![CAMDEN CM-RQE70A Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/camden/cm-rqe70a/cm-rqe70a_installation-instructions-manual_3628432005.webp)
Page 5 of 6
CM-RQE70A PIR ‘REQUEST TO EXIT’ DETECTOR
INSTALLATION INSTRUCTIONS
Vin- C1 NO1 NC1 C2 NO2 NC2
Vin+ I1 I2 I3 GND T1 T2
12 - 24 V
DC
Power
+
-
Maglock
MOV
Door Contact Request to Exit
Push Button
Sounder
Control
Notes:
1. Relay is set to Safe Mode in
this application
2. Relay O/P2 is EMF protected.
If using O/P1a diode should be
place across the maglock
power connections.
Notes:
1. Relay is set to Safe Mode in
this application
2. Relay O/P2 is EMF protected.
If using O/P1a diode should be
place across the maglock
power connections.
Notes:
1. Relay is set to Safe Mode in
this application
2. Relay O/P2 is EMF protected.
If using O/P1a diode should be
place across the maglock
power connections.
MODE 1&2 WIRING DIAGRAM
Vin- C1 NO1 NC1 C2 NO2 NC2
Vin+ I1 I2 I3 GND T1 T2
12 - 24 V
DC
Power
+
-
Maglock
MOV
Door Contact Request to Exit
Push Button
MODE 3 WIRING DIAGRAM
1 2 3
4 5 6
7 8 9
Access
Control
Keypad/
Reader
Vin- C1 NO1 NC1 C2 NO2 NC2
Vin+ I1 I2 I3 GND T1 T2
12 - 24 V
DC
Power
+
-
Maglock
MOV
Door Contact Request to Exit
Push Button
MODE 4 WIRING DIAGRAM
REX Sensor
Keypad
Eye Beams
J2
J4
J2
J4
J2
J4
J2
1
2
3
4
5
6
7
J4
1
2
3
4
5
6
7
Description
Power +
Input 1
Input 2
Input 3
Ground
Tamper Switch 1
Tamper Switch 2
Description
Relay 1b - Normally Closed (NC2)
Relay 1b - Normally Open (NO2)
Relay 1b - Common (C2)
Relay 1a - Normally Closed (NC1)
Relay 1a - Normally Open (NO1)
Relay 1a - Common (C1)
Power -
EMF Spike
protected relay
Voltage:
12 /24V DC operation
Current Draw:
50mA (max)
Relays:
(2) Form ‘C’ (DPDT)
Contact Rating:
3A @ 30VDC
Programming:
On-board push buttons
and status LED
Modes:
- (4) Factory Default
- (1) Fully Custom
- Selectable Fail Safe/
Fail Secure
Coverage:
- Max. 10’ W x 10’ H
- Horizontal & vertical
adjustment (mechanical)
- Sensor sensitivity/range
(electronic)
Time Delay:
Adjustable, 0.5, 1, 2.5,
5, 15, 30, 45 & 60
second
Sounder:
On/Off, with adjustable
volume
Piezo Buzzer:
92db.@ 10cm.
Indicator:
Activation LED
Card or
Keypad Input:
(1) N/O
Door Position
Switch Input:
(1) N/O
Request to
Exit Input:
(1) N/O
Tamper Switch
Contact Rating:
50mA @ 12VDC
Temp Operating
Range:
32°F - 120°F (0 - 50°C)
Humidity Range:
0 - 93% non-condensing
Dimensions:
1 3/4”H x 7” W x 1 3/4” D
(43mm x 176mm x 43mm)
Weight:
0.25 lbs. (0.12kg.)
Colors:
White and black models
UL 294 Access Control Performance
Levels
1)
Access Controls, Destructive Attack
Level I (No Attack)
2)
Line Security -
Level I (No Line
Security)
3)
Endurance -
Level IV (100,000 cycles)
4)
Standby Power -
Level I (No Stand by
Power)
Power is to be supplied by a compatible
UL294 Listed control unit, or by a UL294
Listed or UL603 Listed Class 2 low-voltage
power limited power supply that is capable of
4 hours of standby power, as described in the
installation guide.
The products shall not be installed in the
fail-secure mode unless permitted by the
local authority having jurisdiction and shall
not interfere with the operation of Listed
panic hardware.
5. SPECIFICATIONS