CM-RQE70A PIR ‘REQUEST TO EXIT’ DETECTOR
INSTALLATION INSTRUCTIONS
Programming Buttons
There are no DIP switches to set on this Rex Sensor. 3 buttons are used
for all setup and programming.
The MODE Button (top):
The MODE button is used to select 1 of 4 pre-set modes or a fully
configurable custom Mode. Pressing the MODE button for the first time
will indicate which Mode the REX sensor is currently in. The REX sensor
will BEEP and the LED will flash red the number of times equal to the
MODE number. I.E. 1 Beep/Flash = Mode 1.
The Parameters Button (Middle)
This button selects the available parameters in each mode that can be
customized. From within any Mode, press this button to cycle through
the parameters.
Factory Reset
The Camden CM-RQE70A Request to Exit sensor can be reset to factory
defaults by pressing and holding the MODE and Adjust buttons. The
Sensor will start to beep. Continue holding the MODE and ADJUST
buttons while the beeping gets progressively faster until it reaches a
steady tone. When the tone stops, the REX sensor has been reset to
factory defaults and the MODE and ADJUST buttons may be released.
The Adjust Button (Bottom)
The adjust button is used to change the value of the Parameter.
Once a Parameter is selected, use the Adjust button to cycle through
the available options for each parameter as described in the below
table.
Regulatory Information
The unit shall be installed in accordance with National Electrical Code
ANSI/NFPA 70 and part 1 of the Canadian Electrical Code CSA C22.1,
Safety Standard for Electrical Installations and authorities having
jurisdiction (AHJ’s).
MODE
PARAMETER
ADJUST
LED
LENS
LOCK
DOWN
SCREW
TAMPER
SWITCH
SOUNDER
OUTPUT
RELA
Y
J4
J2
Parameter 1 beep
2 beeps
3 beeps
4 beeps
5 beeps
6 beeps
7 beeps
8 beeps
LED
Relay On
Time
0.5
1
2.5
5
15
30
45
60
Yellow Solid
Fail Mode
Safe
Secure
Red/Yellow
Flashing
Operation
Mode
Latched
Door Prop
Open Alarm
Unauthor-
ized Access
Timed
Green/Yel-
low Flashing
PIR
Sensitivity
1
2
3
4
5
Red/Green
Flashing
Sound
Volume
0
1
3
3
4
Red/Green/
Yellow
Flashing
Input #1
Unused
Press to Exit
Card/
Keypad
Door
Contact
Sounder
Input
Sequential
Input
External
Disable
External
Disable
Red
Flashing
Input #2
Unused
Press to Exit
Card/
Keypad
Door
Contact
Sounder
Input
Sequential
Input
External
Disable
External
Disable
Green
Flashing
Input #3
Unused
Press to Exit
Card/
Keypad
Door
Contact
Sounder
Input
Sequential
Input
External
Disable
External
Disable
Yellow
Flashing
Mode
Beeps
Red
LED
Flashes
Description
1
1
1
Latched Mode
2
2
2
Door Prop Alarm Mode
3
3
3
Access Control Mode
4
4
4
Secondary Activation Mode
5
5
5
Custom Settings Mode