMER MODE

 

Set dipswitches as shown > 
Refer also to Diagram 01.  
Connect a dry contact such as a wall switch to 

DRY1

 

(Terminals  11  &  12).    A  Wet  (powered)  output 

connects to 

WET 2

 (Terminals 13 & 14). 

Upon  a  switch  activation  the  strike  relay  will  fire  for 

the time set by potentiometer 1 (

DOR  RL1

).  After a 

delay, adjustable by potentiometer 2 (

DOO RL2

), the 

operator relay will fire.  The hold time for relay #2 is 

set with potentiometer 2 (

DOR RL2

). 

Most  modern  door  operators  have  built-in  time 

delays, and if so, it is usually desirable to use them to 

add sufficient hold-open time. In this case adjust the  

CX-12  to  send  just  a  momentary  pulse  (1  or  2 

seconds only). 
Observe  the  door  and  adjust  timers  until  desired 

operation is observed. 
The  above  dipswitch  setting  is  also  used  for 

applications  such  as  apartment  entries  with  an 

interphone panel.  Refer to Diagrams 03a & 03b. 
In  each  case  the  interphone  input  (

WET  1

)  will 

activate the strike relay only.  If a courtesy switch is 

located  in  the  vestibule,  it  is  connected  to 

DRY  2

 

(Terminals 15 & 16).  This input is only active when 

the strike relay is energized. 
Another  application  using  this  mode  is  door 

sequencing  in  one  direction  only.    Connect  Door  1 

operator  to  relay  1,  and  door  2  operator  to  relay  2.  

The delay between the two doors is adjusted via the 

DOO 

RL2

  potentiometer.    For  bi-directional 

sequencing refer to specific set-up instructions below. 

 

EXTENDED TRIGGER MODE – RELAY 1 

 
Set dipswitches as shown > 
Refer also to Diagram 02b. 
Typically the access panel (or time clock) will be wet 

(powered) therefore connect to 

WET  1

 (Terminals 9 

&10). 
The  exterior  activating  switch  is  wired  to 

DRY  2

 

(Terminals  15  &  16).    This  input  signals  the  door 

operator (Relay 2), and is only active when the strike 

relay is energized. 

 

An  interior  switch  may  be  connected  to 

DRY  1

 

(Terminals  11  &  12).    This  input  will 

always

  unlock 

and  open  the  door  when  activated.  (Regardless  of 

the status of input connected to 

WET 1

). 

If  the  interior  switch  is  Wet  (powered)  connect  to 

WET 2 

(Terminals 13 & 14).  

EXTENDED TRIGGER MODE – RELAY 2 

 

Set dipswitches as shown > 
Refer to Diagram 02a. 
Suitable  for  connection  to  a  Fire  Alarm  Panel,  this 

mode will fire the electric lock momentarily, then hold 

in the operator relay until the input is released. 
Connect the Wet (powered) output of the Fire panel 

to 

WET 2

 (Terminals 13 & 14) 

A  device  with  a  dry  output  such  as  a  Presence 

sensor will connect to 

DRY 1

 (Terminals 13 & 14). 

Bi-Directional Sequencing MODE 

 
Set dipswitches as shown > 
Refer to Diagram 04. 
Turn on power and activate the Interior input (switch). 

Observe 

LED1

,  which should light immediately. The 

length of hold time is determined by adjusting the pot 

marked  DOR/RL1,  clockwise  for  more  time,  counter 

clockwise for less time. 
The delay between the two doors is adjusted via the 

DOO RL2 potentiometer. 
After the above-mentioned delay, 

LED2

 should light.  

The length of hold time is adjusted by the pot marked 

DOR/RL2.   
The  ideal  time  delay  between  the  two  doors  is  best 

set by actual walk-testing.  It should be set so that a 

person can walk in either direction without having to 

pause before the second door activates.  Test in both 

directions. 
If  an  emergency  (or  anti-entrapment)  switch  is 

desired in the vestibule, then wire that switch directly 

to  one  of  the  operator  inputs.  Usually  the  exterior 

door is used in this case. 
Once  the  desired  operation  is  achieved,  proceed  to 

Section 4, for 

System Inspection Instructions

 

Off / On 

Off / On 

Off / On 

Off / On 

Содержание CX-12

Страница 1: ...lock will remain energized while the DRY 2 input allows a wall switch to open the door An input on DRY 1 will always unlock and open the door SEE DIAGRAM 02b Select Relay 2 Maintained if you are conne...

Страница 2: ...Typically the access panel or time clock will be wet powered therefore connect to WET 1 Terminals 9 10 The exterior activating switch is wired to DRY 2 Terminals 15 16 This input signals the door oper...

Страница 3: ...t Section 5_________________ Technical Data Model CX 12 Size 3 x 2 x Mounting Velcro or double sided tape Enclosure Protective paper sleeve Operating voltage 12 24 Volts AC DC Current Draw 18 mA stand...

Страница 4: ......

Страница 5: ...nufacturing 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 12 24 V AC DC Power Dry Input ie Push Switch Wet Input ie Radio Receiver Electric Strike Door Operator MOV Wire MOV supplied directly to str...

Страница 6: ...rlea Blvd Mississauga Ontario L4W 2T7 12 24 V AC DC Power Electric Strike Door Operator MOV Wire MOV supplied directly to strike or magnet Power for Strike Fire Alarm Panel Shown with maintained power...

Страница 7: ...Electric Strike Door Operator MOV Wire MOV supplied directly to strike or magnet Power for Strike Exterior Switch in circuit only while Lock Relay is active If Mag lock used wire to Terminals 4 5 1 5...

Страница 8: ...12 24 V AC DC Power Optional Vestibule mounted Convenience Switch Only active when Lock relay energized Switch opens door Electric Strike Door Operator MOV Wire MOV supplied directly to strike or mag...

Страница 9: ...ence Switch Only active when Lock relay energized Switch opens door Electric Strike Door Operator MOV Wire MOV supplied directly to strike or magnet Power for Strike Apartment Interphone Panel DRY con...

Страница 10: ...SED DATE 11 16 09 Camden Door Controls 5502 Timberlea Blvd Mississauga Ontario L4W 2T7 12 24 V AC DC Power Door 2 Push Switch Door 2 Operator Door 1 Operator Wet output ie RF receiver optional Wet out...

Отзывы: